BLOWER PERFORMANCE DATA

7

  B                 -------                 30 sec/50%             60 sec/100%

Speed Selection Dip Switches

   A       OFF    OFF   OFF   OFF   OFF   OFF

TAP      S1      S2     S3     S4      S5       S6

   B        ON     OFF   ON     OFF    ON    OFF

  A                 -------                   --------                    60 sec/100%

To

 

set Airflow:

(1) Select model and desired High Stage Cooling

Airflow. Determine the corresponding tap (A, B, C, D). Set dip
switches S1 and S2 to the appropriate ON / OFF positions.
(2) Select model and installed electric heater size.  Set dip

switches S9, S10, and S11 to the appropriate ON / OFF positions.

(3) If airflow adjustment is required set Trim Enable Switch 

 to

S8

ON (OFF = 0% Trim) and set S3 and S4 to appropriate ON / OFF

positions. Tap A is +5%,Tap B is -5%, Tap C is +10%, Tap D is
-10%.

   D        ON     ON     ON     ON     ON      ON

   Cool             Adjust          Profile
Selection       Selection      Selection
 Switches       Switches       Switches

Notes:

1. Airflow data shown applies to legacy mode operation only.
    For a fully communicating system, please see the outdoor
    unit's installation instructions for cooling and heat pump
    airflow data. See

ComfortNet System-Airflow Consideration

    section for details.

2. Airflow blink codes are approximations of actual airflow.

Profiles         Pre-Run              Short-Run               OFF Delay

   C       OFF    ON    OFF     ON    OFF    ON

  C                 -------                 7.5 min/82%           60 sec/100%

  D              30 sec/50%         7.5 min/82%           30 sec/50%

To

 

Set Comfort

 

mode:

Select desired Comfort Mode Profile (see

profiles above). Set dip switches S5 and S6 to appropriate ON /
OFF positions.

Dehumidification:

To enable, set dip switch S7 to ON. Cooling

airflow will be reduced to 85% of nominal value during cool call
when Dehum command is present. To disable, set S7 to OFF.

Continuous

 

Fan

 

Speed:

Use dip switches S12 and S13 to select

one of 4 continuous fan speeds, Tap A is 25%. Tap B is 50%, Tap
C is 75%, Tap D is 100%.

Continuous

Fan

Speed

S12

S13

OFF

ON

OFF

ON

OFF

OFF

ON

ON

Model

Speed tap

Low stage

(CFM)

High sta ge

(CFM)

A

410

610

B

565

835

C

660

970

D

765

1125

A

440

610

B

605

835

C

740

1020

D

885

1225

A

500

725

B

700

1000

C

930

1330

D

1120

1600

A

500

725

B

700

1000

C

930

1330

D

1120

1600

A

560

800

B

763

1090

C

994

1420

D

1225

1750

A

900

1350

B

1035

1550

C

1140

1700

D

1200

1800

A

1210

1610

B

1365

1815

C

1450

1920

D

1525

2025

AVPTC60D14**

Cooling/Heat Pump Airflow  Table

AVPTC24B14**

AVPTC30C14**

AVPTC36C14**

AVPTC42D14**

AVPTC48D14**

AVPTC48C14**

Содержание AVPTC24B14A

Страница 1: ...d on page 3 TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL AL RT6121004r2 March 2014 Copyright 2013 2014 Goodman Manufacturing Company L P This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed...

Страница 2: ...cedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a license to install or service heating and air conditioning equipment WARNING WARNING WARNING WARNING All Airhandlers use DIRECT DRIVE MOTORS Power supply is AC 208 230v 60 hz 1 phase A V P T C 24 B 1 4 A A PRODUCT TYPE A Air Handl...

Страница 3: ...ammable liquids or vapors in the vicinity of this appliance WARNING WARNING When installing or servicing this equipment safety clothing includ ing hand and eye protection is strongly advised If installing this equipment in an area that has special safety requirements hard hats etc ob serve these requirements To protect the unit when braz ing close to the painted surfaces the use of a quenching clo...

Страница 4: ...ed spaces where sweating may occur Appliances installed in garages warehouses or other areas where they may be subjected to mechanical damage must be suitably guarded against such damage by installing be hind protective barriers being elevated or located out of the normal path of vehicles When installed on a base the base must also be protected by similar means Heating and cooling equipment locate...

Страница 5: ...PRODUCT DIMENSIONS 5 AVPTC ...

Страница 6: ...24 000 30 000 36 000 42 000 42 000 48 000 60 000 CFM High range 1100 600 1200 600 1600 700 1660 700 1700 800 1800 1350 2000 1600 Blower Diameter 10 10 10 10 10 10 11 Width 6 8 10 10 10 10 10 Coil Drain Connect FPT Refrigerant Line Connection Size Liquid Suction Electrical Data Voltage 208 240 208 240 208 240 208 240 208 240 208 240 208 240 Electric Heat Capacity kW 3 5 6 8 10 3 5 6 8 10 5 6 8 10 1...

Страница 7: ...tion for details 2 Airflow blink codes are approximations of actual airflow Profiles Pre Run Short Run OFF Delay C OFF ON OFF ON OFF ON C 7 5 min 82 60 sec 100 D 30 sec 50 7 5 min 82 30 sec 50 To Set Comfort mode Select desired Comfort Mode Profile see profiles above Set dip switches S5 and S6 to appropriate ON OFF positions Dehumidification To enable set dip switch S7 to ON Cooling airflow will b...

Страница 8: ...cfm speed tap of ON OFF ON For match up with a 3 5 ton outdoor unit Heater kit application shall not exceed 20 kW Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON OFF OFF 3 kW heater kit is not applicable for this indoor application Htr kW 9 10 11 AVPTC24B14A AVPTC30C14A AVPTC36C14A AVPTC48C14 AVPTC42D14A AVPTC48D14A AVPTC60D14A 3 ON ON ON 730 730 NR NR 850 NR NR 5...

Страница 9: ...CALL 1 BK 3 M1 W1 RD L2 8 9 R2 HTR2 5 M2 W1 1 M4 BK C L1 8 TWO 2 ELEMENT ROWS RD DEHUM TX 3 BL TWO STAGE INTEGRATED CONTROL MODULE TL 3 GND TL NOTE WHEN INSTALLING HEATER KIT ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED MBS SPECIFIED FOR THE AIRHANDLER HEATER HTR2 BL R 6 HEAT SEQUENCER R2 RD TRANSFORMER RD FL YL M7 24 V THERMOSTAT CONNECTIONS 2 HEAT SEQUENCER R1 GN 7 WH TR BK RD FL 2 FL L...

Страница 10: ...IT ENSURE SPEED TAP MUST EXCEED OR EQUAL THE MINIMUM BLOWER SPEED MBS SPECIFIED FOR THE AIRHANDLER HEATER KIT COMBINATION ON THIS UNIT S SERIAL PLATE AFTER INSTALLING OPTIONAL HEAT KIT MARK AN X IN THE PROVIDED BELOW NO MARK INDICATES NO HEAT KIT INSTALLED FIVE 5 ELEMENT ROWS NOTE THIS LABEL MUST BE ATTACHED ON THE AIRHANDLER IN A PROMINENT LOCATION BK RD BK RD 3 Phase Heat Kit 25kW Heat Kit AVPTC...

Отзывы: