background image

10

IO-230F

     08/04

IMPORTANT NOTE:  THE EVAPORATOR COIL IS
COATED WITH OILS  THAT MAY DISSOLVE
STYROFOAM  AND CERTAIN  TYPES OF PLASTICS.
THEREFORE, A REMOVAL PUMP OR FLOAT SWITCH
MUST NOT CONTAIN ANY OF THESE MATERIALS.

Tip

: Priming the “P” trap may avoid improper draining at

the initial installation and at the beginning of the cooling
season.

ACHIEVING 2% LOW LEAKAGE RATE

Ensure that the Neoprene gasket with PSA remains intact
on all surfaces that the access panels are secured to.
These surfaces are the entire length of the wrapper and
areas between the upper tie plate, upper and lower access
panels.  Be sure that upper access panel breaker insert
gasket is intact and also flowrator gasket is installed on
the lower access panel. An additional drain hole cover is
required.

ARUF/ARPF MOTOR

Motor Speed Adjustment

The motors in all ARUF and ARPF motors are multi-speed
PSC motors.  The color of the wire coming from the motor
to the “COM” terminal on the control board defines in which
speed the motor will operate.  The black wire represents
high speed, the red wire represents low speed, and the
blue wire (select models only) represents medium speed.
To change speeds, remove the wire attached to the “COM”
terminal on the control board, and swap it with the wire (on
terminal “M1” or “M2”) with the color that will give the
desired speed.

NOTE:  In some models, not all speed taps are allowable
for certain electric heat applications.  Refer to air handler
Series and Ratings plate for minimum speed.

AEPT MOTOR

This section references the operation characteristics of
the AEPT model motor only.  The ECM control board is
factory set with dipswitch #4 in the “ON” position and all
other dipswitches in the “OFF” position. 

 For most

applications this setting is to be changed according
to the electric heat size and the outdoor unit selection.

The AEPT product uses a General Electric ECM

TM

 motor.

This motor provides many features not available on the
traditional PSC motor.  These features include:
• Improved Efficiency
• Constant CFM
• Soft Start and Stop
• Improved Humidity Control

Motor Speed Adjustment

Each ECM

TM

 blower motor has been preprogrammed for

operation at 4 distinct airflow levels when operating in
Cooling, H.P. Heating, Backup Heating (Electric Heating),
and H.P. Heating. Each mode has 4 levels to
deliver different Air Flow CFM [L/s].  The adjustment is
performed by changing the dipswitch(s) either to an “OFF”
or “ON” position.

Dipswitch Functions

The AEPT air handler motor has an electronic control that
contains an eight (8) position dip switch.  The function of
these dipswitches are shown in 

Table 9

.

Dipswitch Number

Function

1
2
3

N/A

4

Indoor Thermostat

5
6
7
8

Cooling & Heat Pump CFM

CFM Trim Adjust

Table 9

Electric Heat 

CFM Delivery
Tables 10

 and 

11

 show the CFM output for dipswitch

combinations 1-2, and 5-6.

Switch

Switch

1

2

OFF

OFF

1100

1210

ON

OFF

850

935

OFF

ON

700

775

AEPT36

OFF

OFF

2050

2150

and

ON

OFF

1750

1835

AEPT60

OFF

ON

1600

1680

ON

ON

1200

1260

Model

TABLE 10 - ELECTRIC HEAT CFM

AEPT30

EMERGENCY 

(ELECTRIC) 

HEAT

HP 

w/BACKUP 

HEAT

Switch Switch

5

6

OFF

OFF

2 ½

1100

ON

OFF

2

800

OFF

ON

1 ½

600

AEPT36

OFF

OFF

5

1800

and

ON

OFF

4

1580

AEPT60

OFF

ON

3 ½

1480

ON

ON

3

1200

Table 11 - Cooling and Heat Pump CFM

Nominal Cooling 

Tonnage

AEPT30

Model

CFM

Thermostat “Fan Only Mode”

During “Fan Only Mode” operation, the CFM output is 30%
of the cooling setting.

CFM Trim Adjust

Minor adjustments can be made through the dip switch
combination of 7-8.  The following

 Table 12

 shows the

switch position for this feature.

CFM

Switch 7

Switch 8

+10%

ON

OFF

-15%

OFF

ON

Table 12

Содержание AEPT

Страница 1: ...Company L P IO 230F 2550 North Loop West Suite 400 Houston Texas 77092 08 04 www goodmanmfg com or www amana hac com 2003 2004 Goodman Manufacturing Company L P INSTALLATION OPERATING INSTRUCTIONS FO...

Страница 2: ...092 713 861 2500 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards It...

Страница 3: ...area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation This ventilation is necessary to avoid t...

Страница 4: ...USTAGREE UNLESS USING HKR3 3 PHASE SERIES HEAT KIT THIS AIR HANDLER DOES NOT HAVE FACTORY INSTALLED ELECTRIC HEAT ELECTRIC HEAT ISAVAILABLE AS AN ACCESSORY IF INSTALLING THIS OPTION THE ONLY HEAT KITS...

Страница 5: ...OR OBJECTIONABLE FUMES ODORS INTO THE DUCTWORK The return ductwork is to be introduced into the air handler bottom upflow configuration Return Air Filters Each installation must include a return air f...

Страница 6: ...e building supply connects to the stripped black and white wires contained in the air handler electrical compartment cavity Aground screw is also contained in this area Attach the supply wires to the...

Страница 7: ...NT NOTE In order to prevent damage to the sensing bulb it is not permanently installed in the factory This bulb is to be removed prior to brazing Place in proper location after braze joint has cooled...

Страница 8: ...that allows for access to all sides To prevent the evaporator coil pan from sweating the DPI accessory insulation kit is to be used when performing this conversion Note The DPI kit is not supplied wi...

Страница 9: ...te The upper drain will become the secondary drain which is mandatory in many municipalities 7 Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubbe...

Страница 10: ...n the OFF position For most applications this setting is to be changed according to the electric heat size and the outdoor unit selection The AEPT product uses a General Electric ECMTM motor This moto...

Страница 11: ...PT MODELS SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS ROOM THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2...

Страница 12: ...UF ARPF ARPT 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R AR UNIT RED OT 1 OT 2 3 EHR 1 2 4 BROWN SEE NOTE 2 NOTES 1 OUTDOOR THERMOSTAT OT 1 SHOULD BE...

Страница 13: ...y available Follow the thermostat manufacturer s instruction for installation START UP PROCEDURE Prior to start up ensure that all electrical connections are properly sized and tightened All panels mu...

Отзывы: