APPENDIX B ELECTRICAL DATA

 

ATTENTION INSTALLING PERSONNEL

Use only the heater kit specified for each model as dictated by the table above.

MIN

MAX

Qty

RLA

LRA

Qty

HP

RLA

HP

FLA 

208/230-60-3

187

253

2

33.3

239.0

3

1/3

2.40

BD STD STATIC

5.0

12.7

460-60-3

414

506

2

17.9

125.0

3

1/3

1.20

BD STD STATIC

5.0

6.4

575-60-3

518

633

2

12.8

80.0

3

1/3

0.90

BD STD STATIC

5.0

5.1

20 TON

ELECTRICAL DATA

ID MOTOR APPL

COMPRESSOR 

(ea)

OD FAN MOTORS 

(ea)

ID FAN 

MOTOR

VOLTAGE 

LIMITATIONS

VOLTAGE  

(NAMEPLATE)

MODELS

NOTE: See unit nameplate for proper overcurrent protection.

When using electric heat kit, use of the single point kit installed in the unit is required to meet UL requirements

MIN

MAX

Qty

RLA

LRA

Qty

RLA

LRA

Qty

HP

RLA

HP

FLA 

208/230-60-3

187

253

1

29.5 195.0

1

25.0

164.0

3

1/3

2.40

BD STD STATIC

3.0

9.2

460-60-3

414

506

1

14.7

95.0

1

12.2

100.0

3

1/3

1.20

BD STD STATIC

3.0

4.6

575-60-3

518

633

1

12.2

80.0

1

9.0

78.0

3

1/3

0.90

BD STD STATIC

3.0

4.2

MODELS

15 TON

SMALLER

COMPRESSOR 

ELECTRICAL DATA

ID MOTOR

APPL

LARGER

COMPRESSOR 

OD FAN MOTORS 

(ea)

ID FAN  MOTOR

VOLTAGE 

LIMITATIONS

VOLTAGE  

(NAMEPLATE)

UNIT

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

EHK3-31

5250

EHK4-31

5250

EHK7-31

5250

15 TON

EHK3-46

5250

EHK4-46

5250

EHK7-46

5250

EHK3-60

5250

EHK4-60

5250

EHK7-60

5250

EHK3-31

7000

EHK4-31

7000

EHK7-31

7000

20 TON

EHK3-46

7000

EHK4-46

7000

EHK7-46

7000

EHK3-60

7000

EHK4-60

7000

EHK7-60

7000

EHK3-75

7000

EHK4-75

7000

EHK7-75

7000

Содержание 15 ton CPC Series

Страница 1: ...air caution is to be observed It is your responsibility to install the product safely and to educate the customer on its safe use C US NOTE Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual These installation instructions cover the outdoor installation of single package electric heating and cooling units See the Specification Sheet app...

Страница 2: ...MAGE PERSONAL INJURY REDUCED UNIT PERFORMANCE AND OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON APPROVED DEVICES WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARNING WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DE...

Страница 3: ...k NY 10018 System design and installation should also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services su...

Страница 4: ...let gas vent termination or plumbing vent outlet For specific distances required consult local codes Allow minimum clearances from the enclosure for fire protection proper operation and service access see Unit Clearances These clearances must be permanently maintained When the unit is heating the temperature of the return air entering the unit must be between 50 F and 100 F GROUND LEVEL INSTALLATI...

Страница 5: ...ispose of the boards and brace appropriately Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure Check for adequate fastening method prior to setting the unit on the curb Full perim...

Страница 6: ...ccess and to insure proper venti lation and condenser airflow The unit must not be installed beneath any obstruction The unit should be installed re mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake Insulated Panels Roof Curb Installation ROOF CURB POST INSTALLATION CHECKS After installation check the top of the curb duct connection frame and duct f...

Страница 7: ... with the unit during transport Remove wood struts mounted beneath unit base frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Important If using bottom discharge with roof curb duct wo...

Страница 8: ...ATIVE IF ASSISTANCE IS REQUIRED WARNING TO PREVENT DAMAGE TO THE WIRING PROTECT WIRING FROM SHARP EDGES FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS CAUTION CONDUIT AND FITTINGS MUST BE WEATHER TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING CAUTION For unit protection use a fuse or HACR circuit breaker that is in excess of th...

Страница 9: ...D LOW VOLTAGE BLOCK LOCATIONS FAILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS WARNING Areas Without Convenience Outlet It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable ligh...

Страница 10: ...tream of the heat exchanger A cover should be tightly attached to prevent air leaks Ductwork dimensions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission VENTING NOTE Venting is self contained CONDENSATE DRAIN CONNECTION CONDENSATE DRAIN CONNECTION A 3 4...

Страница 11: ...r Ohmmeter Test lead Minimum 16 AWG with insulated alligator clips Air temperature measuring device General refrigeration mechanics tools TEMPORARY HEATING OR COOLING If the unit is to be used for temporary heating or cooling a Startup Adjustments and Checks must first be performed in accordance with this manual Failure to comply with this requirement will void the warranty After the machines are ...

Страница 12: ...life of your belt Too loose a belt will shorten its life too tight premature mo tor and bearing failure will occur Check you belt drive for adequate run in belt tension by measuring the force required to deflect the belt at the midpoint of the span length Belt tension force can be measured using a belt tension gauge available through most belt drive manufacturers t Span length inches C Center dist...

Страница 13: ...ir Flow Adjustments 12 Make sure the unit is free of rattles and the tubing in the unit is free from excessive vibration Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges If so correct the trouble 13 Set the thermostat at the appropriate setting for cooling and heating or automatic change over for normal use 14 Be sure the Owner is instructed on the ...

Страница 14: ...CAUTION Your Self Contained PackagedAir Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly However it is recommended that the homeowner inspect the unit before a seasonal start up The coils should be free of debris so adequate airflow is achieved The return and supply registers should be free of any obstructions The filters sho...

Страница 15: ... BY QUALI FIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle INADEQUATE AIR VOLUME THROUGH INDOOR COIL When a heat pump is in the heating cycle the indoor coil is functioning as a condenser The return air filter must always be clean and sufficient air volume must pass through the indoor coil to pr...

Страница 16: ...BHP CFM BHP CFM BHP 0 2 7203 2 18 6718 1 94 0 4 7306 2 54 6777 2 14 6257 1 80 5711 1 66 0 6 7477 2 97 6899 2 51 6323 2 10 5716 1 72 5103 1 39 0 8 7112 2 96 6467 2 46 5795 2 01 5101 1 61 1 0 5983 2 38 5190 1 89 1 2 4426 1 71 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 9664 4 05 0 4 9570 4 08 9197 3 82 8702 3 51 0 6 9038 3 82 8460 3 46 7949 3 14 0 8 8171 2 93 7630 3 70 7068 2 79 1 0 ...

Страница 17: ... BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 7120 3 26 6223 2 55 1 2 6927 3 39 5924 2 61 1 4 6739 3 52 5602 2 65 1 6 6587 3 69 5245 2 67 1 8 6419 3 84 4877 2 70 2 0 6261 4 01 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9090 5 79 8297 5 06 7479 3 62 1 2 8774 5 60 7914 4 83 6989 4 07 1 4 8471 5 43 7549 4 63 1 6 8209 6 14 7194 4 45 1 8 7967 6 02 6883 5 01 2 0 6594 4 87 6 C...

Страница 18: ...uirements MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA 208 230 60 3 187 253 1 29 5 195 0 1 25 0 164 0 3 1 3 2 40 BD STD STATIC 3 0 9 2 460 60 3 414 506 1 14 7 95 0 1 12 2 100 0 3 1 3 1 20 BD STD STATIC 3 0 4 6 575 60 3 518 633 1 12 2 80 0 1 9 0 78 0 3 1 3 0 90 BD STD STATIC 3 0 4 2 MODELS 15 TON SMALLER COMPRESSOR ELECTRICAL DATA ID MOTOR APPL LARGER COMPRESSOR OD FAN MOTORS ea ID FAN MOTOR V...

Страница 19: ...19 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 ...

Страница 20: ...20 2010 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com ...

Отзывы: