APPENDIX B ELECTRICAL DATA
ATTENTION INSTALLING PERSONNEL
Use only the heater kit specified for each model as dictated by the table above.
MIN
MAX
Qty
RLA
LRA
Qty
HP
RLA
HP
FLA
208/230-60-3
187
253
2
33.3
239.0
3
1/3
2.40
BD STD STATIC
5.0
12.7
460-60-3
414
506
2
17.9
125.0
3
1/3
1.20
BD STD STATIC
5.0
6.4
575-60-3
518
633
2
12.8
80.0
3
1/3
0.90
BD STD STATIC
5.0
5.1
20 TON
ELECTRICAL DATA
ID MOTOR APPL
COMPRESSOR
(ea)
OD FAN MOTORS
(ea)
ID FAN
MOTOR
VOLTAGE
LIMITATIONS
VOLTAGE
(NAMEPLATE)
MODELS
NOTE: See unit nameplate for proper overcurrent protection.
When using electric heat kit, use of the single point kit installed in the unit is required to meet UL requirements
MIN
MAX
Qty
RLA
LRA
Qty
RLA
LRA
Qty
HP
RLA
HP
FLA
208/230-60-3
187
253
1
29.5 195.0
1
25.0
164.0
3
1/3
2.40
BD STD STATIC
3.0
9.2
460-60-3
414
506
1
14.7
95.0
1
12.2
100.0
3
1/3
1.20
BD STD STATIC
3.0
4.6
575-60-3
518
633
1
12.2
80.0
1
9.0
78.0
3
1/3
0.90
BD STD STATIC
3.0
4.2
MODELS
15 TON
SMALLER
COMPRESSOR
ELECTRICAL DATA
ID MOTOR
APPL
LARGER
COMPRESSOR
OD FAN MOTORS
(ea)
ID FAN MOTOR
VOLTAGE
LIMITATIONS
VOLTAGE
(NAMEPLATE)
UNIT
HEATER KIT
MODEL NUMBER
MINIMUM CFM
Downshot
HEATER KIT
MODEL NUMBER
MINIMUM CFM
Downshot
HEATER KIT
MODEL NUMBER
MINIMUM CFM
Downshot
EHK3-31
5250
EHK4-31
5250
EHK7-31
5250
15 TON
EHK3-46
5250
EHK4-46
5250
EHK7-46
5250
EHK3-60
5250
EHK4-60
5250
EHK7-60
5250
EHK3-31
7000
EHK4-31
7000
EHK7-31
7000
20 TON
EHK3-46
7000
EHK4-46
7000
EHK7-46
7000
EHK3-60
7000
EHK4-60
7000
EHK7-60
7000
EHK3-75
7000
EHK4-75
7000
EHK7-75
7000