System Voltage - 

That nominal voltage value assigned to a

circuit or system for the purpose of designating its voltage
class.

Nameplate Voltage - 

That voltage assigned to a piece of

equipment for the purpose of designating its voltage class
and for the purpose of defining the minimum and maximum
voltage at which the equipment will operate.

Utilization Voltage - 

The voltage of the line terminals of the

equipment at which the equipment must give fully satisfac-
tory performance. Once it is established that supply voltage
will be maintained within the utilization range under all sys-
tem conditions, check and calculate if an unbalanced condi-
tion exists between phases. Calculate percent voltage un-
balance as follows:

Three Phase Models Only

3) PERCENT VOLTAGE 

      UNBALANCE 

2) MAXIMUM VOLTAGE DEVIATIONS

FROM AVERAGE VOLTAGE

1) AVERAGE VOLTAGE

HOW TO USE THE FORMULA:
EXAMPLE: With voltage of 220, 216, and 213
1) Average Voltage = 220+216+213=649 / 3 = 216
2) Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4

3) Percent Voltage Unbalance = 100 x 

  = 

=  1.8% 

Percent voltage unbalance MUST NOT exceed 2%

.

4

216

400
216

= 100 X 

F

IELD

 D

UCT

 C

ONNECTIONS

Verify that all duct connections are tight and that there is no
air bypass between supply and return.

F

ILTER

 S

ECTION

 C

HECK

Remove filter section access panels and check that filters
are properly installed. Note airflow arrows on filter frames.

BELT DRIVE

B

EARING

 C

HECK

Prior to energizing any fans, check and make sure that all
setscrews are tight so that bearings are properly secured to
shafts.

For heat pump units, the airflow must be adjusted so that the
air temperature rise falls within the ranges given stated on
Data Plate (see Appendix A - Blower Performance).

NOTE: 

Section on high static tables may require a field motor

change.

T

ENSION

 

AND

 A

LIGNMENT

 A

DJUSTMENT

Correct belt tension is very important to the life of your belt.
Too loose a belt will shorten its life; too tight, premature mo-
tor and bearing failure will occur. Check you belt drive for
adequate “run-in” belt tension by measuring the force required
to deflect the belt at the midpoint of the span length. Belt
tension force can be measured using a belt tension gauge,
available through most belt drive manufacturers.

t = Span length, inches

C = Center distance, inches

D = Larger sheave diameter, inches
d = Smaller sheave diameter, inches

h = Deflection height, inches

DRIVE BELT TENSION ADJUSTMENT

BELT

DRIVE

Used

New

15 Ton 

B, BX Standard

4.3 to 5.5

5.5 + .5 8.2 + .5

1/4 ± 1/16

15 Ton 

B, BX

High 

Static

4.3 to 5.5

5.5 + .5 8.2 + .5

1/4 ± 1/16

20 Ton

B, BA Standard

4.3 to 5.5

5.5 + .5 8.2 + .5

1/4 ± 1/16

20 Ton

B, BA

High 

Static

4.3 to 5.5

5.5 + .5 8.2 + .5

1/4 ± 1/16

MODEL

DEFLECTION

(in)

DEFLECTION

FORCE (lbs)

SHEAVE

DIAMETER 

(in)

TYPE

RECOMMENDED POUNDS OF FORCE PER BELT

New V-belts will drop rapidly during the first few hours of use.
Check tension frequently during the first 24 hours of opera-
tion. Tension should fall between the minimum and maximum
force. To determine the deflection distance from a normal
position, measure the distance from sheave to sheave using
a straightedge or a cord. This is your reference line. On mul-
tiple belt drives, an adjacent undeflected belt can be used as
a reference.

E

VAPORATOR

 F

AN

 R

OTATION

 C

HECK

 (T

HREE

 P

HASE

 M

ODELS

O

NLY

)

Check that fan rotates clockwise when viewed from the drive
side of unit and in

 

accordance with rotation arrow shown on

blower housing. If it does not, reverse the two incoming power
cables at Single Point Power Block. In this case, repeat bear-
ing check.

Do not attempt to change load side wiring. Internal wiring
assures all motors and compressors will rotate in correct di-
rection once evaporator fan motor rotation check has been
made.

E

LECTRICAL

 I

NPUT

 C

HECK

Make preliminary check of evaporator fan ampere draw and
verify that motor nameplate amps are not exceeded. A final
check of amp draw should be made upon completion of air
balancing of the duct system (see Appendix C).

Содержание 15 ton CPC Series

Страница 1: ...air caution is to be observed It is your responsibility to install the product safely and to educate the customer on its safe use C US NOTE Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual These installation instructions cover the outdoor installation of single package electric heating and cooling units See the Specification Sheet app...

Страница 2: ...MAGE PERSONAL INJURY REDUCED UNIT PERFORMANCE AND OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON APPROVED DEVICES WARNING THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARNING WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DE...

Страница 3: ...k NY 10018 System design and installation should also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services su...

Страница 4: ...let gas vent termination or plumbing vent outlet For specific distances required consult local codes Allow minimum clearances from the enclosure for fire protection proper operation and service access see Unit Clearances These clearances must be permanently maintained When the unit is heating the temperature of the return air entering the unit must be between 50 F and 100 F GROUND LEVEL INSTALLATI...

Страница 5: ...ispose of the boards and brace appropriately Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure Check for adequate fastening method prior to setting the unit on the curb Full perim...

Страница 6: ...ccess and to insure proper venti lation and condenser airflow The unit must not be installed beneath any obstruction The unit should be installed re mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake Insulated Panels Roof Curb Installation ROOF CURB POST INSTALLATION CHECKS After installation check the top of the curb duct connection frame and duct f...

Страница 7: ... with the unit during transport Remove wood struts mounted beneath unit base frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Important If using bottom discharge with roof curb duct wo...

Страница 8: ...ATIVE IF ASSISTANCE IS REQUIRED WARNING TO PREVENT DAMAGE TO THE WIRING PROTECT WIRING FROM SHARP EDGES FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS CAUTION CONDUIT AND FITTINGS MUST BE WEATHER TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING CAUTION For unit protection use a fuse or HACR circuit breaker that is in excess of th...

Страница 9: ...D LOW VOLTAGE BLOCK LOCATIONS FAILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS WARNING Areas Without Convenience Outlet It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable ligh...

Страница 10: ...tream of the heat exchanger A cover should be tightly attached to prevent air leaks Ductwork dimensions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission VENTING NOTE Venting is self contained CONDENSATE DRAIN CONNECTION CONDENSATE DRAIN CONNECTION A 3 4...

Страница 11: ...r Ohmmeter Test lead Minimum 16 AWG with insulated alligator clips Air temperature measuring device General refrigeration mechanics tools TEMPORARY HEATING OR COOLING If the unit is to be used for temporary heating or cooling a Startup Adjustments and Checks must first be performed in accordance with this manual Failure to comply with this requirement will void the warranty After the machines are ...

Страница 12: ...life of your belt Too loose a belt will shorten its life too tight premature mo tor and bearing failure will occur Check you belt drive for adequate run in belt tension by measuring the force required to deflect the belt at the midpoint of the span length Belt tension force can be measured using a belt tension gauge available through most belt drive manufacturers t Span length inches C Center dist...

Страница 13: ...ir Flow Adjustments 12 Make sure the unit is free of rattles and the tubing in the unit is free from excessive vibration Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges If so correct the trouble 13 Set the thermostat at the appropriate setting for cooling and heating or automatic change over for normal use 14 Be sure the Owner is instructed on the ...

Страница 14: ...CAUTION Your Self Contained PackagedAir Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly However it is recommended that the homeowner inspect the unit before a seasonal start up The coils should be free of debris so adequate airflow is achieved The return and supply registers should be free of any obstructions The filters sho...

Страница 15: ... BY QUALI FIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle INADEQUATE AIR VOLUME THROUGH INDOOR COIL When a heat pump is in the heating cycle the indoor coil is functioning as a condenser The return air filter must always be clean and sufficient air volume must pass through the indoor coil to pr...

Страница 16: ...BHP CFM BHP CFM BHP 0 2 7203 2 18 6718 1 94 0 4 7306 2 54 6777 2 14 6257 1 80 5711 1 66 0 6 7477 2 97 6899 2 51 6323 2 10 5716 1 72 5103 1 39 0 8 7112 2 96 6467 2 46 5795 2 01 5101 1 61 1 0 5983 2 38 5190 1 89 1 2 4426 1 71 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 2 9664 4 05 0 4 9570 4 08 9197 3 82 8702 3 51 0 6 9038 3 82 8460 3 46 7949 3 14 0 8 8171 2 93 7630 3 70 7068 2 79 1 0 ...

Страница 17: ... BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 7120 3 26 6223 2 55 1 2 6927 3 39 5924 2 61 1 4 6739 3 52 5602 2 65 1 6 6587 3 69 5245 2 67 1 8 6419 3 84 4877 2 70 2 0 6261 4 01 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9090 5 79 8297 5 06 7479 3 62 1 2 8774 5 60 7914 4 83 6989 4 07 1 4 8471 5 43 7549 4 63 1 6 8209 6 14 7194 4 45 1 8 7967 6 02 6883 5 01 2 0 6594 4 87 6 C...

Страница 18: ...uirements MIN MAX Qty RLA LRA Qty RLA LRA Qty HP RLA HP FLA 208 230 60 3 187 253 1 29 5 195 0 1 25 0 164 0 3 1 3 2 40 BD STD STATIC 3 0 9 2 460 60 3 414 506 1 14 7 95 0 1 12 2 100 0 3 1 3 1 20 BD STD STATIC 3 0 4 6 575 60 3 518 633 1 12 2 80 0 1 9 0 78 0 3 1 3 0 90 BD STD STATIC 3 0 4 2 MODELS 15 TON SMALLER COMPRESSOR ELECTRICAL DATA ID MOTOR APPL LARGER COMPRESSOR OD FAN MOTORS ea ID FAN MOTOR V...

Страница 19: ...19 APPENDIX C UNIT DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 ...

Страница 20: ...20 2010 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com ...

Отзывы: