RD-G2+ digital repeater module with simplified wiring (non-polarised 2-wire bus
-
:
RD-G2+ digital repeater module for the G2+ system that allows the following operating modes
w
Amplifi
mode:
er
-Allows to increase the monitor bus distance, 1 RD-G2+ module "amplifier mode" and 1 RD-G2+ module "power
mode" with its power supply unit FA-G2+ are required (see page 4 and 26).
-Allows to increase the bus distance in a "power mode" or "block mode" system when it is more than 300 m
between the
and the first RD-G2+ "amplifier mode" (see page 5, 9, 29 and 35).
door panel
Important:
Up to 4 RD-G2+ modules in amplifier mode.
w
Power mode:
-Allows 32 additional monitors (max. 4 RD-G2+ and up to 128 elements).
-Allows risers/verticals installation ( a . 32 risers
, up to 32 monitores per riser and up to128 monitors in
/vertical
m x
s
installation.
-Up to 4 door panels.
-Door panels with EL632-G2 + SE video module with 'V04' or later for compatibility with this operating mode.
,
w
Block mode:
-Allows an installation with up to 4 general door panels and up to 32 buildings with interior door panels.
-Up to 4 door panels e
building
p r interior
.
-Up to 4 generals coded panels.
-Up to 32 i terior buildings up to 4 interior door panels per interior building
n
(
).
-RD-G2+ module
“
block mode
”
with its FA-G2+ power supply per inner building.
-Door panels with EL632-G2 + SE video module with 'V04' or later for compatibility with this operating mode.
,
- FA-G2+ power supply unit is required for each RD-G2+ module in "power mode" and "block mode".
- It is necessary to configure the operating mode.
-
).
DIP switches (operating mode, building address number
“
”
and end of line
block mode
-
Led.
Power supply status
RAP-2150 (GOLMAR) CABLE CHARACTERÍSTICS
SAFETY PRECAUTIONS
-
Always disconnect the power supply
before installing or making modifications to the device.
- The fitting and handling of this device must be carried out by
authorised personnel.
- The wiring must run at list
40 cm. de cualquier otra instalación.
- Install the RD-G2+ module in a dry protected location free from risk of dripping or splashing water.
- Install the
module
“
”
and
“
”
together with its FA-G2+ power supply
RD-G2+
power mode
block mode
.
-
Avoid locations that are humid, dusty or near heat sources.
-
Ensure that the air vents are free from obstruction so that air can circulate freely.
-
To prevent damage, the RD-G2 module must be firmly secured in place.
+
RD-G2+ DIGITAL REPEATER
Electrical resistance of the conductor at 20°C
ELECTRICAL CHARACTERISTICS
19 5 /Km
.
Capacity between conductors
Characteristic impedance
VALUES
CONSTRUCTION CHARACTERISTICS
Class V
VALUES
Flexible 1mm twisted pair polished copper conductor
2
45pf/m 10%
100 10%
15 V/m
Wiring