All gas piping must be installed to comply with local codes, or, in the absence of local
codes, with the latest edition of the National Fuel Gas Code ANSI Z223.1.
Unions in gas lines shall be of ground joint type. Compounds used on threaded joints of
gas piping must be resistant to the action of liquefied petroleum gas. Gas piping must be
of sufficient size to provide a minimum natural gas pressure at the appliance of 7" water
column or 11" for L.P. gases for the purpose of input adjustment. The maximum inlet gas
pressure to the unit must not exceed 10" for natural gas, and 13" for L.P. gases. If this
unit is to be supplied with L.P. gas (bottled propane) the tank or bottle supplying the gas
must have a regulator that reduces the gas pressure to between 11 and 13 inches water
column. The control will not operate with gas line pressure directly from the tank and may
leak gas due to this excessive pressure.
DANGER:
OPERATION OF THIS UNIT ON L.P. GAS WITHOUT AN APPROVED
REGULATOR AT THE SUPPLY CONTAINER WILL LEAD TO GAS LEAKS AT THE
CONTROL WITH POSSIBLE FIRE OR EXPLOSION.
Include a manual shut-off valve and union in the line so the control or heater may be
disconnected for servicing. Include a drip leg and a plugged 1/8" N.P.T. tapping into the
line also. The tapping must be accessible for the test gauge connection immediately
upstream of the gas supply connection to the unit. Use a soap and water solution or
liquid gas leak detector to coat each joint in the piping system and look for bubbles
which indicate gas leaks. Repair all gas leaks.
CAUTION:
THE APPLIANCE AND ITS APPLIANCE MAIN GAS VALVE MUST
BE DISCONNECTED FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF
1/2 PSI (3.5 KPA).
THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY
CLOSING THE EQUIPMENT SHUTOFF VALVE DURING ANY PRESSURE TESTING OF
THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN
1/2 PSI (3.5 KPA).
DANGER:
DO NOT USE CANDLES, MATCHES OR OTHER IGNITION SOURCES WHEN
CHECKING FOR LEAKS. FUEL GASES ARE VERY FLAMMABLE AND IN CERTAIN
CONCENTRATIONS, EXPLOSIVE. CHECKING FOR LEAKS WITH AN OPEN FLAME MAY
LEAD TO FIRE OR EXPLOSION.
GAS PIPING AND GAS PRESSURE REQUIREMENTS
5
Содержание LFP9618
Страница 13: ...13 WIRING DIAGRAM see below 6003 3V Model Different valve may use pin connector 6003V 6K Model ...
Страница 17: ...17 ...
Страница 19: ...19 Inc ...