background image

All gas piping must be installed to comply with local codes, or, in the absence of local 
codes, with the latest edition of the National Fuel Gas Code ANSI Z223.1.

Unions in gas lines shall be of ground joint type. Compounds used on threaded joints of 
gas piping must be resistant to the action of liquefied petroleum gas. Gas piping must be 
of sufficient size to provide a minimum natural gas pressure at the appliance of 7" water 
column or 11" for L.P. gases for the purpose of input adjustment. The maximum inlet gas 
pressure to the unit must not exceed 10" for natural gas, and 13" for L.P. gases. If this 
unit is to be supplied with L.P. gas (bottled propane) the tank or bottle supplying the gas 
must have a regulator that reduces the gas pressure to between 11 and 13 inches water 
column. The control will not operate with gas line pressure directly from the tank and may 
leak gas due to this excessive pressure.

DANGER:

 OPERATION OF THIS UNIT ON L.P. GAS WITHOUT AN APPROVED 

REGULATOR AT THE SUPPLY CONTAINER WILL LEAD TO GAS LEAKS AT THE 
CONTROL WITH POSSIBLE FIRE OR EXPLOSION.

Include a manual shut-off valve and union in the line so the control or heater may be 
disconnected for servicing. Include a drip leg and a plugged 1/8" N.P.T. tapping into the 
line also. The tapping must be accessible for the test gauge connection immediately 
upstream of the gas supply connection to the unit. Use a soap and water solution or 
liquid gas leak detector to coat each joint in the piping system and look for bubbles 
which indicate gas leaks. Repair all gas leaks.

CAUTION:

 THE APPLIANCE AND ITS APPLIANCE MAIN GAS VALVE MUST 

BE DISCONNECTED FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY 
PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF  
1/2 PSI (3.5 KPA).

THE APPLIANCE MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY 
CLOSING THE EQUIPMENT SHUTOFF VALVE DURING ANY PRESSURE TESTING OF 
THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 
1/2 PSI (3.5 KPA).

DANGER:

 DO NOT USE CANDLES, MATCHES OR OTHER IGNITION SOURCES WHEN 

CHECKING FOR LEAKS. FUEL GASES ARE VERY FLAMMABLE AND IN CERTAIN 
CONCENTRATIONS, EXPLOSIVE. CHECKING FOR LEAKS WITH AN OPEN FLAME MAY 
LEAD TO FIRE OR EXPLOSION.

GAS PIPING AND GAS PRESSURE REQUIREMENTS

5

Содержание LFP9618

Страница 1: ...S Z21 50 2014 WARNING THIS FIREPLACE MUST BE INSTALLED USING AN APPROVED POWER VENT FAN SEE INSTALLING CHIMNEY VENT SYSTEMS SECTION OF THIS MANUAL FOR APPROVED FAN MODELS AND SPECIFICATIONS MODEL LFP9618 POWER VENTED TOP VENT GAS FIREPLACE 2 21 ...

Страница 2: ...ssure Requirements 5 Installation Instructions 6 9 Lighting Instructions 14 15 Trouble Shooting 16 17 Replacement Parts 18 2 INSIDE ROOM FLUSH MOUNT CHASE INSTALLATION OPTIONS Figure 2 1 Glass Installation Flame Stabilizer Installation 10 11 Maintenance Instructions Wiring Diagram 12 13 Operating Guidelines 12 ...

Страница 3: ...TERIOR VIEW Left Outside Air Control Damper Control Lever Pilot Assy Flame Sensor Right Outside Air Control On Off Switch LEFT RIGHT 3 Valve Access Door OUTSIDE AIR CONNECTIONS LFP9618 COMPONENT LOCATIONS ...

Страница 4: ...2014 The design of this FIREPLACE has been tested and is listed with PFS CORPORATION in accordance with THE AMERICAN NATIONAL STANDARDS INSTITUTE ANSI Z21 50 2014 This manual serves only as a basic guideline for installation and use of this and gas piping The complete installation must be in accordance with local codes and ordinances or in the absence of local codes with the American National Stan...

Страница 5: ...S LEAKS AT THE CONTROL WITH POSSIBLE FIRE OR EXPLOSION Include a manual shut off valve and union in the line so the control or heater may be disconnected for servicing Include a drip leg and a plugged 1 8 N P T tapping into the line also The tapping must be accessible for the test gauge connection immediately upstream of the gas supply connection to the unit Use a soap and water solution or liquid...

Страница 6: ...cted of 2 x 4 lumber or heavier The framing headers may rest on the standoffs Refer to Figure 7 1 for and framing reference dimensions CAUTION VERIFY FIREPLACE DIMENSIONS FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING CONSTRUCTION BEGINS Determine the exact position of the so that the vent run can be planned Figure 2 1 shows possible locations for the inside of a room mount in a chase Us...

Страница 7: ... DIMENSIONS LFP9618 LFP 9618 A 106 B 111 C 96 D 104 3 4 Model LFP9618 is approved to be used with 10 B Type Gas Vent The Fireplace must be installed with an Enervex Model RS 14 Exhaust Fan PDS 1 or ADC 100 Draft Switch that is connected to this Fireplace WARNING This Fireplace must not be installed without Exhaust Fan Golden Blount Inc can supply the Enervex products or they can be purchased throu...

Страница 8: ...VENT EXHAUST FAN 1 800 833 1134 WARNING This gas appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance Note a draft hood is installed and is in the same atmospheric pressure zone as the combustion air inlet to the appliance and is located so that the relief opening is accessible for checking vent operation Minimum Vent Length 5 Maximum Vertical Run 50 Ma...

Страница 9: ... choice Do not install a combustible mantle or other combustible projection above the opening unless it is a minimum of 12 inches above top of opening Figure 9 2 CAUTION All joints between the wall and the surround Top and Sides can only be sealed with non combustible material Only non combustible material can be applied as facing to the surround Figure 9 2 Hearth Extension A Hearth Extension may ...

Страница 10: ...d Fireglass to enhance the overall appearance 2 Fill the burner tray below and up to the top of the burner ports Do not cover burner ports 3 Distribute additional glass around front sides and rear of burner tray covering floor area Figures 10 1 10 2 GLASS INSTALLATION CONT Figure 10 2 ...

Страница 11: ...ER THAT HELPS BURNER FLAME MAINTAIN A VERTICAL POSITION LOCATE GLASS FLAME STABILIZER CLIPS AND INSERT GLASS FLAME STABILIZER INTO THEM CENTER GLASS FLAME STABILIZER SO THAT THERE IS SAME CLEARANCE ON LEFT AND RIGHT SIDES 3 GLASS FLAME STABILIZER SHOULD BE SEATED AGAINST FIREPLACE FLOOR AS SHOWN ...

Страница 12: ...E BEGINNING OF EACH HEATING SEASON WARNING THE FLOW OF COMBUSTION AND VENTILATION AIR MUST NOT BE OBSTRUCTED When lit for the time the appliance will emit a slight odor for an hour or two This is due to paint and lubricants used in the manufacturing process The main burner characteristics are steady not lifting or Typically the top 1 4 inch of the sensor should be engulfed in the pilot A periodic ...

Страница 13: ...13 WIRING DIAGRAM see below 6003 3V Model Different valve may use pin connector 6003V 6K Model ...

Страница 14: ...EC SPARK TO PILOT NOTE DAMPER CONTROL LEVER MUST BE IN THE OPEN POSITION TO IGNITE GAS VALVE An approved Power Vent Fan must be installed prior to operating this Fireplace See page 8 of this manual for fan information D 1 STOP Read the safety information above 2 After installing Enervex RS 14 Power Vent and Proven Draft Switch you can proceed with lighting of this Fireplace 3 Set the switch to OFF...

Страница 15: ... DO NOT use a telephone inside of building 3 Shut off gas at L P tank outside of building 4 Telephone gas company and department Ask instructions Before hanging up give your name address and phone number DO NOT go back into building If your L P tank runs out of fuel turn off gas at the appliance After L P tank is appliance TO TURN OFF GAS TO APPLIANCE must be re lit according to manufacturer s ins...

Страница 16: ...16 Enervex Fan not operating and connecting Draft Switch to operate Fireplace 9 Check to see if Enervex Fan is running and Draft Switch is closing Fireplace circuit 9 13 ...

Страница 17: ...17 ...

Страница 18: ...REPLACEMENT PARTS THE FOLLOWING REPLACEMENT PARTS ARE AVAILABLE FROM YOUR GOLDEN BLOUNT DEALER 1 2 3 6 10 11 12 16 15 4 14 13 18 7 8 ...

Страница 19: ...19 Inc ...

Отзывы: