Low pressure regulator Type NDR 0515 and Type NDR 0516
9 / 12
If bubbles form, tighten the connections (see ASSEMBLY). If the leaks cannot be repaired,
the product must not be used.
In Germany, the test specifications according to Item 8.3 TRF 2012 must also be taken into
account.
For testing at the test connection, we recommend the leak and function tester type DFP25
(Part no. 02 617 05).
START-UP
After the product has been ASSEMBLED and LEAK TESTING has been carried out
successfully, it is immediately ready for operation.
1. All shut-off fittings on the connected devices must be closed.
2. Slowly open the withdrawal valve or the gas cylinder valve.
3. Observe the assembly and operating instructions of the connected devices.
If you open the withdrawal valve or the gas cylinder valve too quickly, this can result in
a short-term pressure increase that triggers the overpressure shut-off device (OPSO).
If the visual indicator switches to
RED
during start up, do the following:
•
Allow a few short bursts of gas to escape from the connected device to equalise the
pressure.
•
If the pressure does not equalise and the OPSO cannot be unlocked
(visual indicator remains
RED
), the pressure regulator must be replaced.
OPERATION
The product requires no operation while it is running.
TROUBLESHOOTING
Fault cause
Action
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Close the gas supply.
Do not use any electric switches.
Do not use a phone in the building.
Ventilate rooms well.
Shut down the LPG system.
Contact a specialised company.
Abnormal flame pattern of
non-adjustable pressure
regulator
Compare the nominal outlet pressure with the nominal
connection pressure:
if they do not correspond, replace the pressure regulator
or the gas appliance
Measure the outlet pressure; outlet pressure is not within
the specified limits:
check the system configuration
pressure regulator is defective, replace
check the gas filter