WARNING
Always burn the unit at a low heat for the first few fires to enable good dilation of the components.
Handles are hot when the unit is functioning.
Always ensure that your installation is in conformity with the National Legislation of the country and
region where the unit is installed.
GENERAL SPECIFICATIONS
CHIMNEY AND ITS CONNECTION
Before installation, ensure that the chimney is in good condition and that the duct ensures a
satisfactory draught.
Depression must be 1.5mm water gauge, at least. i.e. 1.5mm WG (0.06’’WG)
The chimney should be well insulated
It must be airtight and its cross section area must be constant.
The minimum area of cross section must be no less than 2.5dm2 (39sq inches) which corresponds to
180mm. On the other hand, an excessively large area of cross section produces too great volume,
which is difficult to heat and is one of the principle causes of poor draught.
A comparison cannot be made with previous units’ results, where the air supply is different.
An efficient chimney must be built with materials, which have poor heat conductive capacity.
The chimney must only vent one fireplace.
It must suitably emerge into free air at least 0.40m above the rooftop or any other obstacle situated
within distance of 8 meters from the chimney.
Any chimney deviated must be very open angled.
The draught must range between 1.5mm WG and 2mm WG when burning normally and must drop at
0.5mm WG roughly when burning slowly. If the draught is too high, a damper should be fitted. If the
draught is insufficient, check if the characteristics of the chimney comply with those prescribed in this
paragraph.
If the cross-section of the fireplace is too large, the volume to be heated is too big and the draught
won’t be able to reach satisfactory levels. In such cases, the chimney shall require internal piping with
tubes adapted to wood fires. The pipes diameter should in no case be inferior to 180mm.
Never obstruct the air louver installed in the door.
The height of the flue should be no less than 6 meters and the top should be above the ridge of the
roof and terminate without any form of restriction in the open air.
It is recommended that a well sealed sweeping/cleaning trap is fitted approximately 50cm below the
axis of the smoke duct.
Never reduce the diameter of the extraction pipe designed for the appliance. The majority of problems
experienced during the operation of the units are related to an adjustment in the specified chimney
conduit. We cannot emphasize this enough.
The origin of the chimney must be located in the same room as the appliance.
The connection between the stoves pipe and the chimney must be perfectly airtight.
Note: It is essential to check that the room in which the appliance is installed is well ventilated to provide
adequate air supply.