  ngs Menu

The Advanced System Se   ngs Menu provides for addi  on system setup op  ons. These se   ngs can 
a

 ect system opera  on and should only be changed by quali

fi

 ed HVAC installers.

To access the Advanced System Se   ngs menu, 

fi

 rst press and hold the 

FAN

 bu  on to get into the 

Setup menu. While in the Setup Menu, press and hold both the 

FAN

 and 

 bu  ons for 5 seconds. 

• Use the 

 bu  ons to scroll through the menu op  ons to the desired se   ng. 

• Press 

SELECT

 (Mode) bu  on to change a se   ng. Once it begins to 

fl

 ash, use the 

 bu  ons to 

select the desired se   ng. 

• Press the 

SELECT

 bu  on to accept the new se   ng (

fl

 ashing will stop).

Feature

Description

Range

Default 
Setting

Test Mode

Test mode shortens the system built-in delays (like 
MOT and MRT)
Y = Test mode on. Reduces all delays to 10 seconds for 
quicker system tes  ng
N = Test mode o

 . Normal system delays

Y or N

N

Aux Heat 
Enable (Heat 
Pump Systems 
only)

Enables the auxiliary heat opera  on.
Typically the auxiliary heat will be heat-strips in a heat 
pump system.

Y or N

N

2nd Stage 
Heat Enable

Enables the second stage heat opera  on

Y or N

N

2nd Stage Cool 
Enable

Enables the second stage cool opera  on

Y or N

N

Minimum run 

 me

Sets the Minimum Run Time (MRT) delay before a 
hea  ng/cooling cycle can turn o

 .

Sets hea  ng/cooling cycle   me. Prevents rapid on/o

  

cycling.

1-9

3

Minimum O

  

 me

Sets the Minimum O

  Time (MOT) delay before 

another hea  ng/cooling cycle can begin. Provides 
compressor short cycle protec  on. “Wait” is displayed 
on screen when ac  ve.

5-9 Minutes

5

Heat Setpoint 
Max.

Sets the maximum hea  ng setpoint value.
Will not ramp or accept setpoints higher than this 
maximum

55F to 96F
(4C to 43C)

90F 
(32C)

Cool Setpoint 
Min.

Sets the maximum hea  ng setpoint value

60F to 99F
(6C-45C)

60F
(15C)

Heat Blower 
O

  Delay

Sets the system blower delay o

    me a  er a heat call 

ends (fan purge)

0 to 9 
seconds

0 (o

 )

Cool Blower
O

  Delay

Sets the system blower delay o

    me a  er a cool call 

ends (fan purge)

0 to9 
seconds

0 (o

 )

Содержание GC-TBZ48

Страница 1: ...MODE FAN 74 Off Auto F Model GC TBZ48 Battery Powered Z Wave Thermostat Installation Operation Guide...

Страница 2: ...MRT 11 Entering Menu Mode 12 Menu Mode Naviga on 12 System Menu 13 System Type 13 Fan Type For Standard HVAC systems only 13 Changeover Type For Heat Pump HVAC Systems Only 13 Z Wave Installa on 14 In...

Страница 3: ...format display with white backlight Hea ng and cooling setup display op ons System mode OFF Heat Cool Auto E Heat Fan mode control and display Auto ON Changeover type for Heat Pump HP systems On scree...

Страница 4: ...WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK PANEL INTERNAL RC RH JUMPER C WIRE IS NOT REQUIRED FOR BATTERY OPERATION C WIRE IS REQUIRED FOR 24VAC OPERATION DEFAULTTHERMOSTAT SETUP TYPE STAND...

Страница 5: ...C SYSTEM BLUE RED WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK PANEL Y2 Y1 G R C R W1 O INTERNAL R R JUMPER C WIRE IS NOT REQUIRED FOR BATTERY OPERATION BATTERIES ARE NOT REQUIRED FOR 24VAC P...

Страница 6: ...re typically a red wire Ba ery Power Powering the thermostat from ba eries does not require a C wire connec on DO NOT install ba eries if the thermostat is powered by 24VAC They are not required for b...

Страница 7: ...hooting later if needed Terminal Typical Wire Color Function Y YELLOW Cool W WHITE Heat G GREEN Fan R RED 24VAC Return C BLUE 24V Common typically BLUE When the wire is present the thermostat can be p...

Страница 8: ...nel of thermostat Mount the thermostat back panel on the wall See Figure 4 1 Use the two 2 wall anchors and two 2 Phillips screws provided to mount the back panel 2 Level as needed Figure 4 Mounting t...

Страница 9: ...ese are internally jumpered together If installing a Standard HVAC system connect the wires from the HVAC system to the corresponding terminals on the thermostat back terminal block Use the table belo...

Страница 10: ...low as a guideline for connec ng the wires Wire Terminal Y2 Connect to the Y2 terminal 2 stage systems only Y or Y1 Connect to the Y1 terminal G Connect to the G terminal COOL Rc Connect to RC termina...

Страница 11: ...minal Y Connect to the Y1 terminal G Connect to the G terminal R Connect to either R terminal C Connect to the C terminal The C wire 24VAC common Heat Pump systems typically have the C wire connected...

Страница 12: ...s on bo om of case See Figure 12 Install the four 4 type AA ba eries and assemble as shown in Fig 13 Figure 12 Opening Battery Case Cover Figure 13 Battery Installation MODE MODE FAN FAN BODY FRONT PA...

Страница 13: ...h the first press Wait Mode The thermostat has a Minimum O Time MOT delay a er any hea ng or cooling cycle ends This delay prevents rapid hea ng cooling cycles and also provides short cycle protec on...

Страница 14: ...bu ons to scroll through the following menu items Figure 15 Menu Navigation The following menu items are displayed in order SETUP user preference se ngs SYSTEM HVAC system setup Z WAVE install uninst...

Страница 15: ...e hea ng system type For Gas heat select GAS This is the default se ng For Electric heat press the bu ons to change to ELECTRIC Press SELECT to set Press DONE to exit Changeover Type For Heat Pump HVA...

Страница 16: ...thermostat to network 7 Display line should flash WAIT then SUCCESS if Z Wave connec on is made 8 If Z Wave does not connect to controller WAIT then FAIL will flash in status display line 9 If thermo...

Страница 17: ...7 Press SELECT FAN Done FAN Done INFO Menu The INFO menu displays informa on about the thermostat Use the bu ons to scroll through the various items MODEL GC TBZ48 VERSION Thermostat firmware version...

Страница 18: ...s Y or N N Aux Heat Enable Heat Pump Systems only Enables the auxiliary heat opera on Typically the auxiliary heat will be heat strips in a heat pump system Y or N N 2nd Stage Heat Enable Enables the...

Страница 19: ...egrees 2 Hea ng Stage 2 O Threshold Sets the delay from setpoint that stage 2 hea ng stops Stage 2 turns o at setpoint Delta Stage 2 0 to 6 degrees 0 Aux Heat On Threshold Sets the delta from setpoint...

Страница 20: ...ive displayed System is ON and cooling blinking System is ON and cooling Minimum Run Time MRT delay is active NOTE Degrees C Celsius are shown in 5 degree increments Degrees F Farenheit are shown in 1...

Страница 21: ...l system mode Heat E for Emergency Heat will be displayed if the HVAC System Type is set to Heat Pump If there is a compressor failure with the Heat Pump system se ng the mode to Emergency Heat will a...

Страница 22: ...the hea ng setpoint lower if the cooling setpoint is set below the current hea ng setpoint A 3 degree separa on is maintained between the hea ng and cooling setpoints The same is true for raising the...

Страница 23: ...s Use the FAN bu on to select the HVAC system s fan mode Auto Fan automa cally operated by the HVAC system normal se ng On Manual Fan mode Fan stays on un l mode is changed back to Auto independent of...

Страница 24: ...can be set to 0 which will keep the backlight on con nuously SENSOR CALIBRATION Change the temperature calibra on by 7 degrees Press the UP or DOWN arrow bu ons to change to the desired display temper...

Страница 25: ...DONE DONE INFO Menu The INFO menu displays informa on about the thermostat Use the bu ons to scroll through the various items MODEL NTBZ48 VERSION Thermostat firmware version ZWAVE Z Wave firmware ve...

Страница 26: ...acy 1 F 0 5 C Remote Control Via Z Wave Standard Gas Electric HVAC Systems 2 stage hea ng 2 stage cooling Heat Pump HVAC System 3 stage hea ng 2 stage cooling Thermostat Connections Uses standard ther...

Страница 27: ...could void the user s authority to operate the equipment Industry Canada Notices IC 9374A TBZ48 This device complies with Industry Canada license exempt RSS standard s Opera on is subject to the follo...

Страница 28: ...the USA and Canada Dial 855 2GIG TECH 855 244 4832 Email 2gigtechsupport nortek com Visit website for technical support hours of operation For technical support outside of the USA and Canada Contact...

Отзывы: