BATTERY CHARGING PROFILE CHART
1. When the battery type is sealed, gel, flooded, the adjusting range of equalizing duration is 0 to180min and boost duration is 10 to180min.
2. When setting a custom “User” battery type, (for example: a LiFePO4) use these rules when setting voltage parameters.
• Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging Voltage ≥ Float Charging
Voltage > Boost Reconnect Charging Voltage.
• Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage
• Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage.
• Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥ Discharging Limit Voltage.
• Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage.
No Power to LCD Screen
Solution 1
Check the connection between the DuraLite Kit and the controller, and the controller and the battery. The controller requires a minimum
voltage of 8v to run.
Solution 2
Your battery may be too far discharged to accommodate the controller. Keep the solar kit plugged in and placed in full sun for a few hours
and try the controller again.
FLASHING
Solution
This is an Overvoltage Error. The battery voltage is too high. Disconnect the DuraLite kit and plug in a power draw to lessen the voltage
in the battery.
FLASHING
Solution
This is an Over Discharge Error. The battery voltage is too low. Connect the DuraLite kit to charge the battery.
11. ERRORS AND TROUBLESHOOTING