background image

[page 10]  |  gpelectric.com

®

The SOLAR CONTROLLER Maximum 37.5A rating is based on a 30-amp total maximum short circuit current rating (Isc) from the solar 

modules nameplate ratings. The National Electric Code specifies the PV equipment/system rating to be 125% of the maximum Isc from the 

PV module ratings (1.25 times 30 = 37.5A). E.G. Three modules in parallel with an Isc of 7 amps each equal a total Isc input of 21 amps. 
When selecting PV modules for use with the SOLAR CONTROLLER do not exceed a total nameplate Isc current of 30A. Solar modules 
list the Isc amps on their nameplate label.

The controller will not work unless there is a battery connected to the Battery 1 terminals.

WARNING: When the photovoltaic (solar) panel is exposed to light, it supplies a dc voltage to this equipment.

1) Automatic cycle interface

Display

: PV voltage, PV current, PV power, Battery voltage and Battery temperature

2) Clear the generated energy

Operation: 

Step 1

: Press the “SET” button and hold 5s under the PV power interface and the value is flashing.

Step 2

: Press the “SET” button to clear the generated energy

Note

8. SOLAR CONTROLLER OPERATING INSTRUCTIONS

CHOOSING A BATTERY

Содержание GP-DURALITE-100

Страница 1: ...100 GP DURALITE 100E 2021 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power Headquarters 201 710 Redbrick St Victoria BC Canada V8T 5J3 Tel 1 866 247 6527 MANUAL_GP...

Страница 2: ......

Страница 3: ...ECIFICATIONS 8 6 2 SOLAR CONTROLLER WARNINGS 9 7 CHOOSING A BATTERY 9 8 SOLAR CONTROLLER OPERATING INSTRUCTIONS 10 9 LED INDICATORS 11 10 BATTERY CHARGING PROFILE CHART 11 11 ERRORS AND TROUBLESHOOTIN...

Страница 4: ...re in a well ventilated space away from sparks for open flames Wiring connections Ensure all connections are tight and secure Loose connections may generate sparks and heat Be sure to check all connec...

Страница 5: ...e controller 4 USB ports LED indicator 5 DC output port 6 Battery clamps 7 Quick connect dust cover 8 SAE Solar Plug for connecting to RVs 9 Ring terminals for permanent mounting 10 2 Pin XLR Connecto...

Страница 6: ...on 1 Handle 2 Foldable legs 3 USB ports LED indicator 4 DC output port 5 2x Extension Cable 6 Barrel Connector for connecting to portable power stations 7 MC4 Connector for connecting to portable powe...

Страница 7: ...adjusted to track the sun s movement throughout the day southerly exposure Stabilize the panel by inserting a tent peg into the grommet hole at the base of each leg 5 SET UP TYPE MODULE SIZE CLOSED M...

Страница 8: ...ys Charging Current Battery Voltage and Battery State of Charge Reverse Polarity protected Temperature Compensated RoHS Compliant environmentally safe Accepts up to 3 DuraLite Kits 300 watts of solar...

Страница 9: ...nd working around batteries Do not exceed the SOLAR CONTROL LER max current ratings The maximum current of the solar system is the sum of paral lel connected PV module rated short circuit Currents Isc...

Страница 10: ...do not exceed a total nameplate Isc current of 30A Solar modules list the Isc amps on their nameplate label The controller will not work unless there is a battery connected to the Battery 1 terminals...

Страница 11: ...V 15 0V 15 0V 14 8 9 17V Over Voltage Reconnect Voltage 15 0V 15 0V 15 0V 14 8 9 17V Equalize Charging Voltage 14 6V 14 8V 9 17V Boost Charging Voltage 14 4V 14 2V 14 6V 14 8 9 17V Float Charging Volt...

Страница 12: ...TEM SEALED GEL FLOODED LIFEPO4 USER Equalize Duration 120min 120min 0 180min Boost Duration 120min 120min 120min 120min 10 180min LFP1 is used for 12V Lithium batteries LFP2 is used for 24V lithium ba...

Страница 13: ...g Reconnect Voltage Under Voltage Warning Voltage Discharging Limit Voltage Boost Reconnect Charging voltage Low Voltage Disconnect Voltage No Power to LCD Screen Solution 1 Check the connection betwe...

Страница 14: ...he meter value on the SOLAR CONTROLLER display is an approximate reading intended for indication purposes only There is an approximate 0 1 VDC inherent error present that may be accentuated when compa...

Страница 15: ...are followed Even if it appears the system is not functioning it should be treated as a fully functioning system generating live power Display Reading Blank Time of Day Daytime Nighttime Possible Caus...

Страница 16: ...or correct wire polarity Check that all connections are clean tight and secure Shorten the distance from the controller to battery or obtain larger gauge wire It is also possible to double up the exis...

Страница 17: ...cross the solar module may cause the power output to be significantly reduced Overcast days may also cut the power output of the module Further Steps if required Disconnect one or both panel wires fro...

Страница 18: ...expansion panel You do not need to utilize all 3 connections on the branch connector for the expansion kit to function Connections are to be made red to red black to black You will hear a click when...

Страница 19: ...ot limited to improper environmental protection and improper hook up Vandalism or theft Acts of God including lightning floods earthquakes fire and high winds Damage in handling including damage encou...

Страница 20: ...2021 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power Headquarters 201 710 Redbrick St Victoria BC Canada V8T 5J3 Tel 1 866 247 6527 MANUAL_GP DURALITE 100 100E...

Отзывы: