GNB TUBULAR-LMX Скачать руководство пользователя страница 1

POST THESE INSTRUCTIONS IN THE BATTERY MAINTENANCE AREA

TUBULAR-LMX™ LOW MAINTENANCE MOTIVE POWER BATTERIES  

INSTALLATION AND OPERATING INSTRUCTIONS

1. SAFETY

1.1   Follow your company’s Safety Instructions when working with or near industrial truck batteries. 

Observe the caution label affixed to the battery.  Thoroughly familiarize yourself with industry 

and government guidelines (OSHA, ANSI) for charging, handling, and maintaining industrial 

batteries.

1.2  Assign battery and charger care to properly trained personnel.

1.3   This battery contains sulfuric acid electrolyte.  Avoid contact with skin, eyes, or clothing.  Wear 

rubber  apron,  gloves,  boots,  and  goggles  or  face  shield  when  handling,  checking,  filling, 

charging or repairing batteries.

1.4   Keep water readily available for flushing spilled electrolyte from eyes or skin. Use plain water 

only and obtain medical attention immediately.  Special deluge showers and eye washbasins 

are required.

1.5   Batteries produce hydrogen and oxygen gas during charge.  Keep open flames away.  Do not 

check electrolyte level with a cigarette lighter or match.  Use a flashlight or permanent lights.  

Switch on/off away from the top of the battery.  Do not smoke or create sparks.

1.6   Lift  batteries  with  a  certified/approved  hoist,  crane,  lift  truck,  or  similar  equipment.    Move 

batteries with trucks, conveyors, or rollers.  Be sure to place a rubber mat or similar insulating 

material across the tops of coverless batteries when handling.  Make sure equipment is of 

 ample strength and properly installed.

1.7  Never lay metal tools, such as wrenches or screwdrivers, on top of a battery.

1.8   Disconnect the battery from the truck when performing maintenance and repair on motor or 

electrical system.

1.9  Open or “break” the battery circuit before attempting repairs to the charging plug or receptacles.

1.10   Apply a strong neutralizer, such as baking soda or soda ash, when electrolyte is spilled on the 

floor.  Check local regulations regarding the disposal of neutralized waste.

DO NOT USE CHAIN OR WIRE ROPE SLINGS.

Page 1

Содержание TUBULAR-LMX

Страница 1: ...ashbasins are required 1 5 Batteries produce hydrogen and oxygen gas during charge Keep open flames away Do not check electrolyte level with a cigarette lighter or match Use a flashlight or permanent lights Switch on off away from the top of the battery Do not smoke or create sparks 1 6 Lift batteries with a certified approved hoist crane lift truck or similar equipment Move batteries with trucks ...

Страница 2: ...r with an I E I charging profile in order to achieve a minimum 45 day watering interval To achieve a minimum 90 day watering interval GNB requires the use of a GNB charger with a Tubular LMX charging profile Open the vent caps from each cell and check to see that the electrolyte level is above the plate separators If it is obvious that the electrolyte has spilled out of any cells replace it with e...

Страница 3: ... lead acid batteries the electrolyte temperature must not exceed 110 F 43 C If the battery is continuously operated at or above this temperature the service life of the battery will be severely diminished Under normal operating conditions battery electrolyte temperature should be maintained between 60 100 F 15 38 C Following charging the battery should be allowed to cool down or rest approximately...

Страница 4: ...d water at the end of the charging period when the battery is fully charged and the charger has tapered to its finish rate See Section 9 When using a GNB SCR200 charger with a Tubular LMX charging profile After each 90 calendar days of operation to 80 DOD at 5 days per week or when the specific gravity in the cells reaches 1 335 to 1 345 add water at the end of the charging period when the battery...

Страница 5: ...ctrolyte levels above the plate separators but no higher than 1 8 from the bottom of the vent well Check the electrolyte level quarterly or as necessary depending on battery use prior to charging If the level is not visible below the plate separators add just enough water to cover them and then proceed with charging the battery Otherwise defer watering the battery until the end of the charging per...

Страница 6: ...lls is needed Operation of the sensor and lead wire connections should be checked quarterly Sensor operation can easily be checked by lifting it out of the cell If the light goes OFF the sensor is functional and can be reinserted When the sensor is removed from the cell if the light continues to FLASH check the lead wire connections If after confirming the lead wire connections the light continues...

Страница 7: ...nacceptable amounts of particles and debris A 20 micron or finer filter is recommended NOTE This is in addition to the auxiliary 100 micron BWT filter pre packed with the system b Pressure Minimum height of water reservoir must be ten feet For municipal water supply lines a pressure regulator is required Recomended static system pressure is 15 psi Excessive pressure can cause plugs to snap shut pr...

Страница 8: ... of maintenance and repair service available GNB can also supply all of your battery charger and accessory device replacement part needs For more information in the U S A and Canada call 1 888 563 6300 All others please contact your local GNB battery sales representative 12 RECYCLING U S Federal and State Regulations require that lead acid batteries be handled and disposed of in compliance with st...

Отзывы: