background image

 

PSD1001 

- SIL 3 - SIL 2 Quad ch. Power Supply for Hazardous Area Equipment 

G.M. International ISM0023-11 

 

Ordering information 

Model:  

PSD1001 

Power Bus enclosure 

/B 

Front Panel and Features 

 



SIL 3 according to IEC 61508, IEC 61511 in Loop Powered mode for Lifetime = 10 years. 



SIL 2 according to IEC 61508, IEC 61511 in Bus Powered mode for Tproof = 2 / 5 years (10 / 20 % of total SIF). 



PFDavg (1 year) 0.00 E-00, SFF 100 % (Loop Powered mode). 



PFDavg (1 year) 3.64 E-04, SFF 80.12 % (Bus Powered mode). 



Output to Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2. 



4 channels Power Supply for Hazardous Area equipment. 



Flexible modular multiple output capability. 



Output short circuit proof and current limited. 



Isolation Input/Output. 



EMC Compatibility to EN61000-6-2, EN61000-6-4. 



ATEX, IECEx, UL & C-UL, FM & FM-C Certifications. 



Type Approval Certificate KR for marine applications. 



High Reliability, SMD components. 



High Density, four channels per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

+ Output Ch 3 for Solenoid Valve or 
+ Output Ch 3 for 2 wire Device 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

- Output Ch 3 for Solenoid Valve or 
- Output Ch 3 for 2 wire Device 

+ Output Ch 4 for Solenoid Valve or 
+ Output Ch 4 for 2 wire Device 

- Output Ch 4 for Solenoid Valve or 
- Output Ch 4 for 2 wire Device 

+ Output Ch 1 for Solenoid Valve or 
+ Output Ch 1 for 2 wire Device 

- Output Ch 1 for Solenoid Valve or 
- Output Ch 1 for 2 wire Device 

+ Output Ch 2 for Solenoid Valve or 
+ Output Ch 2 for 2 wire Device 

- Output Ch 2 for Solenoid Valve or 
- Output Ch 2 for 2 wire Device 

9

 

10

 

11

 

12

 

13

 

14

 

15

 

16

 

Not used 

1

 

Not used 

2

 

+ Output Power Supply 24 Vdc 

3

 

- Output Power Supply 24 Vdc 

4

 

Содержание PSD1001

Страница 1: ...PSD1001 SIL 3 SIL 2 Quad ch Power Supply for Hazardous Area Equipment ISM0023 11 PSD1001 INSTRUCTION MANUAL SIL 3 SIL 2 Quad channel Power Supply for Hazardous Area Equipment DIN Rail Model PSD1001...

Страница 2: ...10 11 12 Um 250 Vrms 20 C Ta 60 C Approvals DMT 01 ATEX E 042 X conforms to EN60079 0 EN60079 11 EN60079 26 EN61241 0 EN61241 11 IECEx BVS 07 0027X conforms to IEC60079 0 IEC60079 11 IEC60079 26 IEC61...

Страница 3: ...FM FM C Certifications Type Approval Certificate KR for marine applications High Reliability SMD components High Density four channels per unit Simplified installation using standard DIN Rail and plug...

Страница 4: ...device check that added connecting cable and field device capacitance and inductance do not exceed the limits Co Ca Lo La Lo Ro given in the Associated Apparatus parameters for the effective gas grou...

Страница 5: ...Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respe...

Страница 6: ...ASS I DIVISION 1 GROUPS A B C D CLASS II DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T...

Страница 7: ...en installed in Hazardous Area Hazardous Locations or unless area is known to be nonhazardous Warning substitution of components may impair Intrinsic Safety and suitability for Division 2 Zone 2 Explo...

Страница 8: ...eets your actual Installation Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN...

Отзывы: