D5244 

- SIL 2 - SIL 3 Digital Relay Output , Loop Powered  

G.M. International ISM0271-5 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5244 Associated 

Apparatus Parameters 

Uo / Voc = 0 V 

(Uo equal to the 

connected I.S. circuit) 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5244 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check 
that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective 
gas group. See parameters on

 

enclosure side and the ones indicated in the table below: 

D5244 Terminals 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

Io / Isc = 0 mA 

(Io equal to the 

connected I.S. circuit) 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

Po / Po = 0 mW 
(Po equal to the 

connected I.S. circuit) 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

 

Ii/ Imax 

 

Pi / Pi 

 

 

When connected to other intrinsically safe devices or associated apparatus, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5244 Associated Apparatus are 
not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5244 Associated 

Apparatus Parameters 

Ui / Vmax = 40V 

Uo / Voc 

D5244 Terminals 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

li / Imax = 2 A 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

 

Io / Isc 

 

Ci = 0 nF, Li= 0 nH 

Ch1 

Ch2 

13 - 14 - 15/16 

17 - 18 - 19/20 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Содержание D5244D

Страница 1: ...2 SIL 3 Digital Relay Output Loop Powered G M International ISM0271 5 SIL 2 SIL 3 Digital Relay Output Loop Powered DIN Rail and Termination Board Models D5244S D5244D D5244S D5244D INSTRUCTION SAFET...

Страница 2: ...clauses 5 6 for safety related systems up to and included SIL3 Technical Data Characteristics Input 24 Vdc nom 18 to 30 Vdc reverse polarity protected ripple within voltage limits 5 Vpp Current consu...

Страница 3: ...N61000 6 4 EN61326 1 EN61326 3 1 for safety systems ATEX IECEx T V Certification T V Functional Safety Certification High Reliability SMD components High Density two channels per unit Simplified insta...

Страница 4: ...heck that maximum allowable voltage current Ui Vmax Ii Imax of the D5244 Associated Apparatus are not exceeded by the safety parameters Uo Voc Io Isc of the Intrinsically Safe device indicated in the...

Страница 5: ...red independent channels NC 13 1 2 SIL 2 Out 1 3 4 NO 14 COM 15 16 NC 17 NO 18 COM 19 20 In 1 Control SIL 2 Out 2 In 2 Control Termination board connector Relay contacts shown in de energized position...

Страница 6: ...ONE 2 GROUP IIC T4 Relay contacts shown in de energized position MODEL D5244D 1oo2 channel architecture NC 13 1 2 3 4 NO 14 COM 15 16 NC 17 NO 18 COM 19 20 Termination board connector In 1 Control Out...

Страница 7: ...Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 100 with determination of SIL supposing module contributes 10 of total SIF dangerous failu...

Страница 8: ...en into account Failure rate date taken from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 10...

Страница 9: ...ailure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 100 with determination of SIL supposing module contributes 10 of total SI...

Страница 10: ...ors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmos...

Отзывы: