GMI D5244D Скачать руководство пользователя страница 2

 

D5244 

- SIL 2 - SIL 3 Digital Relay Output , Loop Powered  

G.M. International ISM0271-5 

General Description:

 

The single and dual channel DIN Rail and Termination Boards Digital Relay Output, models D5244S and D5244D, are loop powered digital output modules enabling a Safe Area loop 

voltage signal, to control a device in Hazardous Area, providing 2 port isolation (input/output). Outputs are galvanically isolated. 

Typical applications include switching of Hazardous Area circuits, changing of polarities and sounder tones, calibrating of strain gauge bridges, resetting of field devices, testing of fire 

detectors. Each output channel provides a SPDT relay, with two contacts defined NO (Normally Open) and NC (Normally Close) when the output relay is de-energized. Considering 

each channel NE (Normally Energized), the output relay is energized,so that NO contact is closed (useful for NE loads or Hazardous Area circuits) and NC contact is open (useful for 

ND loads or Hazardous Area circuits). The safe state is reached when the channel and the output relay are de-energized, so that NO contact is open (de-energizing loads or 

Hazardous Area circuits) and NC contact is closed (energizing loads or Hazardous Area circuits). 

Function: 

1 or 2 channels I.S. relay output, provides 2 port isolation (input/output). 

D5244S (Loop Powered mode) 

or 

D5244D (Loop Powered mode with independent channels)

, as shown in function diagrams:

 

SIL 2 Safety Function for NE load (de-energized in safe state) is available at Terminal Blocks 14-15/16 and Terminal Blocks 18-19/20. 

SIL 2 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 13-15/16 and Terminal Blocks 17-19/20. 

D5244D (Loop Powered mode with 1oo2 channel architecture)

,as shown in function diagram: 

SIL 3 Safety Function for NE load (de-energized in safe state) is available at Terminal Blocks 14-19/20. 

SIL 3 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 13-15/16 (or 17-19/20 because externally connected in parallel). 

Signalling LEDs: 

Output status (yellow). 

EMC: 

Fully compliant with CE marking applicable requirements. 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  

part 1 clauses 5-6 for safety related systems up to and included SIL3. 

 

 

 

Technical Data 

Characteristics 

Input: 

24 Vdc nom (18 to 30 Vdc) reverse polarity protected, 

ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

20 mA / channel with relay energized. 

Power dissipation:

 0.4 W / channel with 24 V loop voltage and relays energized. 

Trip voltage levels:

 OFF status 

 15 V, ON status 

 18 V (maximum 30 V). 

Isolation (Test Voltage): 

I.S. Out/In 1.5 KV; I.S. Out/I.S. Out 1.5 KV; In/In 500 V. 

Output I.S.: 

voltage free SPDT relay contact. 

Contact material: 

AgNi90/10. 

Contact rating: 

40 Vdc, 2 A for use in Intrinsic Safety applications, 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load) for non Intrinsic Safety applications. 

DC Load breaking capacity: 

Mechanical / Electrical life: 

15 * 10

6

 / 1 * 10

5

 operations, typical. 

Operate / Release time: 

5 / 2 ms typical. 

Bounce time NO / NC contact: 

1 / 5 ms. 

Response time In / Out: 

50 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating: 

temperature limits –40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Storage: 

temperature limits – 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3(1)G Ex nA nC [Ex ia Ga] IIC T4 Gc, I (M1) [Ex ia Ma] I, II (1)D [Ex ia Da] IIIC 

IECEx:

 Ex nA nC [Ex ia Ga] IIC, [Ex ia Ma] I, [Ex ia Da] IIIC 

associated apparatus and non-sparking electrical equipment. 

Uo/Voc = 0 V, Io/Isc = 0 mA, Po/Po = 0 mW at terminals 13-14-15/16, 17-18-19/20 

(Uo, Io, Po equal to the connected Intrinsic Safety circuit). 

Ui/Vmax = 40 V, Ii/Imax = 2 A, Ci = 0 nF, Li = 0 nH at term. 13-14-15/16, 17-18-19/20. 

Um = 250 Vrms, -40 °C 

 Ta 

 70 °C. 

Approvals: 

BVS 16 ATEX E 109 X conforms to EN60079-0, EN60079-11, EN60079-15. 

IECEx BVS 16.0071X conforms to IEC60079-0, IEC60079-11, IEC60079-15. 

TÜV Certificate No. C-IS-236198-04 SIL 2 / SIL 3 conforms to IEC61508:2010 Ed.2. 

TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting: 

T35 DIN Rail according to EN50022 or on customized Termination Board. 

Weight:

 

about 175 g D5244D, 165 g D5244S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 123 mm, Height 120 mm. 

FSM

SIL 3

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

200

300

0.3 0.5

1

2

5

Resistive 

Load

Содержание D5244D

Страница 1: ...2 SIL 3 Digital Relay Output Loop Powered G M International ISM0271 5 SIL 2 SIL 3 Digital Relay Output Loop Powered DIN Rail and Termination Board Models D5244S D5244D D5244S D5244D INSTRUCTION SAFET...

Страница 2: ...clauses 5 6 for safety related systems up to and included SIL3 Technical Data Characteristics Input 24 Vdc nom 18 to 30 Vdc reverse polarity protected ripple within voltage limits 5 Vpp Current consu...

Страница 3: ...N61000 6 4 EN61326 1 EN61326 3 1 for safety systems ATEX IECEx T V Certification T V Functional Safety Certification High Reliability SMD components High Density two channels per unit Simplified insta...

Страница 4: ...heck that maximum allowable voltage current Ui Vmax Ii Imax of the D5244 Associated Apparatus are not exceeded by the safety parameters Uo Voc Io Isc of the Intrinsically Safe device indicated in the...

Страница 5: ...red independent channels NC 13 1 2 SIL 2 Out 1 3 4 NO 14 COM 15 16 NC 17 NO 18 COM 19 20 In 1 Control SIL 2 Out 2 In 2 Control Termination board connector Relay contacts shown in de energized position...

Страница 6: ...ONE 2 GROUP IIC T4 Relay contacts shown in de energized position MODEL D5244D 1oo2 channel architecture NC 13 1 2 3 4 NO 14 COM 15 16 NC 17 NO 18 COM 19 20 Termination board connector In 1 Control Out...

Страница 7: ...Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 100 with determination of SIL supposing module contributes 10 of total SIF dangerous failu...

Страница 8: ...en into account Failure rate date taken from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 10...

Страница 9: ...ailure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 100 with determination of SIL supposing module contributes 10 of total SI...

Страница 10: ...ors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmos...