![GMI D5202S Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/gmi/d5202s/d5202s_instruction-and-safety-manual_2236272003.webp)
3
D5202S
- 4 A, 24 Vdc, SIL 3 Power Distribution and Diagnostic Module
G.M. International ISM0177-4
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 20 years (
≤
10% of total SIF).
PFDavg (1 year) 2.19 E-07, SFF 99.86 %.
Systematic capability SIL 3
Installation in Zone 2 / Safe Area
Separate single or redundant 24 Vdc Supply in groups of 4 A each into the power bus
Supply current to approximately 40-50 D5000 modules.
5 LEDs indicate power presence, supply variation, supply faults, common bus faults.
2 replaceable 5x20, 6 A fuses.
Very low internal dissipation (ideal diode circuits)
Operating temperature range –40 to +70°C.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, UKR TR n. 898, TUV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
Simplified installation on beginning, end or both sides of Isolators package.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with Power Bus.
Model: D5202S
Terminal block connections
SAFE AREA
1
Common Fault Output (CM common pole of NO or NC contact)
2
Common Fault Output (NO normally open pole)
3
Common Fault Output (NC normally closed pole)
5 6 7 8
1 2 3 4
9 10 11 12
5
6
7
9
Power Supply 1: (+) Positive pole
10
Power Supply 1: (-) Negative pole
11
Power Supply 2: (+) Positive pole
12
Power Supply 2: (-) Negative pole
1oo2 Power Fault (CM common pole of NO or NC contact)
1oo2 Power Fault (NO normally open pole)
1oo2 Power Fault (NC normally closed pole)
Power Bus and DIN-Rail accessories:
Connector JDFT050
Cover and fix MCHP196
Terminal block male MOR017
Terminal block female MOR022