GMI D5202S Скачать руководство пользователя страница 3

 

D5202S 

- 4 A, 24 Vdc, SIL 3 Power Distribution and Diagnostic Module 

G.M. International ISM0177-4 

Ordering Information 

 

Front Panel and Features 

 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 20 years (

10% of total SIF). 



PFDavg (1 year) 2.19 E-07, SFF 99.86 %. 



Systematic capability SIL 3 



Installation in Zone 2 / Safe Area 



Separate single or redundant 24 Vdc Supply in groups of 4 A each into the power bus 



Supply current to approximately 40-50 D5000 modules. 



5 LEDs indicate power presence, supply variation, supply faults, common bus faults. 



2 replaceable 5x20, 6 A fuses. 



Very low internal dissipation (ideal diode circuits) 



Operating temperature range –40 to +70°C. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



ATEX, IECEx, UKR TR n. 898, TUV Certifications. 



TÜV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



Simplified installation on beginning, end or both sides of Isolators package. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks, with Power Bus. 

Model: D5202S 

Terminal block connections 

SAFE AREA 

1

 

Common Fault Output (CM common pole of NO or NC contact) 

2

 

Common Fault Output (NO normally open pole) 

3

 

Common Fault Output (NC normally closed pole) 

5      6       7     8 

1       2      3      4 

 9    10    11    12 

5

 

6

 

7

 

9

 

Power Supply 1: (+) Positive pole 

10

 

Power Supply 1: (-) Negative pole 

11

 

Power Supply 2: (+) Positive pole 

12

 

Power Supply 2: (-) Negative pole 

1oo2 Power Fault (CM common pole of NO or NC contact) 

1oo2 Power Fault (NO normally open pole) 

1oo2 Power Fault (NC normally closed pole) 

Power Bus and DIN-Rail accessories: 
Connector JDFT050 

 

Cover and fix MCHP196 

Terminal block male MOR017 

Terminal block female MOR022 

Содержание D5202S

Страница 1: ...02S 4 A 24 Vdc SIL 3 Power Distribution and Diagnostic Module G M International ISM0177 4 4 A 24 Vdc SIL 3 Power Distribution and Diagnostic Module DIN Rail Model D5202S D5202S INSTRUCTION SAFETY MANU...

Страница 2: ...rtificate No C IS 224248 01 SIL 3 conforms to IEC61508 2010 Ed 2 T V Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010 Ed 2 for Management of Functional Safet...

Страница 3: ...ATEX IECEx UKR TR n 898 TUV Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications Simplified installation on beginning end or both sides of...

Страница 4: ...AREA ZONE 2 GROUP IIC T4 9 10 11 12 MODEL D5202S F Power and Fault Bus Power Supply 1 3 NC 2 NO Common Fault Output 1oo2 Power Fault 1 CM 7 NC 6 NO 5 CM Power Supply 2 Note In case of single power su...

Страница 5: ...ble describes the OFF operation absence of supply on Power Bus and the ON operation presence of 20 30 Vdc supply on Power Bus of the D5202S according to the OFF ON state of each Power Supply source al...

Страница 6: ...erefore considering all diagnostic functions enabled the cumulative fault diagnostic functionality is described by the following table where the status open or closed of Common Fault output contact is...

Страница 7: ...the contact maximum rating 5 A 250 Vac 1250 VA 5 A 250 Vdc 175 W resistive load To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay br...

Страница 8: ...detection on power supply 2 4 Operation with disabled cumulative fault detection DIP switch configurations 1 2 3 4 ON 5 6 7 8 OFF OFF OFF ON ON ON OFF OFF 1 2 3 4 ON 5 6 7 8 OFF OFF OFF ON ON ON OFF O...

Отзывы: