D5093-TB 

- SIL3 24/220Vdc/Vac Transistor-Out Detector 

G.M. International ISM0541-2 

Functional Safety Manual and Application 

Application for D5093S-TB or D5093D-TB

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

3.52 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

98.05 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 101.57

 

MTBF (safety function, single channel) = (1 / 

λ

tot safe

) + MTTR (8 hours) 

1123 years

 

λ

no effect

 = “No Effect” failures 

98.33 

λ

not part

 = “Not Part” failures 

2.90 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

  

202.80

 

MTBF (device, single channel) = (1 / 

λ

tot device

) + MTTR (8 hours) 

562 years

 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.00 FIT 

98.05 FIT 

0.00 FIT 

3.52 FIT 

96.53% 

T[Proof] = 1 year

 

T[Proof] = 6 years

 

PFDavg = 1.54 E-05 - Valid for 

SIL 3

 

PFDavg = 9.27 E-05 - Valid for 

SIL 3

 

T[Proof] = 20 years

 

PFDavg = 3.09 E-04 - Valid for 

SIL 3

 

PFDavg vs T[Proof] table

 (assuming Proof Test coverage of 95%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures: 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 95%), with determination of SIL supposing module contributes 

10% of total SIF dangerous failures:       

Failure rates table according to IEC 61508:2010 Ed.2 : 

Failure rate table:

 

Safety Function and Failure behavior:

  

D5093-TB is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 
The failure behaviour is described from the following definitions : 
 

 fail-Safe State: it is defined as the transistor output being de-energized or open; 

 

 fail Safe: failure mode that causes the module to go to the defined fail-safe state without a demand from the process; 

 

 fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state), so that the transistor output remains 

      energized or closed; 
 

 fail “No Effect”: failure mode of a component that plays a part in implementing the safety function but that is neither a safe failure nor a dangerous failure. 

      When calculating the SFF this failure mode is not taken into account; 
 

 fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness. 

      When calculating the SFF this failure mode is not taken into account.  
The 2 channels of D5093D-TB module could be used to increase the hardware fault tolerance, needed for a higher SIL of a certain Safety Function, as they are completely independent 
from each other, not containing common components. In fact, the analysis results got for D5093S-TB (single ch.) are also valid for each channel of D5093D-TB (double ch.). 

Operation 

Input Signal state 

Pins 7-8 (In 1 - Ch.1) or 9-10 (In 2 - Ch.2) 

Output state 

TB connector (Out 1 - Ch.1 or Out 2 - Ch.2) 

OFF Low 

(

 lower threshold) 

Open (De-energized as safe state condition) 

ON High 

(

 upper threshold) 

Closed (Energized) 

Description:

  

Input AC or DC signals from field are applied to Pins 7-8 (In 1 - Ch.1) and Pins 9-10 (In 2 - Ch.2, only for D5093D-TB). See table below for the lower and upper threshold levels. 
Open-drain transistor outputs on TB connector (for Channel 1 and, only for D5093D-TB, for Channel 2) are both normally open (or de-energized as safe state condition) for OFF 
operation, or they are both closed (or energized) for ON operation. See page 6 for DIP-switch configuration. 

OFF operation 

ON operation 

Field Input AC or DC signal 

 lower threshold 

Field Input AC or DC signal 

 lower threshold 

D5093S-TB  

(only Ch.1) 

or 

D5093D-TB 

(Ch.1 and Ch.2) 

Out 1 is open or de-energized 

Channel 1 

Channel 2 

 

 

 

In 1 

8

In 2 

10

 

 

 

Field Input AC or DC signal 

 upper threshold 

Field Input AC or DC signal 

 upper threshold 

Out 1 is closed or energized 

Safety 

PLC 

Input 

 

TB connector 

TB connector 

Out 1 

Out 2 is open or  
de-energized 

Safety 

PLC 

Input 

The following table describes the state (open or closed) of each output when its input AC or DC signal is in the High (

 upper threshold) or Low (

 lower threshold) state. 

Typical input signal 

Dip-switch position to be enabled (ON) 

Lower threshold 

Upper threshold 

24 Vac / Vdc 

15 Vac / Vdc 

21 Vac / Vdc 

48 Vac / Vdc 

30 Vac / Vdc 

40 Vac / Vdc 

60 Vac / Vdc 

35 Vac / Vdc 

50 Vac / Vdc 

110 Vac / Vdc 

75 Vac / Vdc 

100 Vac / Vdc 

220 Vac / Vdc 

160 Vac / Vdc 

200 Vac / Vdc 

NOTE: 

These values are always valid for each of 5 possible thresholds. 

 

Out 2 

 

 

D5093S-TB  

(only Ch.1) 

or 

D5093D-TB 

(Ch.1 and Ch.2) 

Channel 1 

Channel 2 

 

 

 

In 1 

8

In 2 

10

 

 

 

Safety 

PLC 

 

Out 1 

Out 2 is closed  
or energized 

Safety 

PLC 

Input 

 

Out 2 

 

 

Systematic capability SIL 3.

 

TB connector 

TB connector 

TB connector 

TB connector 

TB connector 

TB connector 

Содержание D5093S-TB

Страница 1: ...D5093 TB SIL3 24 220Vdc Vac Transistor Out Detector G M International ISM0541 2 SIL3 24 220Vdc Vac Transistor Out Detector Models D5093S TB D5093D TB D5093S TB D5093D TB INSTRUCTION SAFETY MANUAL...

Страница 2: ...cal input ON 200 Vac Vdc OFF 160 Vac Vdc for 220 Vac Vdc typical input threshold level selection by means of internal dip switch Output voltage free SPST optocoupled open drain transistor solid state...

Страница 3: ...one 2 Safe Area Input Output and Channel Channel isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL EAC Ex UKR TR n 898 T V Certification...

Страница 4: ...A ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 MODEL D5093D TB Out 1 SIL 3 10 7 8 Termination board connector Out 2 SIL 3 9 In 1 24 220 Vac In 2 24 220 Vdc 2...

Страница 5: ...afety function but part of the circuit diagram and is listed for completeness When calculating the SFF this failure mode is not taken into account The 2 channels of D5093D TB module could be used to i...

Страница 6: ...mplitude falls below the related lower threshold value the output transistor turns to the open state as detectable by the safety related PLC and the yellow status LED is turned off A dangerous failure...

Страница 7: ...stened by a mixture of detergent in water Electrostatic Hazard to avoid electrostatic hazard the enclosure of D5093 TB series must be cleaned only with a damp or antistatic cloth Any penetration of cl...

Отзывы: