D5091-103
- SIL3 Relay Out Module for 5 A ND Loads
G.M. International ISM0457-1
3
Ordering information
Front Panel and Features
SIL 3 (low demand mode of operation) according to IEC 61508:2010 Ed.2 with Tproof = 6/20 years (
≤
10 / >10 % of total SIF)
for ND load with ND relay (terminals 7-8).
SIL 3 (low demand mode of operation) according to IEC 61508:2010 Ed.2 with Tproof = 14/20 years (
≤
10 / >10 % of total SIF)
for ND load with NE relay (terminals 9-10).
SIL 3 (high demand mode of operation) according to IEC 61508:2010.
SC 3: Systematic Capability SIL 3
Installation in Zone 2/Div. 2
Up to 5 A functional / 6 A inrush current
Low current consumption
Service contact available
Input/Output isolation
Model:
D5091S-103
Power Bus and DIN-Rail accessories:
DIN-Rail stopper MCHP196
Terminal block connections
SPDT Output Common
SAFE AREA
SPDT Output Normally Open Contact
SPDT Output Common
SPDT Output Normally Close Contact
7
8
9
10
+ Input
1
- Input
2
7 8
9 10
1
2
D5091
-103
7
8
1
2
SIL 3
9
10
STS