D5091-103 

- SIL3 Relay Out Module for 5 A ND Loads 

G.M. International ISM0457-1 

Ordering information 

Front Panel and Features 



SIL 3 (low demand mode of operation) according to IEC 61508:2010 Ed.2 with Tproof = 6/20 years (

 10 / >10 % of total SIF) 

for ND load with ND relay (terminals 7-8). 



SIL 3 (low demand mode of operation) according to IEC 61508:2010 Ed.2 with Tproof = 14/20 years (

 10 / >10 % of total SIF) 

for ND load with NE relay (terminals 9-10). 



SIL 3 (high demand mode of operation) according to IEC 61508:2010. 



SC 3: Systematic Capability SIL 3 



Installation in Zone 2/Div. 2 



Up to 5 A functional / 6 A inrush current 



Low current consumption 



Service contact available 



Input/Output isolation 

 

 

Model:  

D5091S-103 

Power Bus and DIN-Rail accessories: 
DIN-Rail stopper MCHP196 

Terminal block connections 

SPDT Output Common 

SAFE AREA 

SPDT Output Normally Open Contact 

SPDT Output Common 

SPDT Output Normally Close Contact 

7

 

8

 

9

 

10

 

+ Input 

1

 

- Input 

2

 

7 8 

9 10 

D5091

-103 

SIL 3 

10 

STS 

Содержание D5091S-103

Страница 1: ...D5091 103 SIL3 Relay Out Module for 5 A ND Loads G M International ISM0457 1 SIL3 Relay Out Module for 5 A ND Loads DIN Rail and Termination Board Model D5091S 103 D5091S 103 INSTRUCTION MANUAL ...

Страница 2: ...s to IEC60079 0 IEC60079 15 UL C UL E222308 conforms to UL 61010 1 UL 121201 for UL and CAN CSA C22 2 No 61010 1 12 CSA C22 2 No 213 17 for C UL TUV Certificate No C IS 272994 01 SIL 3 conforms to IEC61508 2010 Ed 2 TÜV Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010 Ed 2 for Management of Functional Safety Mounting EN IEC60715 TH 35 DIN Rail or on custo...

Страница 3: ...tal SIF for ND load with NE relay terminals 9 10 SIL 3 high demand mode of operation according to IEC 61508 2010 SC 3 Systematic Capability SIL 3 Installation in Zone 2 Div 2 Up to 5 A functional 6 A inrush current Low current consumption Service contact available Input Output isolation Model D5091S 103 Power Bus and DIN Rail accessories DIN Rail stopper MCHP196 Terminal block connections SPDT Out...

Страница 4: ...CATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay breaking capacity diagram MODEL D5091S 103 In 7 8 9 10 1 2 Termination board connector SIL3 SPDT Out ND Load 7 8 or 9 10 All relay contacts are shown in de energized position ...

Страница 5: ...hen installed in EU Zone 2 the unit shall be mounted in a certified Ex enclosure that provides a degree of protection not less than IP54 in accordance with EN IEC60079 15 When installed in a Class I Division 2 Hazardous Location the unit shall be mounted in a supplemental enclosure that provides a degree of protection not less than IP54 The enclosure must have a door or cover accessible only by th...

Отзывы: