6
D5062
- SIL 2 Vibration Transducer Interface
G.M. International ISM0184-7
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20)
GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVI-
SION 1, GROUPS A, B, C, D,
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Input configuration selection via internal Dip-Switch
1 2 3 4
ON
OFF
2 wires transducers (4 mA)
1 = ON, 2 = OFF, 3 = OFF, 4 = OFF.
1 2 3 4
ON
OFF
2 wires transducers (6 mA)
1 = ON, 2 = ON, 3 = OFF, 4 = OFF.
1 2 3 4
ON
OFF
2 wires transducers (10 mA)
1 = ON, 2 = OFF, 3 = ON, 4 = OFF.
MODEL D5062S
5 +
6 - Supply 24 Vdc
=
=
Out
1
2
In
Signal -
Common
Vibration
Monitor
=
=
=
2 wires
Vibration
Transducer
- Signal
Common
8
9
7
Input Sensor
selection
via DIP Switch
+
-
Termination
board
connector
Power
Bus
10
7/9