background image

 

D1062 

- Vibration Transducer Interface 

G.M. International ISM0094-7 

 

Ordering information 

 

Model:  

D1062S 

Power Bus enclosure 

/B 

Front Panel and Features 



Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2. 



0 to –20 V Input/Output Signal. 



Wide band signal transfer. 



Input and Output short circuit proof. 



High Accuracy. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4. 



ATEX, IECEx, FM & FM-C Certifications. 



High Reliability, SMD components. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

For AC Output Sensor if connected to terminal 14 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

For Current Selection if connected to terminal 11 or 12 

For Current Selection if connected to terminal 10 

For Current Selection if connected to terminal 10 

For Current Supply if connected to terminal 14 

- Power Input Ch 1 for 3 wires Vibration Transducer 

- Signal Input Ch 1 for 3 wires Vibration Transducer 

Common Input Ch 1 for 3 wires Vibration Transducer 

9

 

10

 

11

 

12

 

13

 

14

 

15

 

16

 

- Signal Output Ch 1 for Vibration Monitor 

1

 

Common Output Ch 1 for Vibration Monitor 

2

 

+ Power Supply 24 Vdc 

3

 

- Power Supply 24 Vdc 

4

 

Содержание D1062S

Страница 1: ...D1062 Vibration Transducer Interface ISM0094 7 D1062S INSTRUCTION MANUAL Vibration Transducer Interface Din Rail Model D1062S...

Страница 2: ...mVrms on 0 5 to 20 KHz band Frequency response DC to 10 KHz within 0 1 dB 10 KHz to 20 KHz within 3 dB Performance Ref Conditions 24 V supply 10 K load 23 1 C ambient temperature Calibration accuracy...

Страница 3: ...Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier For AC Output Sensor if connected to terminal 14 Terminal block connections HAZARDOUS AR...

Страница 4: ...ted 14 16 15 16 with terminals 13 14 connected Li Ri device and L cable R cable IIC A B Lo Ro 61 7 H Lo Ro 247 1 H Lo Ro 494 3 H IIB C IIA D IIC A B Lo Ro 56 8 H Lo Ro 227 3 H Lo Ro 454 7 H IIB C IIA...

Страница 5: ...nsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the configura...

Страница 6: ...Out 1 11 12 10 9 1 2 In 1 Signal Common Vibration Monitor Programmable Current Source 2 wires Vibration Transducer AC Signal Common AC Output Sensor Jumper Sensor operating in AC signal mode Jumpers...

Страница 7: ...ning substitution of components may impair Intrinsic Safety and suitability for Division 2 Zone 2 Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before s...

Страница 8: ...milar sensor connect sensor negative supply wire at terminal 14 sensor signal wire at terminal 15 and sensor common wire identical for both signal and supply at terminal 16 For 2 wires powered sensor...

Отзывы: