D1045 

- Digital Output Loop / Bus Powered 

G.M. International ISM0081-7 

Installation 

 

D1045 is a digital output isolator housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1045 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing). 

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 
Connect input signal of channel 1 at terminal “5” and “6” regardless the polarity. 
Connect input signal of channel 2 at terminal “7” and “8” regardless the polarity. 
Connect positive output of channel 1 at terminal “13” and negative output at “14” using Out-A diagram or positive output at terminal “15” and negative at terminal “16” using Out-B diagram. 
Connect positive output of channel 2 at terminal “9” and negative output at “10” using Out-A diagram or positive output at terminal “11” and negative at terminal “12” using Out-B diagram. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1045 must be cleaned only with a damp or antistatic cloth. 
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1045 must be connected to SELV or SELV-E supplies. 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. 
Turn on power, the “power on” green led must be lit, status led on each channel must be in accordance with condition of the corresponding input line. 
If possible close and open input lines one at time checking the corresponding status leds condition as well as output to be correct. 

Содержание D1045Y

Страница 1: ...D1045 Digital Output Loop Bus Powered ISM0081 7 D1045Y INSTRUCTION MANUAL Digital Output Loop Bus Powered DIN Rail Model D1045Y ...

Страница 2: ...ltage levels OFF status 1 0 V ON status 6 0 V maximum 30 V Current consumption 24 V 3 mA 10 KΩ input impedance Output 70 mA at 11 3 V 17 0 V no load 81 4 Ω series resistance at terminals 13 14 9 10 Out A 70 mA at 12 2 V 17 0 V no load 68 6 Ω series resistance at terminals 15 16 11 12 Out B Short circuit current 85 mA 90 mA typical Response time 20 ms power up in 600 ms typical in loop powered mode...

Страница 3: ...allation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output Ch 2 A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AREA Output Ch 2 A for Solenoid Valve Output Ch 2 B for Solenoid Valve Output Ch 2 B for Solenoid Valve 9 10 11 12 Loop powered Open Terminals or Loop powered Close Terminals by ju...

Страница 4: ...ameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20µH per foot 0 60µH per meter The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the ...

Страница 5: ...S CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1045Y 3 4 5 6 Supply 24 Vdc 7 8 In 1 Control In 2 Control 1 2 Loop Powered Open Terminals 13 14 15 16 9 10 11 12 Solenoid Valve Out 1 A Out 2 A Common positive connection Solenoid Valve Output channels are actuated in alternative When both inputs are enabled only output 2 is activated MODEL D1045Y 3 4 5 6 Supply 24 Vd...

Страница 6: ... 13 14 15 16 9 10 11 12 Solenoid Valve Out 1 B Out 2 B Common positive connection Solenoid Valve MODEL D1045Y 3 4 5 6 Supply 24 Vdc 7 8 1 2 13 14 15 16 9 10 11 12 Out 2 B Common positive connection Solenoid Valve Loop Powered Close Terminals Output channels are actuated in alternative When both inputs are enabled only output 2 is activated Output Diagram D1045Y OUTPUT DIAGRAM OUT A D1045Y OUTPUT D...

Страница 7: ...epaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Each of the two independent and isolated channels of D1045Y accepts an input from Safe Area Non Hazardous Locations logic level or switch contact and provides an output see the output diagram on data sheet for details of voltage and curre...

Страница 8: ... for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conductors are well isolated from each other and do not produce any unintenti...

Отзывы: