General Description:
The D1045 is a dual channel, actuated in alternative, DIN Rail Digital Output module enabling a Safe Area contact, logic level or drive signal, to control a device
in Hazardous Area, providing 3 port isolation (input/output/supply). Typical applications include driving 1 or 2 positions directional solenoid valves or other process control devices.
It can also be used as a controllable supply to power measuring or process control equipments in Hazardous Area.
Output channels have the capability of driving loads both in Gas Groups IIC and IIB/IIA with different safety parameters.
Function:
2 channels I.S. actuated in alternative to operate Hazardous Area loads from contacts, logic levels or drive logics in Safe Area providing 3 port isolation (input/output/supply),
loop or bus powered, as indicated in the function diagram.
Signalling LEDs:
Power supply indication (green), output status (yellow).
Field Configurability:
Loop/Bus powered operating mode, output channel driving capability by external wiring.
EMC:
Fully compliant with CE marking applicable requirements.
Supply:
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits
≤
5 Vpp.
Current consumption @ 24 V:
90 mA with output energized at nominal load, 110 mA with short circuit output.
Power dissipation:
1.4 W with 24 V supply voltage, output energized at nominal load.
Max. power consumption:
at 30 V supply voltage and short circuit output, 2.9 W.
Isolation (Test Voltage):
I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V; In/In 500 V.
Input:
switch contact, logic level or loop powered.
Trip voltage levels:
OFF status
≤
1.0 V, ON status
≥
6.0 V (maximum 30 V).
Current consumption @ 24 V:
3 mA (
≈
10 K
Ω
input impedance).
Output:
70 mA at 11.3 V (17.0 V no load, 81.4
Ω
series resistance) at terminals 13-14, 9-10 (Out A).
70 mA at 12.2 V (17.0 V no load, 68.6
Ω
series resistance) at terminals 15-16, 11-12 (Out B).
Short circuit current:
≥
85 mA (90 mA typical)
Response time:
20 ms (power up in 600 ms typical in loop powered mode).
Compatibility:
CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive.
Environmental conditions:
Operating:
temperature limits -20 to + 60 °C, relative humidity max 95 %.
Storage:
temperature limits – 45 to + 80 °C.
Safety Description:
II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA II T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus.
Uo/Voc = 18.9 V, Io/Isc = 249 mA, Po/Po = 1173 mW at terminals 13-14, 9-10 (Out A).
Uo/Voc = 18.9 V, Io/Isc = 307 mA, Po/Po = 1286 mW at terminals 15-16, 11-12 (Out B).
Um = 250 Vrms, -20 °C
≤
Ta
≤
60 °C.
Approvals:
DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11,
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15,
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611,
3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15.
DNV No.A-13778 Certificates for maritime applications.
Mounting:
T35 DIN Rail according to EN50022.
Weight:
about 130 g.
Connection:
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm
2
.
Location:
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA
T4 installation.
Protection class:
IP 20.
Dimensions:
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
Technical Data
Characteristics