D1045 

- Digital Output Loop / Bus Powered 

ISM0081-7 

D1045Y 

INSTRUCTION MANUAL 

Digital Output 

Loop/Bus Powered 

DIN-Rail Model D1045Y 

Содержание D1045Y

Страница 1: ...D1045 Digital Output Loop Bus Powered ISM0081 7 D1045Y INSTRUCTION MANUAL Digital Output Loop Bus Powered DIN Rail Model D1045Y ...

Страница 2: ...ltage levels OFF status 1 0 V ON status 6 0 V maximum 30 V Current consumption 24 V 3 mA 10 KΩ input impedance Output 70 mA at 11 3 V 17 0 V no load 81 4 Ω series resistance at terminals 13 14 9 10 Out A 70 mA at 12 2 V 17 0 V no load 68 6 Ω series resistance at terminals 15 16 11 12 Out B Short circuit current 85 mA 90 mA typical Response time 20 ms power up in 600 ms typical in loop powered mode...

Страница 3: ...allation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Output Ch 2 A for Solenoid Valve Terminal block connections HAZARDOUS AREA SAFE AREA Output Ch 2 A for Solenoid Valve Output Ch 2 B for Solenoid Valve Output Ch 2 B for Solenoid Valve 9 10 11 12 Loop powered Open Terminals or Loop powered Close Terminals by ju...

Страница 4: ...ameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20µH per foot 0 60µH per meter The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the ...

Страница 5: ...S CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1045Y 3 4 5 6 Supply 24 Vdc 7 8 In 1 Control In 2 Control 1 2 Loop Powered Open Terminals 13 14 15 16 9 10 11 12 Solenoid Valve Out 1 A Out 2 A Common positive connection Solenoid Valve Output channels are actuated in alternative When both inputs are enabled only output 2 is activated MODEL D1045Y 3 4 5 6 Supply 24 Vd...

Страница 6: ... 13 14 15 16 9 10 11 12 Solenoid Valve Out 1 B Out 2 B Common positive connection Solenoid Valve MODEL D1045Y 3 4 5 6 Supply 24 Vdc 7 8 1 2 13 14 15 16 9 10 11 12 Out 2 B Common positive connection Solenoid Valve Loop Powered Close Terminals Output channels are actuated in alternative When both inputs are enabled only output 2 is activated Output Diagram D1045Y OUTPUT DIAGRAM OUT A D1045Y OUTPUT D...

Страница 7: ...epaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Each of the two independent and isolated channels of D1045Y accepts an input from Safe Area Non Hazardous Locations logic level or switch contact and provides an output see the output diagram on data sheet for details of voltage and curre...

Страница 8: ... for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conductors are well isolated from each other and do not produce any unintenti...