background image

3

221899A

Introduction

Please read these instructions and follow them carefully for the
safe and economical use of your boiler.

The Micron series are fanned flue boilers designed to provide
central heating and indirect domestic hot water.

The boiler is fully automatic in operation having only one user
control, the temperature control.

WARNING.  It is important that the case is not disturbed or
removed other than for servicing by a competent person.

Gas Leak or Fault

If a gas leak or fault exists or is suspected, the boiler must be
turned off, including the electrical supply and must not be used
until the fault has been put right.

Advice/help should be obtained from your installation/servicing
company or the local gas undertaking.

Electrical Supply Failure

Failure of the electrical supply will cause the burner to go out.
Should this occur, operation of the appliance will normally
resume after the electrical supply is restored.

Note: If the boiler is switched OFF, manually, wait at least 30
seconds before switching on again.

Safety Temperature Limiter

If the overheat Safety Temperature Limiter operates as indicated
by illuminated reset light, open the controls cover and turn
temperature control to “0” (anticlockwise) and then back to
original position, refer to diagram 9.1.  If the overheat operates
again, turn the appliance off and contact your installation/
servicing company.

Protection Against Freezing.

If the boiler is to be out of use for any long period of time during
severe weather conditions we recommend that the whole of the
system, including the boiler, be drained off to avoid the risk of
freezing up.  Make sure that, if fitted, the immersion heater in the
cylinder is switched off.  Alternatively, there is a built-in frost
protection which will cause the boiler when it  is switched off at
the control knob to operate in the event of the water temperature
in the boiler dropping to 6

o

C or 7

o

C.  The boiler will switch off

again when the temperature of the water in the boiler reaches
about 15

o

C.  This will only be fully effective if the external

controls are set so that the pump runs continuously, that is they
are calling for heat.

Note: The frost protection will not operate if the electrical supply
is turned off.

Maintenance

To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals.  The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.

If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of The Gas Safety (Installation and Use) Regulations,
Section 35.

It is the law that any servicing is carried out by a competent
person.

To obtain service, please call your installer or Heatcall (Glow-
worm’s own Service Organisation) using the telephone number
given on the front cover of these instructions.

Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.

Instructions for Use

All CORGI Registered Installers carry a CORGI ID card, and
have a registration number.  Both should be recorded in your
boiler Logbook.  You can check your installer is CORGI registered
by calling CORGI direct on :- 01256 372300.

Cleaning

WARNING.  This appliance contains metal parts (components)
and care should be taken when handling and cleaning, with
particular regard to edges.

Clean the casing occasionally by wiping it over with a damp
cloth or dry polishing duster.

Do not use an abrasive cleaner.

To Light the Boiler

WARNING.  Sealed Systems

A sealed water system must be filled and pressurised by a
competent person.

Only light the boiler when you are sure that the system has been
filled and pressurised.

The pressure gauge should show at least 0.7bar, anything less
than this figure could indicate a leak and you MUST contact your
installation/servicing company.

If there is any doubt about the boiler being full of water consult
your installation/servicing company.

ALL SYSTEMS.

Turn the electrical supply on to the boiler and check that all
remote controls are calling for heat.  Check also that the
programmer (if fitted) is in the “ON” mode.

To Turn the Boiler On

Open the controls cover, see diagram 9.1.

Turn the control knob clockwise to any position between “0” and
MAX.  The maximum temperature setting is about 82

o

C (180

o

F),

see diagram 9.1.

The boiler lighting operation is now automatic as follows:

The fan operates and after a short period of time, the spark
ignition operates, the solenoid opens, then the burner will light
shown by the “Burner On” neon on the control panel lighting up.

The burner will remain alight until switched off by the control
thermostat, any remote control or the programmer.

Note: If the boiler is switched OFF, by hand, wait at least 30
seconds before switching on again.

When the boiler switches off, the burner will go out.

The automatic lighting sequence will operate again when heat
is required.

Shut the controls cover.

To Turn the Boiler Off

For short periods, turn the control knob anti-clockwise to “0” Off.
To relight, turn the control knob to any position between “0” and
“MAX”.

For longer periods, turn the control knob fully anti-clockwise to
“0” Off and switch off the electrical supply to the boiler.

To relight follow the lighting sequence given above.

Optional Programmer

A programmer is available, which will automatically switch your
central heating system on and off once or twice a day at
whatever times you choose.

Содержание Micron 40FF

Страница 1: ...ustomer Service number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration Fanned Flue Boiler This is a Cat I2H Appliance Reference in these instructions to British Standards and Statutory Regulations Requirements apply only to the United Kingdom For Ireland the rules in force must be used The instructions con...

Страница 2: ... Notified body 0086 The CE mark on this appliance shows compliance with 1 Directive 90 396 EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels 2 Directive 73 23 EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits 3 Directive 89 336 EEC on the approximation of...

Страница 3: ...ty Installation and Use Regulations Section 35 It is the law that any servicing is carried out by a competent person To obtain service please call your installer or Heatcall Glow worm s own Service Organisation using the telephone number given on the front cover of these instructions Please be advised that the Benchmark logbook should be completed by the installation engineer on completion of comm...

Страница 4: ... have been certified by B S I 1 3 Range Rating This boiler is range rated and may be adjusted to suit individual systemrequirements refertodiagram1 2fordatalabelposition ratings and settings 1 4 Heating System Controls The heating system should have installed a programmer and room thermostat controlling the boiler Thermostatic radiator valves may be installed in addition to the room thermostat Not...

Страница 5: ... suitable for outdoor installation This boiler may be installed in any room although particular attention is drawn to the requirements of the current issue of BS7671 with respect to the installation of a boiler in a room containing a bath or shower Any electrical switch or boiler control utilising mains electricity should be placed so that it cannot be touched by a person using the bath or shower ...

Страница 6: ...f and two or more walls seek advice from the local gas company before installing the boiler If the terminal is fitted within 600mm below plastic guttering or painted soffit an aluminium shield 1500mm long should be fitted immediately beneath the guttering or eaves If the terminal is fitted within 450mm below painted eaves or a painted gutter an aluminium shield 750mm long should be fitted immediat...

Страница 7: ...00 C between flow and return 3 4 Water System For an open vented system the boiler must be supplied from an unrestricted water supply taken from a feed and expansion cistern fitted at a maximum height of 27 metres above the boiler The cold feed must be 15mm minimum size It is important that the relative positions of the pump cold feed and open vent are as shown in diagram 3 1 Theunrestrictedopenve...

Страница 8: ... pressure gauge with a set pointer and covering at least the range of 0 to 4bar 0 to 60lb in2 shall be permanently fitted to the system in a position where it can be seen when filling the system 3 13 Domestic Hot Water Cylinder SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE The domestic hot water cylinder must be of the indirect coil type It must be suitable for working at a gauge pressure of 0 3...

Страница 9: ...IT X plus 47mm RH X plus 183mm LH flue length STD EXTD REAR FLUE Y plus 22 5mm flue length EASYFIT Y plus 50 5mm flue length Y X Y plus 67mm flue length Y STD EXTD Y plus 22 5mm flue length EASYFIT Y plus 50 5mm flue length Y 15mm 52mm Y plus 67mm flue length Y SCREW TAPE Total must not exceed 2m MAX SCREW TAPE STD REAR OUTLET FLUE PACK 1 METRE EXTENSION KIT FOAM SEAL 1 metre extension kits may be...

Страница 10: ...spective of wall thicness 4 3 Rear Top and Side Flue Application Select the boiler location and flue application with due regard to the terminal position see diagram 2 1 Take the template from the boiler pack and temporarily position it on the wall making sure that the minimum clearances are maintained see diagram 4 3 Mark the centre line position of the flue Top or Rear as diagram 4 3 Forasideflu...

Страница 11: ...side wall is not practical the flue system can be installed from inside Use of the optional wall liner kit is required 4 8 Rear Flue Fixing Fit the self adhesive foam seal provided in the flue pack around the air duct at the position shown in diagram 4 1 Make sure that the ductings do not slope down towards the boiler Make good around the flue outside after installation of the boiler Important Ift...

Страница 12: ...agram 5 6 Note The spigot would only be fitted to the top flue outlet where averticalfluekitorincertainfluebendorientationsisincorporated Instructions are supplied with these kits Lift the boiler into position hooking over the top mounting bracket Note Anti theft screw kits are are available part no s 458113 458114 Important Securelowerbrackettowallwithscrewintowall plug already prepared Note It w...

Страница 13: ...t do not fully tighten see diagram 5 8 Swing the air deflector out from right hand side the slot in air deflector allows you to do this to allow easy access to fitting fan assembly Note Apply soap to seals on flue duct extension piece to help it slide in be careful not to damage O ring Insert flue duct extension piece into top turret see diagram 5 7 Note Make sure that the flue duct extension piec...

Страница 14: ...eseparateinstallationinstructionssupplied with programmer Take care not to damage any internal wiring Using heat resistant 85o C cable of at least 0 75mm2 24 0 2mm and of a suitable length thread through the grommet at the rear of the control box through the cable clamp and connect to appropriate terminals Tighten cable clamp screws see diagram 5 10 Standard colours are brown live L blue neutral N...

Страница 15: ...system checks as below should be carried out Diagram 5 9 TOP TURRET 6793 GASKET SCREWS 4 TOP TURRET FLUE OUTLET FLUE DUCT EXTENSION HINGE PIN 7665 Diagram 5 8 CABLE CLAMP GROMMET 1 Test insulation resistance to earth 2 Test earth continuity and short circuit of all cables 3 Test the polarity of the mains The installer is requested to advise and give guidance to the user of the controls scheme used...

Страница 16: ... 3 Initial Lighting and Testing CAUTION This work must be carried out by a competent person in accordance with the current issue of BS6798 Make sure that boiler case is fitted securely Make sure that all naked lights and cigarettes are out Open the control cover refer to Instructions for Use and identify the controls see diagram 9 1 Remove fascia see diagram 6 1 Check that the boiler is isolated f...

Страница 17: ... is made Refit control box and fascia Note The fixing holes of the fascia are slotted to allow fine adjustment to align control cover with casing When the temperature control is turned to the 0 position by hand wait at least 30 seconds before turning On again There may be an initial smell given off from the boiler when new this is quite normal and it will disappear after a short period of time 6 6...

Страница 18: ...l back electrode protection sleeve and disconnect electrode connection along with earth connection see diagram 8 6 Remove the burner retaining screw located at the right hand side of the burner see diagram 8 4 When completed take hold of burner and slide it to the left clearing the injector and remove Take care not to damage the combustion chamber insulation Use a vacuum cleaner or suitable stiff ...

Страница 19: ...s required the breaking and remaking of the electrical connections the earth continuity polarity short circuit and resistance to earth checks must be repeated using a suitable multimeter Refer to Boiler Fault Finding see diagram 9 2 Fault Finding Wiring Diagram see diagram 9 3 Pictorial Wiring Diagram see diagram 9 4 9 2 Electrical Supply Failure Failure of the electrical supply will cause the bur...

Страница 20: ... and then on Do not operate the boiler without combustion chamber front fitted Before carrying out fault finding ensure that gas electricity and water are available at the boiler Is neon 1 lit NO Check power supply Is neon 2 lit NO YES YES Faulty thermistor Replace Disconnect the 2 way thermistor plug from the PCB Check that there is a resistance between 14k 2 5kOhms Faulty PCB Replace Is neon 3 l...

Страница 21: ...ITER P C B CONTROL BOARD GAS CONTROL VALVE BLOCK CONNECTOR THERMISTOR ELECTRODE AIR PRESSURE SWITCH NEON 1 NEON 5 NEON 4 NEON 6 NEON 2 NEON 3 F4A FUSE p y g p b bl bl bl b bl b r g y bl b LS LIVE Switched N LS N br br br br br r g y g y g y g y br b b br BROWN b BLUE g y GREEN YELLOW g GREY bl BLACK p PURPLE y YELLOW r RED KEY g y NEUTRAL EARTH MAIN KEY TO TERMINAL BLOCK 9 Fault Finding Diagram 9 ...

Страница 22: ...wtheelectricalthermistor from its phial see diagram 10 2 Remove thermistor lead from the plastic R clips at rear of case and the cable clips these are located down left hand side of boiler Draw thermistor lead followed by thermistor out through the case grommet Re assembly note When fitting the thermistor make sure it is fully inserted into the phial see diagram 10 2 Take care when re threading as...

Страница 23: ...supplied into recess before fitting the replacement multifunctional control After assembly test for gas soundness and purge in accordance with the current issue of BS6891 10 7 Solenoid diagram 10 4 Remove the electrical plug from the multifunctional control Remove the securing screw and then the solenoid assembly 10 8 Burner Remove the burner as Section 8 2 10 9 Injector Part No 205757 Remove the ...

Страница 24: ...TUBE 11 1 Part Identification The part number and the diagram location will help to identify the part 11 2 Ordering Whenorderinganysparepartspleasequotethenumberanddescriptionfromthelisttogetherwiththemodelnameandserialnumber If ordering from the local gas undertaking also quote the GC number of the appliance and part 11 Spare Parts Part No Description Location GC Part No 801159 Multifunctional co...

Отзывы: