
7
221954D
MINIMUM CLEARANCES FROM WALLS
CEILING, FLOOR, CUPBOARD, WORKTOPS,
AND INFLAMMABLE MATERIALS
Diagram 1.2
1.13 Room Ventilation
The boiler is room sealed and does not require the room or
space containing it to have permanent airvents.
1.14 Boilers in a Compartment
Where the installation of the boiler will be in an unusual position,
special requirements are needed, the current issue of BS6798
gives detailed guidance on these requirements.
A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose. An existing
cupboard or compartment modified for the purpose may be
used. Details of essential requirements for cupboard or
compartment design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for
easy removal of the boiler.
1 General
FRONT
VIEW
6mm
6mm
6mm
160mm
500mm
From a permanent surface
ADDITIONAL CLEARANCES MAY BE
REQUIRED FOR INSTALLATION
6mm
6mm
65mm
Diagram 1.3
DATA LABEL
Where the boiler is fitted in a cupboard or compartment,
permanent high and low level ventilation must be provided. The
minimum ventilation areas are given in Table 2.
1.15 Timber Frame Building
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Glow-worm.
1.16 Heating System Controls
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed, however they
must not be fitted in a room where the room thermostat is
located.
NOTE:
For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.