0020154078_00 - 02/13 - Glow-worm
19
MAINTENANCE
6.1
Observe maintenance intervals
∙
Maintain the product only if you are a competent person.
∙
Carry out annual maintenance.
6.2 Preparing
maintenance
6.2.1
Providing spare parts for maintenance and
repair work
∙
In case you need spare parts during maintenance or repair,
exclusively use genuine Glow Worm spare parts.
The genuine component parts of the product have been
certi
fi
ed together with the product in the course of the
CE conformity check. If you do NOT use certi
fi
ed genuine
Glow Worm spare parts during maintenance or repair, the
CE conformity of the product will expire. That is why we
imperatively recommend to install genuine Glow Worm spare
parts.
6.3 Pre-maintenance
instructions
Comply with the basic safety rules before performing
maintenance or installing spare parts.
∙
Shut down the system.
∙
Switch o
ff
the system electrical supply.
∙
Isolate the hydraulic circuit from the appliance using the
shut-o
ff
valves where necessary.
∙
Drain the appliance if you need to replace hydraulic circuit
components.
∙
Protect all electric components from water if you have to
work on the appliance.
6.4 Annual
Maintenance
∙
Check the proper functioning of safety devices.
∙
Check the pressure of the water system.
∙
Check tightness of refrigerant circuit.
∙
Check that there are no traces of rust or oil around the
refrigerant circuit’s components.
∙
Ensure that the appliance’s components are neither worn
nor broken.
∙
Check that the wires are
fi
rmly attached to the electrical
terminals.
∙
Check the appliance’s grounding.
∙
Check the
fl
ow temperature of the heat pump and the
setting points.
∙
Check that the fan rotates freely.
∙
Check the pressure of the expansion vessel.
6.5 Cleaning
6.5.1 External
cleaning
∙
If the appliance needs cleaning, refer to the user manual.
6.5.2
Cleaning the components
∙
Check the absence of ice on the compressor.
∙
Remove any dust from electronic boxes.
∙
Clean the air / refrigerant battery and make sure that air
circulates between the
fi
ns and around the unit.
∙
Check that condensates can properly drain from the heat
pump by removing the adapter located under the heat
pump (turn it a ¼ turn to unlock).
∙
Clean the evaporator on both sides using a brush with soft
bristles. Remove the fan blades and the rear grill before
cleaning.
a
Warning!
Risk of minor injury.
Handling the fan blades and grill can cause cuts.
•
Wear protective gloves to perform this
operation.
6.6
Draining
∙
Cut o
ff
the appliance’s electricity supply.
2
1
14mm
Key
1 Hydraulic circuit venting valve
2 Draining
hose
∙
Close the shut-o
ff
valves located behind the heat pump.
∙
Engage a hose (2) to the venting valve (1) or place a
container under the venting valve (1) to drain the hydraulic
circuit.
∙
Open the bleed valve (1) with a
fl
at spanner.
Note: if necessary, the heating installation can be drained via
this bleed valve by opening the shuto
ff
valves located at the
rear of the heat pump.