Glow-worm Betacom2 24 Скачать руководство пользователя страница 24

0020145065_01 - 09/12 - Glow-worm

• 

Run the appliance for at least 15 minutes, with a heating 

temperature set to greater than or equal to 50°C (not 

applicable for an installation with underfloor heating).

• 

Vent air from each radiator again until the water flows 

normally, then close the vents.

• 

If you have difficulties in removing the air, launch the air-

removal programs in the heating circuit (see the chapter 

("Technical settings for the appliance and list of parameters").

• 

Make sure that the pressure indicator shows a value of 0.8 

bars; otherwise, fill the appliance again.

11.5  Initial lighting

11.5.1 

Control

i

  IMPORTANT:

The combustion for this appliance has been checked, 

adjusted and preset at the factory for operation on natural 

gas (G20) as defined on the appliance data label. 

 

No measurement of the combustion is necessary.Should 

the appliance require to be converted to LPG gas ensure 

you follow the gas conversion section before lighting the 

boiler.

• 

Check that the appliance has been installed in accordance with 

the instructions.

• 

Check the integrity of the flue system and flue seals.

• 

Check the integrity of the appliance combustion circuit and 

relevant seals.

• 

Check that all internal/external controls are calling for heat.

• 

Check that the gas service isolation is open.

• 

To adapt the appliance to another type of gas, see chapter 

"LPG conversion".

11.5.2 

Adjusting the temperature

• 

Light the appliance by following the procedure below.

• 

Select the "H domestic hot water" function by pressing 

the “Mode” button repeatedly to scroll through your options 

until     are shown.

The appliance will enter a self checking routine, then the fan 

will start and the ignition sequence commence. The boiler, if 

necessary, will automatically repeat the ignition sequence a 

further 4 times.

If the burner fails to ignite “F28” will be displayed, initially, this 

may be due to air in the gas supply line. Press the reset button. 

Do not use the reset button to purge the installation - never press 

reset more than 3 times.

• 

Select the heating function only by pressing the "mode" 

button repeatedly (   is shown only).

• 

Press   or 

 buttons to adjust. 

• 

Select the hot water function only by pressing the "mode" 

button repeatedly (   is shown only).

• 

Press   or 

 buttons to adjust. 

• 

Check that hot water is available at all taps, then close.

• 

Return the appliance to the correct mode by pressing "mode" 

button unit the desired functions are activated.

11.6  Gas rates

The supply from the governed meter must be of adequate size to 

provide a steady inlet working pressure of 20mbar (8in wg) at the 

boiler. 

• 

On completion, test the gas installation for tightness using the 

pressure drop method and suitable leak detection fluid, purge 

in accordance with the above standard.

i

  IMPORTANT:

Due to the modulating operation of the boiler and the 

need to check the gas inlet pressure and measure the 

gas rate at maximum rate, it will be necessary to force it 

to maximum.

• 

Activate the test mode "P.01" and set the value to HI in order to 

force the burner at P. max. See chapter "Specific adjustment > 

Appliance technical settings and parameter list > Test modes".

11.6.1 

Operational Gas Inlet Pressure

1

2

Key

1  Gas service isolation valve

2  Test point

• 

With all other gas appliances operating, check the operational 

supply pressure at the gas service isolation valve test point.

The nominal supply pressure for Natural Gas (G20) is 20mbar. 

The nominal supply pressure for LPG (G31) is 37mbar.

• 

Turn the taps and appliances off, then disconnect the pressure 

gauge. 

Additionally the safe nominal maximum heat input of the 

appliance can be achieved at an inlet pressure down to 15mbar.

i

  IMPORTANT:

The burner pressure cannot be measured and is not used 

to measure the gas rate.

INSTALLATION

- 22 -

Содержание Betacom2 24

Страница 1: ...condens Installation and Servicing Betacom2 24 G C No 47 019 16 Betacom2 28 G C No 47 019 17...

Страница 2: ......

Страница 3: ...ppliance location 8 6 1 Location 8 6 2 Clearances 8 6 3 Ventilation 8 7 Appliance installation 9 7 1 Scope of delivery 9 7 2 Recommendations before installing 9 7 3 Dimensions 10 7 4 Mounting 11 8 Hyd...

Страница 4: ...ault diagnosis 27 14 2 Fault memory 28 14 3 Fault codes 28 14 4 Functional flow diagram 30 15 Gas conversion adjustments 31 15 1 Settings 31 15 2 Restart re check commissioning 32 16 Draining 32 16 1...

Страница 5: ...ng safety The appliance is designed to recognise the potential for an overheat lockout and will shutdown before this happens 2 1 2 Safety discharge valve A safety discharge valve and discharge pipe ar...

Страница 6: ...y a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appropriate Building Regulations The Benchmark Checklist can be used to demonstra...

Страница 7: ...ional test and check for safety 3 2 Regulations 3 2 1 Statutory requirements IMPORTANT Where no British Standards exists materials and equipment should be fit for their purpose and of suitable quality...

Страница 8: ...f the boiler including any heating controls to the electrical supply MUST be through one common isolator and must be fused 3 Amp maximum 3 2 2 Other regulations Control of Substances Hazardous to Heal...

Страница 9: ...al power W 6 6 Operational mode electrical power Max W 151 151 Internal fuse rating on main PCB A 2 2 Index of electrical protection EN 60529 IPX4D IPX4D Description Unit 24 28 Gas connection O D mm 1...

Страница 10: ...building it should be fitted in accordance with the Institute of Gas Engineers document IGE UP 7 1998 If in doubt seek advice from local gas undertaking or Glow worm 6 2 Clearances To allow periodic m...

Страница 11: ...ain the maximum domestic flow is 1 0 bar The maximum working pressure of the domestic hot water circuit is 10 bar If the cold water supply pressure exceeds this then a pressure reducing valve must be...

Страница 12: ...s are shown diagrammatically see diagram below 3 2 1 3 2 1 4 8 9 7 5 7 6 5 Key 1 Heating flow circuit 2 Heating return circuit 3 Boiler 4 Double check valve assembly 5 Domestic cold water supply in 6...

Страница 13: ...ue 80 125 flue 130mm Use a 125mm diameter core drill for internal access only flue installation 60 100 flue 80 125 flue 150mm i IMPORTANT If flue extension pipes are to be used then a core drill size...

Страница 14: ...operation Do not use any solvent products due to the risk of damaging the circuit a DANGER Do not perform any hot work directly under the appliance this may cause damage to the appliance base Heat ma...

Страница 15: ...e pipe 2 Condensate outlet pushfit Make sure there is no protective plug fitted Connect the condensate pipe 1 to the condensate outlet 2 i IMPORTANT The pipe should have a fall of a least 2 5 44mm met...

Страница 16: ...0020145065_01 09 12 Glow worm INCREASE PIPE SIZE 75 mm min 100 mm min Washing machine trap waste 44 2 5 INSTALLATION 14...

Страница 17: ...s Being a condensing boiler some pluming may occur from the flue outlet This should be taken into consideration when selecting the position for the terminal Carports or similar extensions of a roof on...

Страница 18: ...onal 90 bend is necessary or 2 at 45 the length L must be reduced by 1 m When using the Plume Management Kit the maximum lengths flue pipe A and B 60 100mm are A m 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5...

Страница 19: ...C 60 C 71 6 79 10 Electrical connections e DANGER Incorrect installation can cause electric shock or appliance damage The electrical connection of the appliance must be made only by a qualified engine...

Страница 20: ...850C insulated cable not less than 0 75mm 24 0 20 A fused three pin plug and shuttered socket outlet may be used instead of a fused spur box provided that it is not used in a room containing a fixed...

Страница 21: ...s as below Resistance to earth 1 Ohm Short circuit test L N Resistance to earth L E Polarity check 10 3 2 230V permanent supply 230V system controls a DANGER All cables connected to the appliance shou...

Страница 22: ...4 13 5 14 6 15 7 16 8 17 9 18 X20 1 2 3 4 1 1 2 1 X21 Green Yellow Green Yellow 18 17 16 1 2 3 4 9 6 5 8 7 10 11 12 13 14 15 Key 1 Control accessories connector 2 Reserved for future use 3 Location fo...

Страница 23: ...r vent located on the pump and automatic air vents on the installation If the CH pressure falls below 0 4 bar the display will flash the current pressure and the boiler will not operate To increase th...

Страница 24: ...a further 4 times If the burner fails to ignite F28 will be displayed initially this may be due to air in the gas supply line Press the reset button Do not use the reset button to purge the installat...

Страница 25: ...urn i IMPORTANT Should the appliance require adjustment refer to the Specific adjustment section overleaf Allow the system to reach maximum temperature then switch off the boiler by isolating from the...

Страница 26: ...measured by the external sensor no d 67 Time remaining before the end of the anti cycle in heating mode min Display the time remaining before the end of the anti cycle no d 71 Maximum temperature sett...

Страница 27: ...vated 1 activated 0 yes 12 4 Status of the appliance Press button for more than 3 seconds to learn the current state of functioning of the appliance The screen displays S and the state of the applianc...

Страница 28: ...s installed check the operation of the appliance Start the appliance to ensure that any adjustments operate correctly and check that the appliance operates safely Check the gas tightness and water tig...

Страница 29: ...s Make sure that the electricity supply has not been interrupted and that the appliance is connected correctly See chapter Trouble shooting Fault diagnosis Check the electrical installation Check the...

Страница 30: ...ure of the installation 0 3 bar Return water valve closed Pump disconnected Leak in the installation Fill the installation Purge the installation Check the pump connections Check the flow and return h...

Страница 31: ...ence Check temperature sensors connections Replace faulty sensors F73 Heating circuit pressure sensor fault The sensor is shorted or disconnected Check the sensor s connections Check the sensor F74 He...

Страница 32: ...0020145065_01 09 12 Glow worm 14 4 Functional flow diagram 14 4 1 Central Heating 14 4 2 Domestic Hot Water MAINTENANCE 30...

Страница 33: ...he appliance can be converted See chapter Commissioning Tools required to make the conversion are a 4mm Allen key and an electricians screwdriver Having checked the appliance and system have been inst...

Страница 34: ...ating circuit of the boiler only by closing the heating flow and return isolating valves See chapter Hydraulic connection Gas and water connections Open the drain point 2 Attach a length of hose 1 if...

Страница 35: ...eck that the pressure sensor is working properly The pressure must be displayed on the screen Check the pressure of the expansion vessel 17 1 2 Other checks Check the CO2 rate in the fuel and compare...

Страница 36: ...Preliminaries Prior to during servicing and after any maintenance or changed parts the following inspection must be carried out The integrity of the flue system and flue seals The integrity of the ap...

Страница 37: ...e to achieve the required results for either the combustion or gas rates it will be necessary to complete a full service of the appliance and then repeat the combustion check procedure If after servic...

Страница 38: ...Use protective gloves 5 3 2 4 1 6 Key 1 Condensate cleaning cap 2 Condensate pipe 3 Condensate outletv 4 Condensate retaining screw 5 Condensate trap 6 Hose Place a container under the condensate tra...

Страница 39: ...t exchanger 12 Burner door seal 13 Burner 14 Gas valve 15 Fan 16 Fan connection 17 Gas pipe 17 8 1 Spark electrode Disconnect the electrode inlet 3 and the grounding cable 2 Remove the 2 spark electro...

Страница 40: ...ion check On completion of the service the Benchmark Service Record sould be completed 18 Replacement of Parts Do not use reconditioned or copy parts only use original parts supplied by Glow worm If a...

Страница 41: ...irclip 5 Remove the steel washer 4 Remove fibre washer 1 Remove the glass 3 18 3 1 Expansion vessel B C D E A 3 2 1 4 2 1 Key 1 Connector 2 Expansion vessel 3 Upper support bracket 4 Retaining screw 5...

Страница 42: ...xchanger 17 Automatic air vent 18 Expansion vessel pipe clip 19 Automatic air vent retaining clip 20 Pump head retaining screws 21 Pump housing 22 Pump head connector 23 Plate to plate heat exchanger...

Страница 43: ...urise the boiler 18 4 5 Flow sensor and impeller Remove the the electrical connection 12 Unclip the flow sensor 13 Unscrew the impeller housing 28 and remove the impeller 18 4 6 Bypass Drain the boile...

Страница 44: ...ut 13 Combustion burner door assembly seal 14 Burner gasket 15 Burner 16 Burner retaining screw 17 Heat exchanger retaining screw 18 Heat exchanger retaining bracket 19 Burner gate retaining screw 20...

Страница 45: ...t exchanger out Drain the boiler heating and hot water circuits as described in the appropriate chapter Draining Remove the flue connection Undo the two screws located on the top of each side panel Re...

Страница 46: ...18 6 Condensate trap b ATTENTION Condensate is mildly acidic Wear protective gloves 5 3 2 4 1 6 Key 1 Condensate reservoir 2 Condensate discharge 3 Condensate outlet 4 Condensate retaining screw 5 Con...

Страница 47: ...to the PCB When refitting the user interface ensure the leads are not trapped 18 7 4 Mains supply cable e DANGER The main supply cable must be replaced by a qualified and competent electrician If the...

Страница 48: ...Thermistor flow and return 4 0020097279 Gas valve 5 0020038441 Electrode assembly 6 0020118159 User interface PCB Key No Part No Description GC Part No 7 0020118165 Plate to plate heat exchanger 24 0...

Страница 49: ...olystyrene end packs Remove top polystyrene pack with fittings Positioning of Appliance for Final Installation no obstructions Recommend 2 persons lift appliance to position into place Fit bracket sec...

Страница 50: ...Declaration of Conformity Installation Commissioning and Service Record...

Страница 51: ......

Страница 52: ...Number Comments Signature SERVICE 7 Date Energy Ef ciency Checklist completed Yes No Engineer Name Company Name Telephone Number Engineer ID Number Comments Signature SERVICE 9 Date Energy Ef ciency...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...ing changes GLOW WORM Nottingham Road Belper Derbyshire DE56 1JT Because of our constant endeavour for improvement details may vary slightly from those shown in these instructions www glow worm co uk...

Отзывы: