NOTICE

Do  not  install  any  bulb-type  sprinkler  if  the  bulb  is  cracked  or 

there is loss of liquid from the bulb. Sprinklers should be tightened 

enough to obtain a leak-tight joint when water pressure is applied 

and/or hydrostatic test is performed. Sprinklers should not be 

overtightened as this can result in distortion and subsequent leak

-

age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque 

for 1/2 inch NPT sprinkler threads.

Step1. 

Sprinklers must be properly oriented.

Step2. 

With pipe thread sealant applied to the pipe 

threads, hand tighten the sprinkler into the sprin-

kler fitting.  

Note: Do not grasp the sprinkler by 

the deflector.

Step3. 

Wrench-tighten the sprinkler using only the 

appropriate wrench. Wrenches are only to be 

applied to the sprinkler wrench flats or wrench 

hex as applicable. 

Note: Do not apply wrench to 

frame arms.

INSTALLATION

CARE AND MAINTENANCE

Prior  to  installation,  it  is  important  to  read  and  follow  the 

“Sprinkler Caution” sheet (GFS-840) included within each 

box of sprinklers.  This sheet is available on Globe’s web 

site (www.globesprinkler.com).

Always  obtain  permission  from  the  proper  authorities  to 

shut down the affected fire protection system and notify all 

personnel who may be affected by this action before closing 

a fire protection system main control valve for maintenance 

work on the system that it controls.
Sprinklers should only be cleaned by means of gently dust

-

ing with a feather duster; otherwise, non-operation in the 

event of a fire or inadvertent operation may result.
Store sprinklers in a cool, dry place. Exposure to extreme 

heat will damage the thermal sensing element, possibly re

-

sulting in premature activation. Avoid direct sunlight.

Replace any sprinkler that shows any corrosion, damage, 

or loss of liquid from the glass bulb. 

Do not attempt to paint or alter the sprinkler’s coating in any 

manner after leaving the manufacturing plant.

Do  not  attach  wiring,  ropes,  decorations  or  fixtures  to  a 

sprinkler.
Absence of an escutcheon, used to cover a ceiling hole, 

may delay sprinkler operation in a fire situation.
It  is  the  owner’s  responsibility  for  inspection,  testing  and 

maintenance of the fire sprinkler system with all components 

and devices in accordance with the National Fire Protection 

Association Pamphlet 25 as well as any other requirements 

as set forth by the local Authority Having Jurisdiction (AHJ).

FIGURE 1:  STANDARD WRENCH 

P/N 325390

FIGURE 2:  RECESSED WRENCH 

P/N 325391

FIGURE 3:  1/2” ADJUSTMENT RECESSED PENDENT

Содержание GL-RES Series

Страница 1: ...FPA 13 13D 13R and any other related documents as appropriate The GL3010 is typically utilized when maximum coverag es are not needed thereby reducing flow demands The GL5610 is typically the sprinkler of choice when utilizing Residential Sprinklers within an NFPA 13 Occupancy The larger K factor can be advantageous when needed to con form to the NFPA 13 hydraulic Special Design Approach for Resid...

Страница 2: ...the room or compartment using the area of the room divided by the number of sprinklers in the room 7psi minimum SIN K FACTOR GPM PSI lpm bar TEMPERATURE MAX AREA OF COVERAGE FEET m MINIMUM PRESSURE PSI bar MINIMUM FLOW GPM L min DEFLECTOR TO CEILING MOUNTING SURFACE DISTANCE INCHES mm MINIMUM DISTANCE BETWEEN SPRINKLERS FEET m 155 F 68 C 175 F 79 C 200 F 93 C GL3010 3 0 43 2 cULus EU 1 cULus cULus...

Страница 3: ...e www globesprinkler com Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls Sprinklers should only be cleaned by means of gently dust ing with a feather duster otherwise non oper...

Страница 4: ...VE CAPS SPRINKLER ESCUTCHEON Quantity Finish Part Number See TABLE C Quantity SIN Temperature Rating Finish Part Number See TABLE B TABLE B PART NUMBER SELECTION PART NUMBER SIN TEMPERATURE FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL3010 3010 155 155 F 68 C 01 BRONZE GL4110 4110 175 175 F 79 C 02 CHROME GL4910 4910 200 200 F 93 C 03 WHITE POLYESTER GL5610 5610 04 BLACK POLYESTER Note All combinat...

Отзывы: