Logging In

To enter programming mode you need to log in.

The Main Panel must be powered up and must have initialised itself i.e. NOT be showing the
‘INITIALISING’ message.

Press ENTER on the IR Keypad (or keyboard). You must now input your unique customer access code
(supplied with the panel). You have unlimited attempts but if code entry is not started within 10
seconds then the panel will revert back to it’s default screen. While entering the code you are allowed
up to 5 seconds between key presses.

The programming functions are arranged using a menu system.

To select a function or sub-menu use either

and ENTER or 0-9 and ENTER.

HOME takes you to "1-Review".
ESC takes you up a menu level.

Any number presses (0-9) will append a digit to what you see unless :

1) You are at the very top (1- Review) then the first press selects the first digit.
2) You are at the bottom then the press replaces the last digit.

The top level menus are:

1 Review Historic Log
2 Text Descriptions & Names
3 Zones - Disable & Assign
4 Sounders - Disable & Assign
5 Input/Output - Disable & Assign
6 Device Set-up
7 Monitor Device Counts & Test
8 General

Most functions operate in a consistent manner using the standard keys. The item that is being
changed is usually highlighted with a flashing cursor.

Function Selection

MAINTENANCE

JUNO-NET

26

OPERATION & MAINTENANCE MANUAL
REVISION 0.7a
16-04-2004

Содержание JUNO-NET

Страница 1: ...OPERATION MAINTENANCE MANUAL JUNO NET Fire Alarm Control Panel REVISION 0 7a 16 04 2004...

Страница 2: ...g into Programming Mode 2 9 Logbook 2 10 Event data sheet OPERATION 1 3 Reset the system 1 4 Sound and silence the alarms 1 5 Read the Fire Fault Test and Disabled queues 1 6 Active Delays 1 7 Lamp Te...

Страница 3: ...n the LEDs in the FAULTS section of the main panel i e 7 8 9 10 If the LED is AMBER it indicates that a detector is in PRE ALARM If the LED is AMBER it indicates that the panel is in a test mode If th...

Страница 4: ...eans that the relay and I O module outputs are disabled If there are disablements then pressing this button will show the disablements on the LCD display If there are more disablements than can be sho...

Страница 5: ...TEST TEST DISABLED DISABLED SYSTEM ON SYSTEM ON ALARM FAULT ALARM FAULT SUPPLY FAULT SUPPLY FAULT PROC FAULT PROC FAULT TRANS FAULT TRANS FAULT SOUND ALARMS SOUND ALARMS PAPER FEED PAPER FEED LAMP TES...

Страница 6: ...5 LCD DISPLAY This procedure should be used if There has been an alarm and the alarm condition no longer exists There has been a fault and the fault condition no longer exists Press the button The sys...

Страница 7: ...NTROLS CONTROLS CONTROLS DISABLEMENTS DISABLEMENTS DISABLEMENTS DISABLEMENTS QUEUE REVIEW QUEUE REVIEW QUEUE REVIEW QUEUE REVIEW 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9...

Страница 8: ...1 23 22 20 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY During installation via the programming functions delays can be set for the sounders I O modules and fire brigade transmission These delays are...

Страница 9: ...T PROC FAULT TRANS FAULT SOUND ALARMS PAPER FEED LAMP TEST SYSTEM RESET ALARM SILENCE DISABLED TEST FAULT FIRE AUXILIARY RELAYS FIRE BRIGADE TRANSMISSION SELECTED DETECTORS ACTIVE DELAYS FIRE BRIGADE...

Страница 10: ...Pt 4 1999 FAULTS CONTROLS DISABLEMENTS QUEUE REVIEW 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 19 21 23 22 20 25 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY To start the fire drill press the SOUND AL...

Страница 11: ...sing The TEST LED will be lit The buzzer will sound for 0 5 seconds every 5 seconds same as FAULT indication ALARM SILENCE will not stop this The message DETECTOR TEST MODE will be displayed on the LC...

Страница 12: ...Panel and Repeater LCD displays for 15 seconds Testing More Than One Device Disablements Sensor sensitivity Other Detectors and callpoints can only be tested one at a time The LED must be extinguishe...

Страница 13: ...THE REQUIREMENTS OF EN54 Pt 2 Pt 4 1999 FAULTS CONTROLS DISABLEMENTS QUEUE REVIEW 1 2 3 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 23 22 20 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY SELECTED DETEC...

Страница 14: ...UFACTURED TO THE REQUIREMENTS OF EN54 Pt 2 Pt 4 1999 FAULTS FAULTS CONTROLS CONTROLS DISABLEMENTS DISABLEMENTS QUEUE REVIEW QUEUE REVIEW 1 1 2 2 3 3 4 4 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 1...

Страница 15: ...AULT PROC FAULT TRANS FAULT SOUND ALARMS PAPER FEED LAMP TEST SYSTEM RESET ALARM SILENCE DISABLED TEST FAULT FIRE AUXILIARY RELAYS FIRE BRIGADE TRANSMISSION SELECTED DETECTORS ACTIVE DELAYS FIRE BRIGA...

Страница 16: ...e new roll The pointing towards the main circuit board Thread the paper into the printer Close the fascia and replace the screws Press the PAPER FEED and check that the paper feeds smoothly from the p...

Страница 17: ...TURNED OFF SIM CARD The SIM CARD is mounted on the back of the main board Release the by pulling in the direction of the arrows With the retaining clips held in the released position push the SIM CARD...

Страница 18: ...ARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTALLING PRINTED CIRCUIT BOARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOV...

Страница 19: ...and check that the battery voltage does not drop significantly Carry out a test on a detector or manual callpoint with the primary supply disconnected to ensure that the batteries are healthy NOTE BA...

Страница 20: ...l the printer is free before starting a new print job If you wish to stop a printout enter the function again and you will be given the option of canceling the printout This function cannot be accesse...

Страница 21: ...ces connected to the Analogue Loops Note that in Installation Mode all information is live i e the count of devices will change as the panel learns and device types will be updated if they change In A...

Страница 22: ...Select the Zones you wish to put into test mode Exit programming mode but DO NOT press SYSTEM RESET as this clears all test modes In test mode when a detector is activated the LED on the detector will...

Страница 23: ...one detector LED can be lit at any one time Select the device and SWITCHED ON and press ENTER The device will typically take a few seconds to respond Selecting NORMAL for that device or selecting SWI...

Страница 24: ...e INFRA RED KEYPAD 0 A 4 E 8 I 1 B 5 F 9 J 2 C 6 G K 3 D 7 H L M N O P Q R S T U V W X Y HOME SHIFT ENTER B SP Z SPACE ESC EXIT HOME Return to first loop zone device etc ENTER Accept current selection...

Страница 25: ...ER RESET PRINTER CONNECTOR PRINTER FUSE PS2 PC KEYBOARD ADAPTOR STANDOFFS 4 FOR LOOPCARD SIM CARD CONNECTOR QUAD UART 50 WAY BOX HEADER FOR J NET CON 16 WAY BOX HEADER FOR LOOP CONNECTOR LOOPCARD HEAD...

Страница 26: ...IFT is off 0 9 are used to input numbers and are used to select items B SP and are often used to change fields move the cursor are often used to select the loop ENTER is used to select items and to st...

Страница 27: ...ion or sub menu use either and ENTER or 0 9 and ENTER HOME takes you to 1 Review ESC takes you up a menu level Any number presses 0 9 will append a digit to what you see unless 1 You are at the very t...

Страница 28: ...be made Sample pages of the logbook are provided here and can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible pe...

Страница 29: ...MAINTENANCE JUNO NET 2 10 EVENT DATA SHEET DATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 28 OPERATION MAINTENANCE MANUAL REVISION 0 7a 16 04 2004...

Отзывы:

Похожие инструкции для JUNO-NET