Global Power Technologies
SERVICE AND MAINTENANCE
05585 rev11 | Model 8550-SD
Page 36 of 53
If this test was conducted because the Power Unit power was below Set Power, see Section 6.1.1
for
test result diagnostic.
If the Power Unit is producing Set Power, the open circuit voltage (V
oc
) should be in the range of 52 to
56 Volts, and the internal resistance (R
INT
) should be in the range of 1.10 to 1.35 Ohms.
NOTE: If the TEG has just been started in the last 10 hours or has been stopped and restarted
several times in the past days, its internal resistance may be somewhat higher.
The maximum operating limits are 56.5 Volts for open circuit voltage and 1.45 Ohms for internal
resistance. If the Power Unit does not produce Set Power and problems with the Burner System, Fuel
System, and Cooling System have been ruled out, increase the fuel pressure until one of the above
limits or Set Power is reached. Remember that it will take at least 10 minutes for a change in fuel
pressure to take full effect. See also sections 5.1.3 and 5.1.4.
If the Power Unit will not produce Set Power without exceeding these limits, or does not respond to
increasing fuel pressure, the Power Unit may be damaged.
NOTE: In some cases, the Power Unit may be operated at derated power, consult GPT for
further information.
WARNING!
Do not operate the Power Unit above Set Power, maximum open circuit voltage, or
maximum internal resistance.