Instruction Manual
4
Inline Duct Fan
4. OPERATION
4.1 Before power is supplied to unit, verify wiring accuracy as per
fan connection diagram.
4.2 At initial start-up, verify that impeller rotation and airflow
direction is correct.
4.3 Ensure that motor amperage draw does not exceed nameplate
rating.
5. MAINTENANCE & CLEANLINESS
5.1 Motor and fan wheel should be inspected periodically;
approximately every six months if continuously operated.
5.2 Please inspect all fastenings and rotating equipment for
stability.
5.3 Appliance maintenance should only be completed by
qualified personnel.
5.4 Prior to maintenance, switch off the main power switch.
During routine maintenance, verify condition of all appliance
parts.
Inline Fan
Size
Dimension (mm)
(inch)
A
B
C
D
E
F
100
4
100
237
204
25
25
42
150
6
150
278
195
25
25
42
200
8
200
333
210
25
25
42
250
10
250
333
210
28.6
28.5
42
300
12
300
402
276
25
30
42
SPECIFICATIONS
Product
Number
Outlet/
Inlet port
diameter
(inch/mm)
Voltage
Frequency
Airflow
Speed
Power
Current
Noise
Insulation
Class
(VAC)
(Hz)
(CFM)
(RPM)
(W)
(A)
(dB)
292655
4"/100
120
60
121
3150
22
0.19
60
F
292656
6"/150
120
60
265
3000
55
0.44
66
F
292657
8"/200
120
60
565
3100
127
1.1
75
F
292658
10"/250
120
60
588
3000
130
1.1
73
F
292659
12"/300
120
60
824
2750
190
1.52
72
F
DIMENSIONAL DATA