Analogue Addressable Fire Detector w/ Smart Addressing
TECHNICAL SPECIFICATIONS
ORDER CODE
DESCRIPTION
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel:
+351 289 896 560
• Sales:
• Technical Support:
• www.
globalfire.pt
Loop Powered - 17 V to 30 V DC
450 uA max.
4 mA - Alarm LED Iluminated
According to EN54-5 or/and EN54-7, EN54-17
0.5-2.5 mm²
20 seconds max.
White / ABS / 95% RH Non-Condensing
0°C to 50°C / -10°C to 85°C
100 mm (D) x 50 mm (H) inc. base / 144 g inc. base
SUPPLY VOLTAGE
CURRENT - QUIESCENT / SURGE
CURRENT - DEVICE IN ALARM
SENSITIVITY
CABLE SIZE
RESET/START-UP TIMES
COLOUR / CASE MATERIAL / MAX. HUMIDITY
NORMAL / TRANSIENT OPER. TEMPERATURE
DIMENSIONS / WEIGHT
ZEOS-AS-S
ZEOS-AS-H
ZEOS-AS-SH
ZEOS-AS-SI
ZEOS-AS-HI
ZEOS-AS-SHI
| CERTIFICATE |
ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH SMART ADDRESSING
ANALOGUE ADDR. TEMPERATURE/HEAT DETECTOR WITH SMART ADDRESSING
ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR WITH SMART ADDR.
ANALOGUE ADDR. PHOTOELECTRIC SMOKE DETECTOR W/ ISOLATOR & SMART ADDR.
ANALOGUE ADDR. TEMPERATURE/HEAT DETECTOR W/ ISOLATOR & SMART ADDR.
ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR W/ ISOLATOR & SMART ADDR.
1328-CPR-0526
1328-CPR-0527
1328-CPR-0525
1328-CPR-0609
1328-CPR-0608
1328-CPR-0524
INSTALLATION
MECHANICAL SPECIFICATION
INSTALLING THE BASE
To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against
terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical
junction boxes.
INSTALLING THE HEAD
Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on
base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and
activate the detection loop. Test the detectors as described below.
TESTING
All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at
the conclusion of testing.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When sufficient
smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear
smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be
met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several
cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm immediately remove
the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to activate within 60 seconds, confirm
connections and programming. If necessary replace unit. Note: After testing, check that the system is returned to normal operation. Notify
the appropriate authorities that the testing procedure has been completed and the system is active again.
MAINTENANCE
The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low
power vacuum cleaner.
>> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR
Detector Head
Detector Base
Alignment Marks
ZEOS-AS
ma_zeosas_01_010001_en_180420
MADE IN PORTUGAL - EU