ADDRESSING THE PANEL 

 

There can be connected up to four ORION MINI- REP V2 to the ORION Conventional Panel. 
When more than one Repeater is needed, each repeater has to be addressed. 
To address the ORION MINI-REP V2 please follow the steps below: 

 

1. Install and connect the repeater (refer to 

INSTALLATION 

section of this manual).  

2. Apply supply voltage to main panel. 
3. On the repeater, introduce code 4321 (

Engineering Functions code

). 

4. Push OUTPUTS AUXILIARY button on the DISABLEMENTS section.  

The LEDs in the FAULTS section will flash alternately (see image on the right) indicating 
that the repeater is in ADDRESSING MODE. General FAULT LED on the STATUS section 
will flash indicating that the communication between the Repeater and the main panel was 
lost. 

5. Select the desired Address by pressing the Red Switch (4) consecutively until the Yellow 

(FAULT) LED that corresponds to the desired Address is ON (please refer to the table 
below for additional details). 

6. Confirm the selection by pressing GREEN (1) key. Upon confirmation, the Red (FIRE) 

LED will be activated. Remove selection by pressing the GREEN key again. The 
corresponding LED will be switched OFF.  

7. Exit function pressing OUTPUTS AUXILIARY button. 
8. RESET the repeater by pressing the RESET key. 
9. Repeat steps 3 to 8 to the remaining repeaters. 
10. Reset the main panel.

 

 

 

Address Configuration Table 

Active RED LEDs 

during setup 

ALL LEDS 

OFF 

Z1 

Z2 

Z3 

Z4 

Z5 

Z6 

Z7 

Z8 

Corresponding 

Address 

No Address 

 

TECHNICAL SPECIFICATIONS 

 

TECHNICAL SPECIFICATIONS

 

SUPPLY VOLTAGE 

24V DC nominal (21-29V DC) 

SUPPLY CURRENT 

40 mA 

CONNECTIONS 

Supply: 

+/-

 ; Communication: Tx/Rx & GND 

REPEATER NETWORK 

RS232, RS485, FO or TCP/IP - 1 Display & C 3 Display Only 

PANEL COMPATIBILITY 

ORION 

MAX. HUMIDITY 

95% RH Non-Condensing 

OPERATING TEMPERATURE 

-10ºC to 50ºC 

DIMENSIONS / WEIGHT 

256 (L) x 194 (W) x 75 (H) mm / 1.4 Kg 

COLOUR / CASE MATERIAL 

White or Red / ABS 

 

 

GLOBAL FIRE EQUIPMENT S.A. 

 

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL 

Tel: +351 289 896 560  •  Sales: [email protected]  •  Technical Support: [email protected]  •  

www.globalfire.pt

 

 

Содержание ORION MINI-REP V2

Страница 1: ...e under development The unit is provided as standard with an RS232 interface Power for the ORION MINI REP V2 can be supplied from the control panel s auxiliary power output or from an external 24 Volt...

Страница 2: ...e interconnecting wires used for both supply and data transmission All connections should be performed with all elements of the Fire Detection System unpowered The Repeater should be located where acc...

Страница 3: ...Global Fire Equipment globalfire pt ma_orionminirepv2_01_020000_en_201015 CONNECTION DIAGRAMS ORION MINI REP V2 General hardware and connections layout 3...

Страница 4: ...with INT RS232 WIRE for multi rep use INT RS485 DTL Maximum distance between Panel ORION MINI REP should be 100 meters ORION MINI REP V2 RS 485 interface Multi repeater connection until a maximum of 4...

Страница 5: ...atus LED used to indicate that the panel has functions that have been disabled in either Access Level 2 or 3 modes Check ORION for detailed information TEST This LED is active whenever panel is in TES...

Страница 6: ...ED along with general Fault LED indicates fault on that zone CONTROLS AUTHORISED USER CODE 2244 Some keys will only be operational at the repeater after entering the authorised user code If the operat...

Страница 7: ...r to the table below for additional details 6 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection by pressing the GREEN key again The co...

Отзывы: