Global Fire Equipment ORION MINI-REP V2 Скачать руководство пользователя страница 2

 

 

Global Fire Equipment // 

globalfire.pt 

ma_orionminirepv2_01_020000_en_201015

 

 

 

INSTALLATION 

 

In order to correctly install an ORION MINI-REP, the following steps should be taken: 

a) 

Remove the 4 screws fixing ORION MINI-REP V2 front cover to the unit’s back box. 

b) 

Disconnect flat cable linking ORION MINI-REP V2 mainboard to Interface Board. 

c) 

Fix unit’s back box in required mounting position using the mounting holes provided. 

 

d)

 Reconnect flat cable connecting ORION MINI-REP V2 Main Board to Data Loop Interface board. 

e)

Connect communication wiring to interface following instructions provided in this manual together with the chosen

 

 

 

   

 

 

 

   

 

 

 

 

 

 

interface manual. Refer to ORION panel’s installation manual for further details about operation. 

f)

Connect Power Supply. ORION MINI-REP V2 requires 24V DC supply voltage, which can be derived from the control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

panel auxiliary supply output. Do not apply supply voltage until installation is complete. 

g)

 Place ORION MINI-REP V2 cover onto the unit's back box using the four previously removed screws. 

Before powering up the unit, verify that all connections are correctly made and that there are no open or short circuits on any

 

   

 

 

 

   

 

 

 

 

 

 

 

   

   

 

   

 

of the interconnecting wires used for both supply and data transmission. 
 
All connections should be performed with all elements of the Fire Detection System unpowered. 
 
The Repeater should be located where access to the internal components is not restricted and where the unit is not exposed

 

 

   

 

 

   

 

 

   

 

 

 

 

 

   

 

 

to high levels of moisture, vibration and shock. 
 

WARNING: 

Observe ESD precautions when handling the PCBs. 

 
All cables should be screened. 

 
WARNING: 

Cable screen’s should only be connected at one point to the physical Earth 

connection in order to avoid current loops. 

 
When using RS232 or RS485 interfaces, only use cables recommended for this communication media. As a general rule,

 

 

   

 

 

 

 

 

 

 

 

 

 

   

 

 

cables used for LAN (Cat 5) are suitable for this type of interfacing technology as they are widely available and offer

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

excellent data transmission characteristics. Other signal cables for RS485 communication (twisted pair) can also be used: 
 
12 AWG Signal 88202 Belden 9583 WPW999 
14 AWG Signal 88402 Belden 9581 WPW995 
16 AWG Signal 88602 Belden 9575 WPW991 
18 AWG Signal 88802 Belden 9574 WPW975 
FIRETUF FDZ1000 by Draka 2 core 
PIRELLI type FP200 Gold 2 core 
PIRELLI type FP-PLUS 
 
Fibre Optic: Multi-mode Dual Core sheathed fire proof with 62,5μ/125μ fibre terminated in ST connectors. 
 

 
MECHANICAL DETAILS 

 

 

A

 - Top Cable Entry 

B

 - Rear Cable Entry 

C

 - Data Loop Interface PCB - Stand-offs 

D

 - Back Box - Mounting Holes

 

 

Содержание ORION MINI-REP V2

Страница 1: ...e under development The unit is provided as standard with an RS232 interface Power for the ORION MINI REP V2 can be supplied from the control panel s auxiliary power output or from an external 24 Volt...

Страница 2: ...e interconnecting wires used for both supply and data transmission All connections should be performed with all elements of the Fire Detection System unpowered The Repeater should be located where acc...

Страница 3: ...Global Fire Equipment globalfire pt ma_orionminirepv2_01_020000_en_201015 CONNECTION DIAGRAMS ORION MINI REP V2 General hardware and connections layout 3...

Страница 4: ...with INT RS232 WIRE for multi rep use INT RS485 DTL Maximum distance between Panel ORION MINI REP should be 100 meters ORION MINI REP V2 RS 485 interface Multi repeater connection until a maximum of 4...

Страница 5: ...atus LED used to indicate that the panel has functions that have been disabled in either Access Level 2 or 3 modes Check ORION for detailed information TEST This LED is active whenever panel is in TES...

Страница 6: ...ED along with general Fault LED indicates fault on that zone CONTROLS AUTHORISED USER CODE 2244 Some keys will only be operational at the repeater after entering the authorised user code If the operat...

Страница 7: ...r to the table below for additional details 6 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection by pressing the GREEN key again The co...

Отзывы: