SETTINGS

Addressable IO Unit

Units fitted with a built-in addressable IO unit can be directly connected to a device loop on any of GFE’s addressable 
panels, via the loop connections. These devices will be monitored directly by the panel.

When fitted, these units will be displayed as IO units and its analogue value monitored by the panel. When there are no 
faults on the BCM unit the analogue value reported by the device to the panel is 16 and when in fault condition is 2.

When the device is showing a fault condition, which is always associated with either a fault in the battery charger or 
battery  voltage  as  monitored  by  the  module,  the  panel  will  also  indicate  this  condition  locally  by  turning  ON  the 
GENERAL FAULT and SUPPLY FAULT LEDs. The LCD of the panel will also display the location of module with a clear 
indication of both Loop and Device Address and its associated text label.

Activation of the relay output is accomplished by including the unit in an IO Group. This group can then be assigned to 
either a zone or device. Please refer to the Installation Manual of the panel being used for further information regarding 
cause and effect programming and functions associated with IO units and groups.

1

2

3

1

2

3

Addressable

SW 2 - OFF
SW 1 - OFF

1

2

3

1

2

3

SW 3 - OFF 

SW 3 - ON 

Conventional

SW 2 - ON
SW 1 - ON

SW 3 - OFF

When OFF the module will monitor the battery voltage and it will disconnect battery when 
below 21V DC avoiding deep discharge.

SW 3 - ON

In this case the battery voltage monitoring is disabled.

SPLY IN

ON when supply input is present.

CHAR FLT

ON when battery charger is faulty or batteries are not connected or faulty.

BAT FLT

ON when battery voltage is below 21 V DC.

Manufacturers of Fire Detection Equipment

globalfire.pt

INSTALLATION MANUAL V.3 - 07/2016

GFE-BCM

Содержание GFE-BCM

Страница 1: ...Manufacturers of Fire Detection Equipment globalfire pt INSTALLATION MANUAL V 3 07 2016 GFE BCM INSTALLATION MANUAL version 3 07 2016 GFE BCM BATTERY CHARGER MONITOR ...

Страница 2: ...monitored and current output controlled and limited to a maximum of 4 Amps Two auxillirary output relays are provided both equipped with a set of changeover contacts One is used to signal fault conditions The Outputrelay whichisonlyavailableforaddressableversions canbeusedwhenincludedinanIOGroup FEATURES BatteryChargerMonitoredbyAddressablePanel FaultRelayOutput RelayO PRemotelyControlledbyPanel L...

Страница 3: ...forfurtherdetails FaultRelayTerminalConnections A single pole changeover relay is provided Activation of relay is caused by any fault detected within the monitoring circuitryofthemodule Whendeviceisinfaultcondition theanalogue valuereportedtothepanelis2anditisindicated by the panel as a supply fault In these cases both the GENERAL and SUPPLY FAULTS LEDs are ON Location of the fault is also provide...

Страница 4: ...8VDC Currentdrivecapacitydependsonmodulespecification SupplyInputTerminalConnections FaultRelayTerminalConnections Asinglepolechangeoverrelayisprovided Activationofrelayiscausedbyanyfaultdetected withinthemonitoringcircuitryofthemodule F1 Battery Fuse SPLY IN CN2 BAT K2 BAT FLT CHAR FLT OUT 24V IN A B C NC C NO FAULT RELAY D 1 2 3 Manufacturers of Fire Detection Equipment globalfire pt INSTALLATIO...

Страница 5: ...module with a clear indicationofbothLoopandDeviceAddressanditsassociatedtextlabel Activation of the relay output is accomplished by including the unit in an IO Group This group can then be assigned to either a zone or device Please refer to the Installation Manual of the panel being used for further information regarding causeandeffectprogrammingandfunctionsassociatedwithIOunitsandgroups 1 2 3 1 2...

Страница 6: ... output to maintain the batteries in a fully chargedstate Beforeconnectingthebatteriescheckthevoltageacrossthebatteryconnectionterminals Itshouldbe28 0V 0 5V NOTE arcing and fire risk Never short circuit the battery terminals Always connect the blue wire between the batterieslast BLACK RED BLUE F1 Battery Fuse BAT OUT 24V IN 1 2 3 Replacement Battery Fuse F1 GFE BCM 3 any version 3 A 5x20 mm Quick...

Страница 7: ... 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 100 101 102 103 104 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 109 110 111 112 1 2 3 4 5 6 7 8 55 1 2 3 4 5 6 7 8 56 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 46 47 48 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 37 38 39 40 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 ...

Страница 8: ...ONTROL MODULE GFE BCM 3 Electronic Module Fixing Holes Electrical Mains Fused Connector SUPPLY IN INDICATOR GREEN BATTERY CHARGER FAULT INDICATOR YELLOW BATTERY VOLTAGE FAULT INDICATOR YELLOW TOP CABLE ENTRY Manufacturers of Fire Detection Equipment globalfire pt INSTALLATION MANUAL V 3 07 2016 GFE BCM ...

Страница 9: ... x 242 W x 107 H mm 1 7 Kg 7 Kg inc 2 x 7 AH Bat 230 V AC 10 15 Monitored 1 7 A OR 2 4 A 28 V DC nominal 1 A max Max 2 x 12 V 7 AH Lead Acid VRLA 3 A Changeover 30 V DC 1 A Resistive 1 7 mA Quiescent 2 4 mA Fault Changeover 240 V AC 10 A Resistive 10ºC to 50º Max 95 no condensation IP21 404 L x 242 W x 107 H mm 1 7 Kg 7 Kg inc 2 x 7 AH Bat 107 mm 404 mm 242 mm L2 L1 1 2 3 4 5 6 7 8 BAT OUT 24V IN ...

Страница 10: ...NSTALLATION MANUAL V 3 07 2016 GFE BCM GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Support techs globalfire pt www globalfire pt ...

Отзывы: