Global Fire Equipment //
globalfire.pt
ma_chmcomm_01_010001_en_191121
Upload a configuration without broadcast
Panel 1
, due to USB Chameleon Connector Config Update, changed the local configuration and the configuration was not
broadcasted to other system panels. All panels will trigger “Panel Configuration Mismatch” on Panel 1. Panel 1 will trigger
the fault mentioning all other panels on the queue.
After an USB Config Update the menu
8-5-4 Broadcast Configuration
should be executed in order to copy same
configuration to all network panels.
The following errors should be mentioned on the panels:
Panel 1
Panel 2
Panel 3
PANEL 02
PANEL CONFIGURATION MISMATCH
TOTAL NUMBER OF FAULTS 0002
PANEL 01
PANEL CONFIGURATION MISMATCH
TOTAL NUMBER OF FAULTS 0001
PANEL 01
PANEL CONFIGURATION MISMATCH
TOTAL NUMBER OF FAULTS 0001
PANEL 03
PANEL CONFIGURATION MISMATCH
TOTAL NUMBER OF FAULTS 0002
27