NOTE:

 This menu only evaluates the RX (receiving) input per channel. Meaning that it will only show 

ERR if, since the last reset, it somehow stopped receiving messages on that specific channel. After a 
reset, if that specific channel never received any message then “---” will be shown.
 

 
 

Check Known Panels 

After all communication channels are verified and showing OK: On each panel, accessing the menu 

8-5-2 Known Panels

 it’s 

possible to check the following: 

Number of recognized panels:

 Check if each panel is aware of all other panels 

Own Panel:

 Check if the address is the correct one. 

List of panels:

 Same as above in a more graphic network view. 

 

This is a very important verification, since it is here that you can check if the panel is not aware of other panels 
announcements. If some panel is not listed, please re-check the “non-listed” panel connections. 
 

Debug Network messages 

Please access menu 

8-5-3 Installation Status

 to check local network messages. Example: If no connection is detected, then 

a “No nodes detected” message is shown.  
Use this menu to have a system network report. 
 

Restart Network Panels 

Restart a Panel: All network panels should restart as well. 
 

Close network LOOP  

At this stage all panels should be aware of all other panels and all communications channels are displaying OK on the 

8-5-5 Menu. 

 
Before proceeding with the commissioning, the communications path should now be “closed” creating a redundant two way

 

 

 

 

 

 

 

 

 

   

 

   

 

 

 

messages path. Please refer to Network Topology chapter for further info.  
If panel communication channels are available, more redundant connections can be made (example with NODE+ or OCTO+

 

 

 

 

 

 

 

 

 

   

 

 

 

   

 

there are three channels available per panel). The Chameleon Network supports mesh network if extra channels are

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

available. 
 

Please repeat the Check All Communications Channels procedure on the new added network path. 

 

Upload and Broadcast Configuration to the network 

Use the Chameleon Connector tool (connected by USB) to upload configuration on one chosen panel.  
After this a 

8-5-4 Broadcast Configuration

 should be made in order to copy same configuration to all network panels.  

 

NOTE:

 If this step is not correctly done, a “mismatch configuration” error may be shown. 

 

Clear NVRAM 

This is only needed if a “clean installation” setup is desired. 

Only recommended for “new” installations. Do not perform this on an already installed system! 
 

NOTE:  

- ATTENTION: THE EVENT LOG WILL BE DELETED WITH THIS OPERATION!!! 
- ALL LOCAL INFO REGARDING STATUS AND NETWORK INFO WILL BE DELETED 
- THE CUSTOMER CONFIGURATION IS KEPT INTACT. 

 

Wait 2 minutes for network recognition 

If no fault message is shown, then the network system is correctly installed. 
 

Change system to Active Mode 

Go to menu 

8-4-1 Active/Installation Mode

 and switch to active mode 

 

 

23 

Содержание CHAMELEON GEKKO

Страница 1: ...RODUCTION 8 Mains Power connection 8 Control Panels and Repeaters Location 8 CHAMELEON NETWORK TOPOLOGY 9 Closed Loop Network example 9 Open Loop Network example 10 Mesh Network example 10 Extended di...

Страница 2: ...23 Wait 2 minutes for network recognition 23 Change system to Active Mode 23 Verify remote devices on the installation 24 TROUBLESHOOTING 24 COMMUNICATION FAILURE 24 RX connection break on Panel 2 dis...

Страница 3: ...n independent SYSTEM EVENT LOG rolling 10000 entries Customer configuration can be broadcasted to all panels over the network High Immunity in high latency network connections Configuration mismatch d...

Страница 4: ...e Optic Link A connection method for data that uses light instead of electrical signals The connection is made using fibre optic cables rather than copper electrical cables Fibre optic signals can tra...

Страница 5: ...Global Fire Equipment globalfire pt ma_chmcomm_01_010001_en_191121 IDENTIFYING COMPONENTS and COMMUNICATIONS INSIDE GEKKO INSIDE OCTO 5...

Страница 6: ...Global Fire Equipment globalfire pt ma_chmcomm_01_010001_en_191121 NOTE ALL CHANNELS CHx SHOULD BE CONNECTED THROUGH INTERFACES 6...

Страница 7: ...S422 P2P S FIBRE OPTIC INTERFACE INT FO P2P D INT FO P2P S INTERFACE FOR TCP IP COMMUNICATION INT TCP IP P2P MIXED INTERFACE INT RS422 P2P MIX FO All Interfaces should be connected to panels using the...

Страница 8: ...positions of the PCBs before powering up the system ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTALLING PRINTED CIRCUIT BOARDS WARNING observe ESD precautio...

Страница 9: ...ations failure In the case of unused connectors network derivations and mesh wired topologies can be used Nevertheless the Closed Loop Example is the most commonly used and recommended Closed Loop Net...

Страница 10: ...fire pt ma_chmcomm_01_010001_en_191121 Open Loop Network example NOTE THIS IS NOT RECOMMENDED IT DOES NOT HAVE COMMUNICATIONS REDUNDANCY Mesh Network example NOTE COMMUNICATIONS HIGHLY REDUNDANT DIFFE...

Страница 11: ...splay In this situation by applying a Chameleon Display you will have an extension of the Fascia with a maximum of two Please do not confuse with Network Addressed Chameleon Repeater panel RS422 FIBRE...

Страница 12: ...ions or short circuits by creating a bi directional communications flow If the panel loses communications with other elements of the network it will have the option via opposite path RS422 422 may be...

Страница 13: ...wo panels with two redundant independent Fibre network paths This will use 4 flat cables two per panel and two for each physical connection Connections are made using fibre optic cables instead of cop...

Страница 14: ...CH1 CH2 CH1 CH2 CH1 TX2 RX1 TX2 RX1 TX2 RX1 RX2 RX1 RX2 TX1 RX2 TX1 If more panels are connected the same scheme can be applied Continue to connect CH2 of one Repeater to CH1 of the next Repeater fol...

Страница 15: ...the Panel On the CHAMELEON REP the flat cable interface connections are different from the GEKKO as shown below GEKKO connections are made on the front of PCB and on CHAMELEON REPEATER are made on th...

Страница 16: ...chnical support INT TCP IP P2P This interface allows a Peer to Peer connection It is necessary one Interface for each physical link acting as a serial point to point link NOTE This is not a double int...

Страница 17: ...obtained directly from the auxiliary power supply output of neighbour panel Apply power to the repeater If after a few seconds upon completion of the initialization phase the LCD display shows the me...

Страница 18: ...able for panels programmed to ZEOS Protocol 6 3 1 Select Device Behaviour Mode 6 3 2 Flashing LEDs On Off 6 3 3 Disable Specific Flashing Leds 6 3 4 Re calibrate All Devices 6 3 5 Check for Devices Ne...

Страница 19: ...system is not in fault nor fire Press ENTER to skip an entry and after each entry It is important to set the date and time because it is used in the event logging and may also be used to change the de...

Страница 20: ...allows changing the Panel Network Number address This should be unique in the network NOTE The Chameleon Rep will need to set an unique Panel Network Number 8 5 2 Known Panels This function will show...

Страница 21: ...on port 01 to 64 ODYSSEY not applied CH2 working as an ODYSSEY port with the specified PANEL ADDRESS XX not applied SHORT MSG 1 CH2 working as short text serial port DECT no fault B Alarm V PreAlarm 2...

Страница 22: ...nge on each panel 8 4 1 menu If any fault is triggered after reset please acknowledge by pressing BUZZER SILENCE button If the triggered fault is related with mismatch configuration or communications...

Страница 23: ...panels and all communications channels are displaying OK on the 8 5 5 Menu Before proceeding with the commissioning the communications path should now be closed creating a redundant two way messages...

Страница 24: ...only reported by RX receiving channel evaluation Go to menu 8 5 5 Communication Channels to check connections RX connection break on Panel 2 disconnect RX1 or RX2 Panel 2 is no longer receiving in on...

Страница 25: ...F FAULTS 0001 PANEL 01 COMMUNICATION FAILURE TOTAL NUMBER OF FAULTS 0001 PANEL 01 COMMUNICATION FAILURE TOTAL NUMBER OF FAULTS 0001 TX2 connection break on Panel 2 Panel 3 is no longer receiving in on...

Страница 26: ...ers have not All panels will trigger Panel Configuration Mismatch on Panel 1 Panel 1 will trigger the fault mentioning all other panels on the queue Panel 1 Panel 2 Panel 3 PANEL 02 PANEL CONFIGURATIO...

Страница 27: ...r the fault mentioning all other panels on the queue After an USB Config Update the menu 8 5 4 Broadcast Configuration should be executed in order to copy same configuration to all network panels The...

Страница 28: ...ation Mode Panel 1 TX2 is not properly wired Meaning that with an open loop Panel 1 is able to see Panel 2 and Panel 3 But Panel 2 and 3 are unable to see Panel 1 on the network Panel 1 is missing Pan...

Страница 29: ...2 Known Panels Known 03 01 02 03 Menu 8 5 5 Communications Channels CH1 CH2 CH3 OK OK Menu 8 5 5 Communications Channels CH1 CH2 CH3 OK Menu 8 5 5 Communications Channels CH1 CH2 CH3 OK OK GLOBAL FIRE...

Отзывы: