10
107299
PROPANE/LP GAS HEATER
CHECKING GAS
CONNECTIONS
WARNING: Test all gas pip-
ing and connections for leaks
after installation or servicing.
Correct all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
heater. See guidelines under
Con-
necting to Gas Supply, page 9.
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1.
Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2
psig will damage heater regulator.
2.
Cap off open end of gas pipe where
equipment shutoff valve was connected.
3.
Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
4.
Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5.
Correct all leaks at once.
6.
Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1.
Close equipment shutoff valve (see Fig-
ure 15).
2.
Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
3.
Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 16). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.
4.
Correct all leaks at once.
Figure 15 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff Valve
Figure 16 - Checking Gas Joints
INSTALLATION
Continued
Pressure Testing Heater Gas
Connections
1.
Open equipment shutoff valve (see Fig-
ure 15).
2.
Open propane/LP supply tank valve.
3.
Make sure control knob of heater is in
the OFF position.
4.
Check all joints from equipment shutoff
valve to control valve (see Figure 16).
Apply mixture of liquid soap and wa-
ter to gas joints. Bubbles forming show
a leak.
5.
Correct all leaks at once.
6.
Light heater (see Operating Heater,
page 11 for non-thermostat models or
pages 12 and 13 for thermostat model).
Check all other internal joints for leaks.
7.
Turn off heater (see To Turn Off Gas
To Appliance, page 11 for non-thermo-
stat models or page 12 for thermostat
model).
8.
Replace front panel.
Propane/LP
Supply Tank
Control
Valve
Location
Equipment
Shutoff Valve