31
Glentek Inc., 208 Standard Street, El Segundo, California 90245, U.S.A. (310) 322-3026
SMA8105, SMA8205, and SMA8305 MANUAL
Resolution
PLD
Code
PLD
Part
Number
S1-1
S1-2
Bits
Min.
S3-7 S3-8
Max.
RPM
(S3-5:ON)
Tach. Volts
V/1000RPM
125
000
8000-1212
ON
ON
10
ON
ON
62,400
0.13
128
000
8000-1212
ON
OFF
10
ON
ON
62,400
0.13
250
000
8000-1212
OFF
ON
10
ON
ON
62,400
0.13
256
000
8000-1212
OFF
OFF
10
ON
ON
62,400
0.13
500
001
8000-1213
ON
ON
12
OFF
ON
15,600
0.5
512
001
8000-1213
ON
OFF
12
OFF
ON
15,600
0.5
1000
001
8000-1213
OFF
ON
12
OFF
ON
15,600
0.5
1024
001
8000-1213
OFF
OFF
12
OFF
ON
15,600
0.5
2000
010
8000-1214
ON
ON
14
ON
OFF
3,900
2
2048
010
8000-1214
ON
OFF
14
ON
OFF
3,900
2
4000
010
8000-1214
OFF
ON
14
ON
OFF
3,900
2
4096
010
8000-1214
OFF
OFF
14
ON
OFF
3,900
2
360
011
8000-1218
ON
ON
12
OFF
ON
15,600
0.5
720
011
8000-1218
ON
OFF
12
OFF
ON
15,600
0.5
2160
011
8000-1218
OFF
ON
14
ON
OFF
3,900
2
3600
011
8000-1218
OFF
OFF
14
ON
OFF
3,900
2
625
100
8000-1215
ON
ON
12
OFF
ON
15,600
0.5
1250
101
8000-1216
ON
ON
14
ON
OFF
3,900
2
2500
110
8000-1217
ON
ON
14
ON
OFF
3,900
2
5.4.3 Encoder Output Resolution Configuration:
Refer to Appendix B drawing 8000-1430 and 8000-1431. There are nineteen standard
resolutions. Up to four resolutions are contained in a single PLD. To configure the pre-amp
for a given resolution, ensure that you have the correct PLD (U13) and then configure the
dip-switches S1-1, S1-2, S3-7 and S3-8 as shown below. The PLD code refers to the table in
the model numbering chapter and the PLD part number is marked on the part.
The BITS refer to the Resolver-to-Digital resolution which must be factory configured.
Encoder resolution may be changed at any time to a resolution which requires the same or
fewer
bits. Increasing the bits increases the possible encoder resolution, but decreases the
maximum motor RPM(refer to the table above). The Tach. Volts (V/1000RPM) are given for
the MAX. RPM of the BIT resolution. Consult a Glentek applications engineer should you
have any questions.
NOTE: The MAX. RPM in the above table is valid when RANGE (S3-5) is ON. The MAX.
RPM is half of what is shown in the table when RANGE (S3-5) is OFF.
Содержание SMA8105
Страница 48: ...48 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX A AMPLIFIER DRAWINGS...
Страница 50: ...50 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX A AMPLIFIER DRAWINGS...
Страница 52: ...52 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX A AMPLIFIER DRAWINGS...
Страница 54: ...54 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX A AMPLIFIER DRAWINGS...
Страница 56: ...56 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX B PERSONALITY MODULE...
Страница 58: ...58 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX B PERSONALITY MODULE...
Страница 60: ...60 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX B PERSONALITY MODULE...
Страница 62: ...62 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026 APPENDIX B PERSONALITY MODULE...
Страница 64: ...64 Glentek Inc 208 Standard Street El Segundo California 90245 U S A 310 322 3026...