Operation
26
Troubleshooting
Table 7 Troubleshooting Service Guide
Symptoms
Possible Cause
Selector switch is in “ON” position & pump will not start.
1. Open disconnect switch
2. Tripped overloads
3. Phase monitor fault
4. Low tank level
Pump is rotating but no pressure is established.
1. Improper rotation
2. No water in reservoir
3. Valves not open
4. No back pressure
5. Pump suction blocked
6. Pump seal leaking
Pump runs properly, but compressor does not start.
1. Compressor is not getting energized
2. Flow switch not activated
Compressor hums but will not start.
1. Low line voltage
2. Motor windings shorted to ground
3. Internal compressor damage
4. Improperly wired
Compressor will not start (no hum).
1. Open disconnect
2. Thermal overload open
3. Relay not closing to start compressor
4. Bad motor windings
5. Loss of refrigerant charge
Compressor starts but trips on internal protector
1. High suction or discharge pressure
2. Low line voltage
3. Bad motor windings
The unit short cycles.
1. Low refrigerant charge
2. Defective expansion valve
High refrigerant pressure fault
1. Dirty air filters
2. Refrigerant overcharge
3. Dirty condenser
4. Malfunction of fan motor
5. Excessive ambient air temperature
Low refrigerant pressure fault
1. Extreme low ambient temperature
2. Refrigerant leak
3. Lack of fluid flow through heat exchanger
4. Liquid line solenoid valve stuck or not opening
5. Expansion valve stuck or lost bulbwell charge.
Fluid flow fault
1. Pump not running
2. System not filled
3. Air in the system
4. Flow switch paddle stuck
Pump Overload fault
1. Overload setting incorrect
2. Bad motor windings
3. Low pump pressure due to low piping resistance
Phase Monitor fault
1. Incorrect line phasing
2. Low/High incoming voltage
3. Voltage imbalance between phases
Low Tank Level fault
1. Low/no fluid in Heat Exchanger reservoir
2. Float switch stuck in the open position
Содержание Koolant Koolers WO2-2-10000
Страница 1: ...Original Instructions 800 968 5665 dimplexthermal com User Manual...
Страница 17: ...Installation 11 Figure 7 Removal or Doors Blockers 3 8 DOOR BOLT 3 8 BLOCKER BOLT BLOCKER DOOR...
Страница 18: ...Installation 12 Figure 8 Removal of Lower Doors LATCHES...
Страница 28: ...Operation 22 Figure 10 Controller Restart Warning Figure 11 Controller Home Page...
Страница 30: ...Operation 24 Figure 15 Controller On Off Menu Figure 16 Controller Pump Enable Disable Menu...
Страница 31: ...Operation 25 Figure 17 Controller Setpoint Menu Figure 18 Controller Alarm Menu...
Страница 37: ...Internal Components 31 Figure 20 Door Side PUMP 2 PUMP 1 FLOAT SWITCH...
Страница 44: ...Appendix A Plumbing 38 Appendix A Plumbing...
Страница 45: ...Appendix B Pump Curve 39 Appendix B Pump Curve...
Страница 46: ...Appendix C Refrigeration WO2 2 5000 40 Appendix C Refrigeration WO2 2 5000...
Страница 47: ...Appendix C Refrigeration WO2 2 7500 41 WO2 2 7500...
Страница 48: ...Appendix C Refrigeration WO2 2 10000 42 WO2 2 10000...
Страница 53: ...Appendix G Chiller Registration 47...