www.gdts.one
DOK4x HOIAO WxDEN · FD 9912
9
Air-to-water heat pump 6 kW
English
5 Installation
5.1 Outdoor unit
Among other things, when selecting the installation locations
for the indoor and outdoor units, ensure that the required
length of refrigerant line is as short as possible. The standard
length of a refrigerant line is 3m. It is possible to have a special-
ist extend the refrigerant line to a length of 7m up to a maxi-
mum of 10m, provided that the information in see cap. 6.7 on
page 17 has been heeded.
HINWEIS
ºº
º
ºº
º
NOTE
In snowy areas, the foundation must be of a sufficient height
to guarantee a free air intake.
HINWEIS
ºº
º
ºº
º
NOTE
The cold air is blown out downwards at the side and can result
in black ice on paths and platforms.
The outdoor unit must be installed on a permanently even,
smooth and horizontal surface. The entire base of the frame
should lie directly on the floor. To prevent small animals from
entering the inside of the device, the connection hole in the
base plate must be sealed where necessary.
The outdoor unit is designed for installation close to walls on
even ground and for installation on a wall bracket. The outdoor
unit must always be fixed in place at the installation location
(Cap. 12.1 on page 25). The responsibility for the heat pump in-
stallation lies with the specialist system construction company.
During the installation, local requirements such as building reg-
ulations, static load of the building, and wind exposure must be
accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured if the clearance displayed below is
maintained.
The specified dimensions are valid for stand-alone installation
only.
If multiple outdoor units are set up next to each other, the re-
quired minimum distance at the side adds up. Ensure that the
cold expelled air is not sucked in again.
HINWEIS
ºº
º
ºº
º
NOTE
Do not restrict or block the area around the intake or the air
outlet area.
HINWEIS
ºº
º
ºº
º
NOTE
Observe country-specific building regulations!
HINWEIS
ºº
º
ºº
º
NOTE
The physical impacts must be observed for installation close
to walls. No windows or doors should be present in the area
surrounding the air outlet of the fan.
HINWEIS
ºº
º
ºº
º
NOTE
In cases of installation close to a wall, there may be more sed-
iment in the intake and air outlet area due to the air flow. The
colder outside air outlet should discharge in such a way as to
not increase the heat losses in heated neighbouring rooms.
HINWEIS
ºº
º
ºº
º
NOTE
Installation in a hollow or in an inner courtyard is not permit-
ted because cooled air collects at ground level and is drawn in
again by the heat pump during extended periods of operation.
1,0 m
0,3 m
0,5 m
0,5 m
Содержание 06CHOIAOC6
Страница 2: ......