Hot and Cold Water System

Pipe Sizing / Materials

To achieve even distribution of the available supply of hot and cold water, it is 
important in any mains pressure system, that the piping in a dwelling should be 
sized in accordance with BS 6700. This is particularly important in a large property 
with more than one bathroom.

However, the following rule of thumb guide lines should be adequate for most smaller 
property types as long as water pressures are within the recommended range of 2-3 
bar.

1.  A 15mm copper or equivalent external service may be suffi cient for a small 

1bathroom dwelling (depending upon the fl ow rate available), but the minimum 
recommended size for new dwellings is 22mm (25mm MDPE).  For the BMBP 225 
model we recommend a 28mm (32mm MDPE) supply pipe.

2.  The internal cold feed from the main incoming stop tap to the BoilerMate  
 

should be run in 22mm pipe.  The cold main and hot draw-off should also  

 

be run in 22mm as far as the branch to the bath tap.  

3. The 

fi nal branches to the hand basins and sinks should be in 10mm and to  

 

the  baths and showers in 15mm. (1 metre minimum)

4.  If an external hose tap is provided this should be branched in 15mm pipework  
 

from the cold pipework as near to the incoming mains as possible.

5.  We would recommend that best results for a balanced system are achieved 

by fi tting appropriate fl ow regulators to each hot and cold outlet. This is 
particularly relevant where the water pressures are above the recommended 
water pressure range of 2-3 bar, or the dwelling is 3 storey.  Details of suitable 
fl ow regulators  are provided in Appendix.

All the recommendations with regard to pipework systems in this manual are generally 
based on the use of BS/EN Standard copper pipework and fi ttings.

However, we are happy that plastic pipework systems can be used in place of copper 
internally as long as the chosen system is recommended for use on domestic hot and 
cold water systems by the manufacturer and is installed fully in accordance with their 
recommendations.

It is also essential that if an alternative pipework material/system is chosen the 
manufacturer confi rms that the design criteria of the new system is at least equivalent 
to the use of BS/EN Standard copper pipework and fi ttings.

Taps/Shower Fittings

Aerated taps are recommended to prevent splashing.

Any type of shower mixing valve can be used as long as both the hot and cold 
supplies are mains fed.  However, all mains pressure systems are subject to 
dynamic changes particularly when other hot and cold taps/showers are opened 
and closed, which will cause changes in the water temperature at mixed water 
outlets such as showers.  For this reason and because these are now no more 
expensive than a manual shower we strongly recommend the use of thermostatic 
showers with this appliance.  These must be used in 3 storey properties where 
the impact on pressure/temperature of opening another tap in the system is 
greater than normal.

The shower head provided must also be suitable for mains pressure supplies.

However, if it is proposed to use a ‘whole body’ or similar shower with a number of 
high fl ow/pressure outlets please discuss with the Gledhill technical department.

The hot water supply to a shower-mixing valve should be fed wherever practical 
directly from the BoilerMate BP or be the fi rst draw-off point on the hot circuit.  The 

cold supply to a shower-mixing valve should 
wherever practical be fed directly from the 
rising mains via an independent branch.  The 
shower must incorporate or be fitted with 
the necessary check valves to provide back-
syphonage protection in accordance with the 
Water Regulations. 

The supply of hot and cold mains water directly 
to a bidet is permitted provided that it is of the 
over-rim fl ushing type and that a type ‘A’ air 
gap is incorporated.

Hot and Cold Water System.

If the length of the hot water draw off 
pipework is excessive the delivery time may 
be unacceptable before hot water is available at 
the tap, you may wish to consider using either 
trace heating to the hot water pipework such 
as the Raychem HWAT system or secondary 
circulation. Please consult Gledhill Technical 
Department for further details.

It is important that the cold water pipework 
is adequately separated/protected from any 
heating/hot water pipework to ensure that 
the water remains  cold and of drinking water 
quality.

Содержание BMBP125

Страница 1: ...oilerMate BMBP 145 BoilerMate BMBP 185 BoilerMate BMBP 215 BoilerMate BMBP 225 All models comply with the Hot Water Association specification for thermal stores For a sealed or an open vented central heating and mains pressure hot water supply system incorporating a thermal store ...

Страница 2: ...eme as an option to notifying the Local Authority directly Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1st January 06 CORGI operates a Self Certification Scheme for gas heating appliances These arrangements represent a change from the situation whereby compliance with theBuildingRegulationswasacceptediftheBenchmarkLogbookwascompletedand this was then left ...

Страница 3: ...ners or Consultants concerned with the design and installation Please Note We do not therefore accept any responsibility for matters of design selection or specification or for the effectiveness of an installation containing one of our products unless we have been specifically requested to do so All goods are sold subject to our Conditions of Sale and Warranty Terms which are set out at the rear o...

Страница 4: ...mary heat exchanger flow C4 Primary heat exchanger return C5 Open vent C6 Cold feed C7 Drain C8 Immersion heater boss All the connections are also labelled on the appliance It is essential that the pipework is connected to the correct connection Note The safety open vent and cold feed expansion must be connected to the F E cisternusingthepipeworkassemblyprovided Do not alter or connect any pressur...

Страница 5: ...onnections 22mm 22mm 22mm 28mm 28mm MCW DHW pipe connections 22mm 22mm 22mm 22mm 22mm Cold feed expansion connection 15mm 15mm 15mm 15mm 22mm Safety open vent connection 22mm 22mm 22mm 22mm 22mm Drain connection R R R R R Maximum Head Thermal Store 6 meters 6 meters 6 meters 6 meters 6 meters Maximum pressure heating circuit 3 bar 3 bar 3 bar 3 bar 3 bar Volume of primary heat exchanger 4 9 litres...

Страница 6: ...Dimensions Model Height D Width E Depth F BMBP 125 2012 680 600 BMBP 145 2012 680 600 BMBP 185 2173 680 600 BMBP 215 2334 680 600 BMBP 225 2534 680 600 Note The Appliance dimensions above do not allow for the100mm high installation base The following table of minimum cupboard dimensions only allow the minimum space requiredfortheappliance includingthetopup cistern Any extra space required for shel...

Страница 7: ...pass valve 4 Manual air vent 5 3 port mid position valve 6 Wiring centre Note All components to be supplied by the installer Example installation of an S plan system 1 Pump 2 Storethermostat 3 Bypass valve 4 Manual air vent 5 Central heating zone valve 6 Hot water zone valve 7 Wiring centre Note All components to be supplied by the installer ...

Страница 8: ...approximate and subject to a tolerance of 10mm in any direction Space will also be required for a 15mm cold water supply and a 22mm warning overflow pipe Note All dimensions are shown in mm and are to the centre line of pipework Connection Details Dimensions For Top Of Unit Figure 5 570 595 including the door clock 580 58 117 370 Cold Feed Expansion 330 Open Vent Connection Details Dimensions For ...

Страница 9: ... s 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Pressure loss mWG 6 5 4 3 2 1 0 BMBP125 BMBP145 BMBP225 BMBP185 BMBP215 Figure 6 Pressure drop across the DHW heat exchanger DHW flow rate l min 5 10 15 20 25 30 Pressure loss bar 4 0 3 5 3 0 2 5 2 0 1 5 1 0 0 5 0 BMBP125 BMBP145 BMBP185 BMBP215 BMBP225 Figure 7 ...

Страница 10: ...actoryfittedin linescaleinhibitorshouldbe specified at the time of order for hardness levels between 200 and 300 ppm mg l Wherethewaterisveryhardie300ppm mg l andabovethe optionalpolyphosphate type inhibitor should be specified at the time of order However this will need to be fitted by the installer at a suitable point in the cold water supply to the appliance If scale should ever become a proble...

Страница 11: ... system is chosen the manufacturer confirms that the design criteria of the new system is at least equivalent to the use of BS EN Standard copper pipework and fittings Taps Shower Fittings Aerated taps are recommended to prevent splashing Any type of shower mixing valve can be used as long as both the hot and cold supplies are mains fed However all mains pressure systems are subject to dynamicchan...

Страница 12: ... designed to be installed with condensing or non condensing oil or gas boiler which is capable of delivering hot water at a minimum temperature of 80 C The boiler must be set to operate at nominal 82 C flow which usually corresponds to maximum boiler control thermostat setting It is recommended that an automatic bypass is fitted to compensate for pressure and hence the flow rate changes in the hea...

Страница 13: ...teBP i e the maximum static pressure in the store must not exceed 0 6bar The primary pipework connecting the boiler the thermal store and central heating system should be sized to achieve either 11 C rise across the boiler or the maximum temperature rise specified by the boiler manufacturer which ever is smaller But in any case should not be less than 22mm copper tube or equivalent The pressure lo...

Страница 14: ...A boiler used in a sealed heating system must be suitable for this application i e must be fitted with an overheat cut out thermostat It is recommended that the F E cistern for the store is fitted at a high level in the same cupboard as the BoilerMate BP However it can be fitted remotely up to 6m above the base of the BoilerMate BP The F E cistern overflow warning pipe should be installed in a mat...

Страница 15: ...d on a material which will not easily deteriorate if exposed to moisture The floor of the cupboard needs to be level and even and capable of supporting the weight of the appliance when full Details of the weight when full is provided in the Technical Data section The appliance is designed to operate as quietly as practicable However some noise from pumps etc is inevitable in any heating system Thi...

Страница 16: ...ntsforelectricalInstallationsBS7671 2 The electrical mains supply needs to be 230V 50Hz 3 A means for disconnection from the supply mains having a contact separation in all poles that provides full disconnection under over voltage category III conditions must be incorporated in the fixed wiring in accordance with the wiring rules This shall be located within 1m of the appliance and only serve the ...

Страница 17: ...yforconnection ofthepipeworkandelectricalsupplies Thefeed andexpansioncisternsupportshallbeinstalled ensuringthatthebaseisfullysupportedandthe working head of the appliance is not exceeded and the recommended access is provided for maintenance see the Technical Data section For further information on manual handling See Appendix Note Althoughtheaboveguidanceisprovided any manual handling lifting o...

Страница 18: ...BoilerMate BP appliance Obviously if installed in the roof space the feed and expansion cistern and any pipework will need to be adequately insulated to protect against frost damage If the automatic fill version appliance is used the overflow warning pipe shall have a continuous fall be fitted to discharge clear of the building and be sited so that any Overflow can be easily observed It shall also...

Страница 19: ...oughtheBoilerMateBPhasnospecialwatertreatmentrequirements theradiators and other parts of the circuit will benefit from the application of a scale and corrosion inhibitor such as Sentinel X100 or a Protector such as Fernox MB1 Thevolumes concentrationshouldbecalculatedinaccordancewiththemanufacturers instructions allowing the volume for the primary coil shown in the Table in the Technical Data sec...

Страница 20: ...pework in the BoilerMate BP cupboard DO plumb the overflow warning pipe if fitted in a 20mm internal diameter pipe material which is suitable for use with a heating F E cistern in accordance with BS 5449 such as copper and ensure it has a continuous fall and discharges in a conspicuous external position DO check that the primary system pressure does not exceed 2 bar when the whole of the system is...

Страница 21: ...k Code 1 Immersion heater Incalloy 825 immersion heater with dual control safety thermostat XB078 2 Brawa mix thermostatic hot water blending valve XC007 3 Mini expansion vessel XB024 4 Scale inhibitor PCB XB142 5 ITC control thermostat XC010 4 3 2 1 5 ...

Страница 22: ... thermostat this should be set at maximum Checkthattheboilerflowtemperatureisadequatewhenitstopsfiring Boilersshould provide a flow temperature of 82 3 C but temperatures as low as 75 C will allow the BoilerMate BP to provide a satisfactory performance Check that the store is charging to at least 75 C Check that the thermostatic blending valve is set to decline water between 55 C 57 C If all the a...

Страница 23: ...ood House 40 New Road Stourbridge West Midlands DY8 1PA TELEPHONE 01384 442611 FAX 01384 442612 Water Savings Water Related Costs Can Be Reduced By Good Plumbing Practice TAPS MIXERS SHOWERS Unregulated 25 30 l m Regulated 10 12 l m Over 20 l m 5 6 or 8 l m 2 tap half open Fitted with regulator Unregulated 4 Fixing Options For Taps Mixers 1 MK Range Combined Regulators Aerator forscrewingontoTaps ...

Страница 24: ...Page 24 APPENDIX APPENDIX B ...

Страница 25: ... these allow one or two persons to have a purposely designed hold at the top of the appliance to ensure easy lifting at the top of the product e Taking the lead for team lifts As more than one person is required for these products ensure that one person is taking the lead This may be you so ensure that each person that is helping is made aware of the weight and of the items listed within this asse...

Страница 26: ...etailed in the installation and service instructions 9 2 6 Defects caused by corrosion or scale deposits are not covered by any Guarantee 9 2 7 Where we agree to rectify any defect we reserve the right to undertake the work on our own premises 9 2 8 We will not accept any labour charges associated with replacing the unit or parts for any of the following products listed 9 3 Guarantees are provided...

Страница 27: ...oods in the Purchaser s possession and in a manner which enables them to be identified as our goods ii the Purchaser shall immediately return the goods to us should our authorised representative so request All the necessary incidents associated with a fiduciary relationship shall apply d the Purchaser s right to possess the goods shall cease forthwith upon the happening of any of the following eve...

Страница 28: ...ing Products reserve the right to modify products without prior notice It is advisable to check the product technical detail by using the latest design and installation manuals available from our technical support team or on our website Issue 01 11 08 Our appliances are distributed through Gledhill Building Products depots at Blackburn Braintree Bristol Dudley Hemel Hempstead Huntingdon Inverkeith...

Отзывы: