GLAZING VISION Xvent Скачать руководство пользователя страница 6

 

405-OM-UK-001 v1.0 

 09 Jul 2020 

 

Need assistance? +44 (0)1379 658300 [email protected] 

Page 6 of 18 

Basic Operation 

 
The Xvent has three prime positions; closed, vent open and fire open. These correspond to 0º, 45º and 140º lid openings respectively. 
Under normal operating conditions the  Xvent will travel between the vent open and closed positions.  It can be stopped in any 
intermediate position and will respond to the full range of input controls listed below. This means that the Xvent will not open 
beyond 45º under the control of the wall mount control switch. 
 
The Xvent is fitted with an ambient air temperature sensor as standard which is part of the bezel assembly fitted to the inside edge 
of the product. This sensor serves as a backup to the fire alarm system. If the sensor detects ambient air temperature of 72ºC (162°F) 
or more it will trigger fire behaviour. Fire alarm activation will also trigger fire behaviour.  
  
Under fire conditions the Xvent will immediately respond by travelling to the fire open position (140º). This will happen regardless 
of the status of any of the other control devices (eg. remote control). The wall mounted control switch will illuminate intermittent 
green during opening to the fire position. Whilst the fire condition is held the Xvent will remain in the fire open position and will 
ignore all other control devices 

other than a “Fireman’s Override” (if configured) open or close activation.

 

 
Recovery from fire alarm activation must be by manual operation using the wall mounted control switch (this is to allow somebody 
to walk around the building during a fire drill and check each that each individual rooflight is functioning correctly). The fire condition 
must be cancelled/reset first before the wall mounted switch will allow the Xvent to be closed from the fire position. 
 
If activated from the temperature sensor, after a 180 second delay control will be returned to the wall mounted control switch, but 
only when the temperature is below the trigger point and the fire alarm input has been reset. 
 
On resetting the fire alarm, if the temperature sensor has not been triggered, control is immediately returned to the wall mounted 
control switch.  
 

Battery Backup 

The Xvent has back up batteries housed inside its base frame. Under normal conditions the power switching device (also located 
inside the product base) will trickle charge the batteries which are isolated from electrical loading. Only when the incoming supply 
to the switching device is lost will the batteries be switched in automatically.  
 
When operating under batteries all appropriate control inputs will be allowed to close the Xvent. Once closed, or if already closed, 
the Xvent will only open under fire behaviour. This is to prevent unnecessary battery drain. 
 
Whilst running on batteries the Xvent will emit a periodic (one second every minute) audible warning to make the building occupants 
are aware that power has been lost. Battery operation is also indicated by a flashing red LED on the bezel fitted to the inside of the 
product frame. For more information, see the troubleshooting section. 
 

 

 

Содержание Xvent

Страница 1: ...405 OM UK 001 v1 0 09 Jul 2020 www glazingvision co uk 44 0 1379 658300 info glazingvision co uk Xvent...

Страница 2: ...tion Page Introduction 3 Safety Information 4 Basic Operation 6 Controls and Operation 7 Manual Override 9 Troubleshooting 12 Glass Specification and Breakage Instructions 13 Routine Testing and Maint...

Страница 3: ...access A variety of optional extras including a rain sensor thermostat remote control and Building Management System connectivity are available This product is robust and long lasting boasting excelle...

Страница 4: ...amage to the product and its mechanisms It should not be relied upon to prevent injuries Let our experts carry out your routine maintenance with a maintenance contract 44 0 1379 658300 info glazingvis...

Страница 5: ...t may open close unexpectedly e g due to the rain sensor activating and cause injury Do not pull on the cables where they exit the product Doing so may loosen connections result in damage to the produ...

Страница 6: ...arm activation must be by manual operation using the wall mounted control switch this is to allow somebody to walk around the building duringa fire drill and check each that each individual rooflight...

Страница 7: ...ion releasing the switch stops the product in that position Note that the product will stop automatically when it becomes either fully open or closed Status Light The status light will illuminate gree...

Страница 8: ...mote control together and immediately release them The status light on the remote control should turn red for a few seconds and then turn off If it turns green or amber try pressing the three buttons...

Страница 9: ...support system in place unscrew the bolts using a pin torx driver This will disengage the mechanisms from the lid Next unscrew the mechanisms from the base frame and allowing them to be removed from...

Страница 10: ...e legs from slipping when working take care not to knock the support legs out of place Figure 6 Support legs Support Option 3 Chain or Strap This option can be used when there is not enough space for...

Страница 11: ...d by Glazing Vision personnel or Approved Installers If the manual override has been used the product requires re initialising As the Xvent is a safety critical product this will need to be done by a...

Страница 12: ...n close button will clear this condition Continuous red after power on fault recovery Indicates that the product requires initialisation synchronisation Pressing close on the wall mounted switch will...

Страница 13: ...eaning open the product and isolate the power supply then clean the rain sensor The thermostat if specified is reacting to a change in temperature and triggering the product to close Check that the th...

Страница 14: ...ance requirements must be completed and logged on the sheets at the back of this manual Glazing Vision can offer a service maintenance contract please contact us for further details Suitably qualified...

Страница 15: ...nsor if present Disposal at End of Life Glazing Vision design products with ease of recyclability at end of life in mind Many of the main components used are widely recyclable and we encourage you to...

Страница 16: ...fied to BS EN 12101 2 2003 and is fully CE marked Visit our website or contact your technical sales advisor for up to date certification documentation The following label will be affixed to the exteri...

Страница 17: ...ents yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement ye...

Страница 18: ...cement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirement...

Отзывы: