GLAZING VISION Xvent Скачать руководство пользователя страница 11

 

405-OM-UK-001 v1.0 

 09 Jul 2020 

 

Need assistance? +44 (0)1379 658300 [email protected] 

Page 11 of 18 

Stuck Closed 

If the Xvent is stuck in the closed position and will not open electrically, the mechanisms can be disconnected to allow the lid to be 
opened manually. As the building will be watertight, manually overriding the Xvent from the closed position is best done when an 
engineer is on hand to resolve the issue. Manual override needs to be done externally, so access to the rooftop will be required 
(ensure that all necessary safety precautions are followed). Before commencing manual override, ensure that a support system has 
been put into place (see the options above). Do not attempt to manually override the product without a safe working platform. 
 
Remove the plugs on the sides of the lid frame (two each side) and unscrew the override screws using a pin torx driver (see the 
diagram in the previous section). This will disengage the mechanisms from the lid and allow the lid to be manually opened (take 
care 

 it will be heavy). Do not attempt to lift the lid without a safe working platform. Once open, use a support system to keep the 

lid open. Any necessary work can now be carried out. 
 
Please contact Glazing Vision for further  assistance 

 the product will no longer be operational. Once the issue is resolved, the 

product must be re-initialised. 
 

Re-Initialisation 

 

 

This is a safety critical product and must be commissioned by Glazing Vision personnel or Approved Installers. 

 
If the manual override has been used the product requires re-initialising. As the Xvent is a safety critical product, this will need to be 
done by a Glazing Vision Engineer. To do this refer to instructions in the installation manual using the below information as reference. 
Please contact Glazing Vision for assistance. 
 
The following instructions should be followed when setting up the mechanisms for the first time or after replacing them due to 
repair. First check that the unit is receiving the correct power from the Power Supply Unit (PSU).  Use a multimeter to check the 
supply voltage by disconnecting the connection to the batteries and placing the multimeter probes across the DC Input Terminals 
of the DR UPS40 switching device. You should get a reading of 27.2V DC. If the reading is higher or lower than this figure, then the 
output from the PSU should be adjusted accordingly. Voltage adjustment is via a screw potentiometer accessed through the front 
cover (remove small plastic plug first). The PSU is external to the Xvent and can be mounted some way from the product, possibly 
resulting in a slight volt drop. This is a common reason for a slightly lower voltage at the battery terminals and requires adjusting. 
27.2V DC must be the reading at the Xvent to ensure the batteries are given sufficient charge. Ensure that the batteries are connected. 
After confirming that the PSU is correct the fire alarm connection should be tested. Ensure that the Xvent has been connected to the 
fire switch (panel, break glass etc.) which will provide a normally closed safety circuit.

 

 

Содержание Xvent

Страница 1: ...405 OM UK 001 v1 0 09 Jul 2020 www glazingvision co uk 44 0 1379 658300 info glazingvision co uk Xvent...

Страница 2: ...tion Page Introduction 3 Safety Information 4 Basic Operation 6 Controls and Operation 7 Manual Override 9 Troubleshooting 12 Glass Specification and Breakage Instructions 13 Routine Testing and Maint...

Страница 3: ...access A variety of optional extras including a rain sensor thermostat remote control and Building Management System connectivity are available This product is robust and long lasting boasting excelle...

Страница 4: ...amage to the product and its mechanisms It should not be relied upon to prevent injuries Let our experts carry out your routine maintenance with a maintenance contract 44 0 1379 658300 info glazingvis...

Страница 5: ...t may open close unexpectedly e g due to the rain sensor activating and cause injury Do not pull on the cables where they exit the product Doing so may loosen connections result in damage to the produ...

Страница 6: ...arm activation must be by manual operation using the wall mounted control switch this is to allow somebody to walk around the building duringa fire drill and check each that each individual rooflight...

Страница 7: ...ion releasing the switch stops the product in that position Note that the product will stop automatically when it becomes either fully open or closed Status Light The status light will illuminate gree...

Страница 8: ...mote control together and immediately release them The status light on the remote control should turn red for a few seconds and then turn off If it turns green or amber try pressing the three buttons...

Страница 9: ...support system in place unscrew the bolts using a pin torx driver This will disengage the mechanisms from the lid Next unscrew the mechanisms from the base frame and allowing them to be removed from...

Страница 10: ...e legs from slipping when working take care not to knock the support legs out of place Figure 6 Support legs Support Option 3 Chain or Strap This option can be used when there is not enough space for...

Страница 11: ...d by Glazing Vision personnel or Approved Installers If the manual override has been used the product requires re initialising As the Xvent is a safety critical product this will need to be done by a...

Страница 12: ...n close button will clear this condition Continuous red after power on fault recovery Indicates that the product requires initialisation synchronisation Pressing close on the wall mounted switch will...

Страница 13: ...eaning open the product and isolate the power supply then clean the rain sensor The thermostat if specified is reacting to a change in temperature and triggering the product to close Check that the th...

Страница 14: ...ance requirements must be completed and logged on the sheets at the back of this manual Glazing Vision can offer a service maintenance contract please contact us for further details Suitably qualified...

Страница 15: ...nsor if present Disposal at End of Life Glazing Vision design products with ease of recyclability at end of life in mind Many of the main components used are widely recyclable and we encourage you to...

Страница 16: ...fied to BS EN 12101 2 2003 and is fully CE marked Visit our website or contact your technical sales advisor for up to date certification documentation The following label will be affixed to the exteri...

Страница 17: ...ents yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement ye...

Страница 18: ...cement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirements yes no Annual Requirements yes no Battery Replacement yes no Cleaning Requirement...

Отзывы: