Connection of MAX to the mains
When the MAX is connected to other luminaires as shows in the diagrams, the
switch will switch off/on all the luminaires. The light in both tubes of the MAX
can be switched while the battery will be charged uninterruptedly.
• Wiring without switch for main light
• Wiring with 1-poled switch for main light
Mains
L
N
L4
3
N
L1
2
L4
3
N
L1
2
MAX HF-E
Emergency
L4
3
N
L1
2
MAX HF
Not emergency
MAX HF-E
Emergency
Mains
L
N
L4
3
N
L1
2
L4
3
N
L1
2
L4
3
N
L1
2
MAX HF-E
Emergency
MAX HF
Not emergency
MAX HF-E
Emergency
Installation and operation MAX LED
Terminal block
Torque value for screws: 1.8Nm
Type and size of wires that can be used:
Solid wire: From 1.0mm² to 6.0mm²
Stranded wire with or without ferrule: From 0.75mm² to 6.0mm²
There can only be connected one wire on each side of the screw on each
side of each terminal. (totally max 4 wires at each terminal).
Earthing the luminaire
The luminaire must be earthed in the terminal block.
Armored cable must be earthed as described in the drawing.
For external bonding, see picture.
Connection of MAX LED
L1 - N for not emergency (main light)
L4 - N for emergency (charging)
Power supply must be from same line (fuse) for both normal light and emergency.
Earth terminal
Earth lug for
armored cable
Terminal wire
For external bonding