3
5. Connection
!
Use the same external conductor for all detectors and
buttons.
L
Several buttons can be connected to one control input.
L
Illuminated buttons can only be used with a neutral con-
ductor connection.
L
Up to 50 DALI operating devices can be connected to
each master device. Distribute the DALI operating devices
evenly over the 3 external conductors.
L
In the addressable operating mode, lighting channels C1
and C2 can be assigned to the required button inputs S1
and S2 via the remote control.
Individual switching
•
As master, the presence detector detects presence and
brightness and controls lighting.
Master
DALI
DA+ DA–
S1 S2
EVG
P
*
N
L
N
L
EVG
*Only for the "addressable" operating mode
Master/master parallel switching
•
Several masters can be used. Every master controls
its lighting groups according to its own brightness
measurement.
•
Time delays and brightness setpoint values are set indi-
vidually on each master.
•
Presence is detected collectively by all the detectors.
•
Switch up to 10 detectors in parallel.
Master
DALI
DALI
DA+ DA–
S1 S2
P
N
L
N
L
EVG
Master
DA+ DA–
S1 S2
P
N
L
EVG
*
*
*Only for the "addressable" operating mode
Integrating an external DALI relay
•
No more than 1 external DALI relay can be connected on
one single DALI line (IEC 62386-208).
•
The detector automatically detects the DALI relay.
•
Switch-on delay and time delay can be set using the
remote control.
Master
DALI RM
r
DALI
DA+ DA–
S1 S2
EVG
P
N
L
N
L
EVG
*
*Only for the "addressable" operating mode
6. Start-up
Initial operation of LMS MG PIR CLS SENSOR-R
LONG BC (broadcast) → factory setting
L
After the start-up phase (30 s), the detector is ready for
operation.
Initial operation LMS MG PIR CLS SENSOR-R LONG
(addressable), unconfigured system
The operating mode can be switched from broadcast to
addressable with the LMS MG PROGRAM REMOTE BT/App:
Select the <LMS MG PIR CLS SENSOR-R LONG BC> parame-
ter as the detector type.
Open the DALI configuration ("Control commands" menu in
the SendoPro).
Send the <Change over to addressable operating mode>
parameter to the detector.
After the changeover, select <LMS MG PIR CLS SENSOR-R
LONG> as the detector type for further parameterization.
After the first changeover to the addressable operating mode
(LMS MG PIR CLS SENSOR-R LONG), the detector restarts,
identifies all connected DALI lights, assigns short addresses
and manages them in a list.
▻
Depending on the system size, the LED on the detector
flashes (5 x ON briefly every 3 s) for up to 3 min.
If no DALI EBs are connected to the detector or a DALI line is
interrupted
▻ the LED flashes (LED is switched on and flashes 2 x OFF
briefly every 3 s).
If the system is functioning, the detector switches to confi
-
guration mode and waits for the configuration of the lighting
groups.
▻ The LED flashes (2 x ON briefly every 3 s).
As long as the configuration has not been carried out, the
system is in the following operating state:
•
Detector is in broadcast mode.
•
Function is in switching mode (only presence detection,
no light measurement).
•
All lights are controlled with 100% switch-on dimming
value.
•
The operating mode is fully automatic device.