External power supply (Order No.: 5999 00, with UPS or Order
Nos.: 5998 00/5981 00) is installed and ready for operation.
Use the enclosed device plug for connecting.
-
Start-up PC with internet browser, LAN connection and net-
work cable (patch or crossover) are available.
Start-up
1. Connect the power supply to the ward control centre.
2. Connect your start-up PC to the "External LAN" connection
via the network cable.
3. Start the internet browser on your start-up PC. Enter the
IP address 192.168.0.111 into the address bar of the internet
browser.
The start screen of the configuration assistant opens.
Fig.
2: Start screen of the ward control centre
1. Select the language you require for starting the configuration
assistant.
2. Enter "admin" in the administrator name field and "admin" in
the password field.
3. Click on "Log on".
Decide which system type you wish to operate.
Proceed as follows if the device is to be operated in a small sys-
tem (with only this ward control centre):
.
Fig.
3: Defining the system type
1. Select "small system" option.
2. You can save your selection that deviates from the standard
configuration via "Save".
3. Click on "Next".
The overview screen of the configuration assistant opens.
Fig.
4: Overview screen in the configuration assistant
You can now carry out settings to the system. Please read the sys-
tem operating instructions and use the onscreen help in the con-
figuration assistant for details.
To connect the ward control centre to an existing (hospital) net-
work, the "External LAN" connection can be configured in the
configuration assistant via the menu item
Administration / Set
up network access
)).
Warranty
The warranty is provided in accordance with statutory require-
ments via the specialist trade.
Please submit or send faulty devices postage paid together with
an error description to your responsible salesperson (specialist
trade/installation company/electrical specialist trade).
They will forward the devices to the Gira Service Center.
Technical data
Important! Voltage on the ward control centre!
The ward control centre Plus does not have a mains switch. The
ward control centre Plus boots immediately after connection
with the external power supply. This procedure takes up to
60 seconds.
i
Note: IP address range of the start-up PC.
Ensure that the IP address of your start-up PC is between
192.168.0.1 and 192.168.0.254 (but not 192.168.0.111) (subnet
mask: 255.255.255.0). Please consult the "Ethernet basics"
chapter of the system operating instructions for further details of
this.
i
Note: the ward control centres are pre-configured.
Each ward control centre is pre-configured for operation in a
large system (with a system central control unit).
In this case do not specify any further settings in the configura-
tion assistant of the system central control unit.
i
Note: read the system operating instructions.
Become familiar with all the possibilities of the device and the
complete call system. Please read the
system operating instruc-
tions
and use the onscreen help information in the configuration
assistant. You can find the
system operating instructions
in further
language variations on the CD-ROM.
i
Note: connect the nurse call system Plus to an existing
network.
Consult a responsible network administrator before carrying out
network settings.
i
Note: using a time server.
If the ward control centre Plus is not connected to an external
network (e.g. company or hospital network) via the "external
LAN" connection, then the system time of the nurse call system
Plus cannot be automatically sourced via a time server (NTP
server) on the internet.
Operating voltage:
24 V DC
Current consumption:
300 mA
Ambient temperature:
-5 °C to +50 °C
Storage temperature:
-25 °C to +75 °C
Humidity:
max. 90 %
Protection type:
IP 20
Connection terminals:
Ø to 2.5 mm
2
Mounting:
intended for DIN top-hat rail