Adjustment, dimming, walking test
1. For the walking test, turn the brightness and operating
time controller to T. The sensitivity controller cannot be
set on min.. If the full range is not desired, grasp the lens
by the lens bracket and tilt it down a little. If necessary, turn
it to the side.
Caution! Carry out the walking test with the dome removed.
Check the detection area by pacing it off. With each
detection, the LED will light up. If necessary, correct the
alignment of the lens.
2. blank out sources of disturbance: To do this, mask off the
appropriate segments on the lens with the matching
segments of the included screen. If this is not enough,
reduce the sensitivity with the controller.
3. Set operating time: 1 second to 30 minutes.
4. Set brightness: 3 to 1000 Lux or day operation.
Recommended: 15 Lux (middle position of the brightness
controller). Subsequent correction: see Teach-in (Teach-in
of the brightness level is not possible during the walking
test).
5. Attach dome and turn to the right until it stops (The
Tectiv 220° can only be operated with a dome).
Adjustment and test.
8
Содержание Tectiv 220