Switching actuator / blind actuator 16 A Standard & Komfort

Switching actuator, 6-gang / blind actuator, 3-gang Standard
Order no.: 5023 00
Switching actuator, 16-gang / blind actuator, 8-gang Standard
Order no.: 5028 00
Switching actuator, 24-gang / blind actuator, 12-gang Standard
Order no.: 5030 00
Switching actuator, 6-gang / blind actuator, 3-gang Komfort
Order no.: 5033 00
Switching actuator, 16-gang / blind actuator, 8-gang Komfort
Order no.: 5038 00
Switching actuator, 24-gang / blind actuator, 12-gang Komfort
Order no.: 5040 00

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

The device may not be opened or operated outside the technical specifications.

Danger of electric shock. Device is not suitable for disconnection from supply voltage.

Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage
and SELV/PELV together to the device.

For parallel connection of several motors to an output it is essential to observe the correspond-
ing instructions of the manufacturers, and to use a cut-off relay if necessary. The motors may be
destroyed.

Use only venetian blind motors with mechanical or electronic limit switches. Check the limit
switches for correct adjustment. Observe the specifications of the motor manufacturers. Device
can be damaged.

Do not connect any three-phase motors. Device can be damaged.

These instructions are an integral part of the product, and must remain with the end customer.

2

Device components

Figure 1: Device components

(1)

Button field for manual operation

(2)

Programming button and LED

(3)

KNX connection

1 / 9

82402612

23.09.2020

Содержание 5023 00

Страница 1: ...utside the technical specifications Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Do not connect loads fo...

Страница 2: ...out with the aid of the ETS version 5 7 3 and above Intended use Switching of electrical loads with potential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and...

Страница 3: ...us manual mode active Flashing temporary manual control active 8 LED ON relay outputs closed manual operation active 9 Button Short switch on adjust slats or stop Long Move hanging upwards 10 Button S...

Страница 4: ...ey press the actuator returns automatically to bus operation Switching off temporary manual operation The device is in short term manual mode No button press for 5 s or Press 6 button briefly as many...

Страница 5: ...gs The device is in continuous manual mode Press the ALL OFF button 7 Switching outputs All outputs switch off NO operating mode relay output opened NC op erating mode relay output closed Venetian bli...

Страница 6: ...Mount device on DIN rail In secure operation The device certificate must be removed from the device and stored securely Connecting the device Figure 3 Device connection connection example Connect bus...

Страница 7: ...program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operation is not possible Activating the safe state mode S...

Страница 8: ...transport temperature 25 70 C KNX KNX medium TP256 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Current consumption KNX Order no 5023 00 5028 00 5033 00 5038 00 5 18 mA Order no 5030 0...

Страница 9: ...stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Connection torque screw terminals max 0 8 Nm 7 Warranty The warranty is provided in accordance with statuto...