4-channel blind/shutter actuator 230 V~

Installation Instructions

4-channel blind/shutter actuator 230 V~

1/07

Page 1 of 10

System information

This device is a product of the Instabus KNX/EIB-sys-
tem and complies with KNX directives. Technical 
knowledge obtained in Instabus KNX training courses 
is a prerequisite to proper understanding.

The functionality of this device depends on the soft-
ware. Detailed information on loadable software and 
attainable functionality as well as the software itself 
can be obtained from the manufacturer’s product da-
tabase.

Planning, installation and commissioning of the unit is 
effected by means of KNX-certified software. The full 
functionality with KNX commissioning software from 
version ETS3.0d. onwards.

The product database, technical descriptions and 
conversion programs and other utilities are available 
in the Internet at www.gira.de.

Function

Designated use

• Switching of electrically operated blinds, shutters, 

awnings and similar devices for mains voltage 
230 V AC or extra-low voltage 12...48 V DC

• Installation on DIN rail in small distribution boards

Product features

• Manual output control, provisional operation
• Suitable for AC motors 230 V and DC motors 

12...48 V

• Automatic run time detection with 230 V AC drives
• Direct control of blind/shutter position
• Direct control of slat position
• Scene function
• Checkback of run status, blind/shutter position and 

slat position for bus and manual operation

• Forced top and bottom position from primary con-

trol

• Safety function: 3 independent wind alarms, rain 

alarm, frost alarm

• Sun protection function
• Integration into the temperature management of 

the building possible

• Disabling of individual outputs by hand or via the 

bus possible

4-channel blind/shutter actuator 230 V~

Order no.: 1039 00

Safety instructions

Electrical equipment must be installed and fitted 
by qualified electricians only.
Failure to observe the instructions may cause 
damage to the device and result in fire or other 
hazards.
The device is not suited for safe disconnection of 
the mains supply.
For parallel connection of several drives to an 
output it is indispensable to observe the corres-
ponding instructions of the manufacturers. 
There is otherwise risk of irreparable damage to 
the drives.
Use only blinds/shutters with mechanical or 
electronic limit switches. Check the limit switch-
es for correct adjustment.
Do not connect mains voltage consumers to-
gether with SELV/PELV consumers to the same 
shutter actuator.
These operating instructions are part of the pro-
duct and must be left with the final customer.

i

State of delivery: output control via keypad 
enabled, provisional operation.

Содержание 1039 00

Страница 1: ...run time detection with 230 V AC drives Direct control of blind shutter position Direct control of slat position Scene function Checkback of run status blind shutter position and slat position for bus...

Страница 2: ...Fig 2 5 indicate the out put states Off output is off On output is on up or down Flashing slowly output in manual control mode Flashing fast output disabled in permanent manual control mode Modes of o...

Страница 3: ...y for at least 5 s LED is on LEDs A1 are flashing permanent manual mode is activated Deactivating the permanent manual control mode The device is in the permanent manual control mode Press the key for...

Страница 4: ...5 s The selected output A1 A4 is enabled The LEDs of the selected output are flashing slow ly Activate the bus mode deactivate the permanent manual control mode Information for qualified electricians...

Страница 5: ...ation for qualified electricians The running time detection function is activated in the software The blinds shutters are not blocked Connect the bus line to the bus terminal Fig 3 Connect the mains v...

Страница 6: ...the label Fig 7 7 Sliding on the protective cap To protect the bus lines against dangerous voltages at the connecting terminal slide on the protective cap Lead out the bus line at the rear of the devi...

Страница 7: ...orehand The running times must be stored in undisturbed conditions i e without any control operations being performed and in the ab sence of wind snow and obstacles The automatic running time detectio...

Страница 8: ...ge temperature 25 C 70 C Mounting width 72 mm 4 modules Weight approx 300 g Help in case of trouble Manual control with keypad not possible Cause 1 Manual control mode not programmed Program the devic...

Страница 9: ...nic limit switches are being used Deactivate the automatic running time de tection Correct the electrical connection and re move the N conductor Blind shutter does not move to limit position po sition...

Страница 10: ...ee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service department giving a brief description of the fault Gira Giersiepen GmbH Co KG Servic...